BLD-Final | 2/11/2013 | 2/11/2013 | 2/11/2013 | P | PASS |
Mike Jordan
|
|
|
fred Phone #: ###-####. ok for perm occ. tenant has deleted the use of the curtain and has gone with a standard office partition.
|
BLD-Final | 1/31/2013 | 2/1/2013 | 2/1/2013 | A | PART |
Mike Jordan
|
|
|
call first...need temp sign off//Faraidon Phone #: ###-####. OK for temp occ. Must reschedule another final when owner has gotten manufactures paperwork showing that proposed curtain meets the requirements of IBC sec 803.1.2 room corner test.
|
FIRE-Final Inspection | 1/28/2013 | 1/28/2013 | 1/28/2013 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
FIRE-Final Inspection | 1/15/2013 | 1/16/2013 | 1/16/2013 | A | FAIL |
Troy Cobbley
|
|
|
Provide exit sign at the north exit, repair the exit sign in the kitchen, provide occupant load signs, provide fire extinguishers and provide re-certification for the hood suppression system when all of the appliances have been installed.
|