Permit Information
Permit NumberBLD11-02864
StatusFinaled
Name JASON HAGER
Site Address 11770 W PRESIDENT DR Unit: I
Project Name 
Customer Number 
ePlanReviewNo
Description
**(ENVIROTECH INDUSTRIES)**(Suite I) Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 1,585 square foot manufacturing tenant space. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. This building was originally constructed in Ada County’s jurisdiction in 1997, it was later annexed into the City of Boise in 1999. TLW
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/7/20122/8/20122/8/2012APASS
DetailsMike Jordan
j d Phone #: ###-####. Ok for perm occ.
FIRE-Final Inspection2/7/20122/8/20122/8/2012APASS
DetailsTroy Cobbley
life safety passed
FIRE-Conference2/3/20122/3/20122/3/2012PDONE
DetailsTroy Cobbley
To final life safety the dead bolt needs to be removed from the rear door. The thumbturn dead bolt needs to be replace with keyed at the main exit as well as providing the sticker over the door.
FIRE-Final Inspection12/20/201112/21/201112/21/2011AFAIL
DetailsTroy Cobbley
Provide inspection and final sign off for the outstanding fire alarm permit FIR02-00290. (sentry security systems ###-####), Remove the thumbturn lock from the main exit and rear exit door. Provide sticker at the main exit door. provide one 2A, 10BC fire extinguisher with current inspection tag mounted in a normal path of travel no higher than 5', provide for annual inspection of the fire sprinkler system.