Permit Information
Permit NumberBLD12-00091
StatusFinaled
Name RAM CONSTRUCTION
Site Address 2466 N BOGUS BASIN RD
Project NamePENDER VILLAGE CONDOS
Customer Number 
ePlanReviewNo
Description
***(PENDER VILLAGE CONDOS - Mechanical room)***This interior remodel project is for the conversion of an existing closet main level elevator lobby into a 2-hour rated elevator mechanical room. Hat channel and 2 layers of 5/8thpe X gyp are to be added to the ceiling of the closet (UL WIJ-2.1 for floor ceiling assembly)and 2 layers of 1" (inch) type X gyp ( UL U366 ) with H-channel / studs at the joints of the drywall (per the UL details attached) are to be added to the walls of the closet interior side. 90 minute rated double doors are also added to the closet. A surface mount smoke fire damper is to be added at the ceiling line over the vent fan housing and the vent duct will run horizontally through the 2nd level floor system to the outside. See Damper detail sheet A/3-1. This building is fully fire sprinklered per NFPA 13-R for story increase. All per the approved plans, details and attachments. 2-24-2012 pep
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/3/20131/3/20131/4/2013PDONE
DetailsTony Young
Rob--Please call for access information Phone #: ###-####
DOC - Permit Finaled1/3/20131/3/20131/3/2013PPASS
DetailsTony Young
done
BLD-Final1/2/20131/2/20131/3/2013PDONE
DetailsTony Young
Rob--Please call for access information Phone #: ###-####
FIRE-Final Inspection12/24/201212/24/201212/24/2012PPASS
DetailsForrest France
Fire life safety approved for final status.
FIRE-Final Inspection9/6/20129/6/20129/6/2012PFAIL
DetailsTroy Cobbley
A fire alarm permit is required for the new and relocated devices (smoke and heat detectors, electrical shunt trip) and their interconnection with the existing fire alarm system. It appears that fire alarm work has already been performed since the elevator recall devices have been relocated to the new mechanical closet and new cover plates installed in the previous locations. Activation of the new fire/smoke damper needs to be addressed as well and its interconnection with the fire alarm system. The permit requirement applies to all four buildings and related building permits BLD12-00090, 91, 92 & 93. Also the emergency lighting at the 2460 address did not function when tested in the first floor lobby. Fire extinguishers appear ok.
BLD-Final7/23/20127/26/20127/27/2012PDONE
DetailsTony Young
rob Phone #: ###-####
DOC - Permit Finaled7/27/20127/27/20127/27/2012PPASS
DetailsTony Young
BLD-Framing/Rough-in7/23/20127/23/20127/23/2012PPASS
DetailsTony Young
rob Phone #: ###-####