Permit Information
Permit NumberBLD12-01735
StatusFinaled
Name ROGER THOMPSON
Site Address 5717 W ALBATROS ST
Project NameTitan Technologies Inc
Customer Number 
ePlanReviewNo
Description
**(TITAN TECHNOLOGIES, Inc)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 6,500 square foot repair facility. This building was built in Ada County’s jurisdiction around 1988. The building was later annexed into the City of Boise in 2006. There are no changes to occupancy or use under this permit. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final7/26/20127/27/20127/27/2012PPASS
DetailsJim Storey
Please call for access -- Sam Phone #: ###-####
FIRE-Final Inspection7/26/20127/27/20127/27/2012APASS
DetailsTroy Cobbley
Life safety passed.
BLD-Final7/9/20127/11/20127/11/2012ADEFR
DetailsJim Storey
after 9am--call 1/2 hr prior--Dean Phone #: ###-#### 408 insp.// pending fire.
BLD-Conference7/10/20127/10/20127/10/2012PPASS
DetailsTom Arcoraci
DEAN Phone #: ###-#### appears ok after fire
FIRE-Final Inspection7/9/20127/10/20127/10/2012AFAIL
DetailsTroy Cobbley
Resubmit plans showing the actual floor layout (mezzanines), resubmit plans and information on the paint room and plating room that shows compliance with IFC chapter 15, provide single action hardware at the exit doors other than the main exit. This includes removing the dead bolts. Remove material/products obstructing doors.