DOC - Permit Expired | | | 3/21/2013 | | DONE |
Tisha Gallop
|
|
|
exceeded time limit of expiration date, new tenant moved in under Bld13-00614
|
BLD-Final | 4/20/2012 | 4/24/2012 | 4/24/2012 | P | NR |
Mike Jordan
|
|
|
Meghan or Julie Phone #: ###-####. Fire/life/safety failed.
|
FIRE-Final Inspection | 4/20/2012 | 4/23/2012 | 4/23/2012 | P | FAIL |
Troy Cobbley
|
|
|
Provide racking permit for the racks that exceed 8'-0" in height. Storage exceeding 12'-0" in height required verification that the sprinkler system is adewuately designed for the stored commodity. This could require high pile storage permit. Provide access to verify annual inspection for fire sprinkler riser and functioning fire alarm system.
|