Permit Information
Permit NumberBLD13-00182
StatusFinaled
Name PETRA INC
Site Address 5301 E WARM SPRINGS AVE
Project NameThe Terraces of Boise
Customer Number 
ePlanReviewNo
Description
The Terraces of Boise - Main Building Wings C, D and E - To construct a new 94,150 square foot, three story, wood framed independent living apartment building. This is a wing of a larger building, with wings separated by two-hour fire walls. This building is being constructed on top of an underground parking garage. The parking garage is separated from the above apartment building by a three-hour horizontal separation. This building is fully fire sprinklered. The sprinklers are used for area increase. First Floor: 35,560 sq. ft. with 18 apartments and common Areas. The common area contains the main entry with porte cochere, vestibule and lobby; administrative offices, fitness and social gathering areas, including a bistro and public restrooms. Second Floor: 32,855 sq. ft. with 24 apartments and small lounge area above the lobby. Third Floor: 25,735 sq. ft. with 17 apartments. All floors contain mechanical/electrical and housekeeping areas. Wings C and D will be constructed as part of Phase I and Wing E will be constructed as part of Phase II. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/13/20161/13/20161/13/2016PPASS
DetailsJim Storey
DOC - Permit Finaled1/13/20161/13/20161/13/2016PPASS
DetailsJim Storey
BLD-Aging Inspection1/11/20161/11/20161/11/2016 PASS
DetailsJim Storey
temp ok
FIRE-Final Inspection11/10/201511/10/201511/10/2015PPASS
DetailsJim Page
Associated FIR permits with this BLD permit complete, life fire safety passed/complete
BLD-Final10/6/201510/7/201510/7/2015APASS
DetailsJim Storey
Gary Phone #: ###-#### tco ok for bld e per aproved plan.
FIRE-Final Inspection10/6/201510/7/201510/7/2015APART
DetailsThomas Walsh
Fire and life-safety inspection for wing E, including inspection and test of exit signs and emergency egress lighting, run off the generator. Added (3) exit signs from last inspection - all passed/tested OK, including exit discharge lighting.
Fire extinguishers OK and fire wall separating wing E from F&G installed on all floors. Tested Area of Refuge communication systems, however the basement and level 2A stations are not operating. Will followup on these with F&G inspections.
Temp. occupancy for Wing E approved by this office. Fire alarm and fire sprinkler systems are to remain in-service at all times.
FIRE-Final Inspection10/5/201510/6/201510/6/2015PPART
DetailsThomas Walsh
Fire and life-safety inspection for Wing E, including exit signs and emergency exit lighting. Need to add an exit sign at the east end of the egress corridor (all floors) directing residents to stair F1 (separation stair between wings E & F). Some other exit signs did not light on battery. A retest will be conducted after these changes are made.
BLD-Final10/5/201510/6/201510/6/2015ANR
DetailsJim Storey
Gary Phone #: ###-####
BLD-Final10/5/201510/5/201510/5/2015PDEFR
DetailsJim Storey
Gary Phone #: ###-####
FIRE-Conference8/28/20158/28/20158/28/2015PDONE
DetailsThomas Walsh
Meeting with GC (Ben-Petra) to review Wing E being added to TCO.
BLD-Aging Inspection8/12/20158/12/20158/12/2015 NR
DetailsJim Storey
BLD-Final6/12/20156/17/20156/17/2015APART
DetailsJim Storey
JC Phone #: ###-####
FIRE-Final Inspection6/12/20156/15/20156/15/2015APASS
DetailsThomas Walsh
Final inspection for FLS of Wings C and D - note Wing E has been removed from this permit.
Fire extinguishers - OK
Exit signage and emergency lighting tested OK (off generator).
Fire lane marking OK
Knox Box installed at main lobby and FD called to lock keys into box.
EVAC signs are temporary while permanant signs to be installed by owner.
BLD-Final6/12/20156/15/20156/15/2015ACANC
DetailsJim Storey
Jesus Phone #: ###-####
BLD-Final6/12/20156/15/20156/15/2015ACANC
DetailsBob Archibald
JC// wing C Phone #: ###-####
BLD-Final6/11/20156/12/20156/12/2015PNR
DetailsTony Young
JC// wing C Phone #: ###-####,, conference only,, need trades 1st,, walk through only
BLD-Final6/9/20156/10/20156/10/2015PNR
DetailsJim Storey
John Phone #: ###-####
BLD-Ceiling Grid Inspection5/22/20155/26/20155/26/2015ANR
DetailsJim Storey
Gary Phone #: ###-####
BLD-Ceiling Grid Inspection4/30/20155/1/20155/1/2015PPASS
DetailsJim Storey
E-Wing Hallway; Gary Phone #: ###-####
BLD-Ceiling Grid Inspection4/30/20155/1/20155/1/2015PPASS
DetailsJim Storey
2nd Floor; Gary Phone #: ###-####
BLD-Framing/Rough-in4/29/20154/29/20154/29/2015PNR
DetailsJim Storey
gary - 3rd floor -- E Coord Phone #: ###-####
BLD-Ceiling Grid Inspection4/16/20154/16/20154/16/2015PPASS
DetailsJim Storey
John// D, 1st floor Phone #: ###-#### ceillings ok to cover
BLD-Ceiling Grid Inspection4/15/20154/15/20154/15/2015PPART
DetailsJim Storey
to cover // John Phone #: ###-#### ceilling ok 3 pipe fire chalk/ holes sealed
BLD-Energy code compliance4/9/20154/9/20154/9/2015PPASS
DetailsJim Storey
fire to cover. first floor E // Gary Phone #: ###-#### top of 3hr ok
BLD-Ceiling Grid Inspection4/7/20154/8/20154/8/2015APASS
DetailsJim Storey
Wing D 2nd floor. To cover late morning // Gary Phone #: ###-####
BLD-Energy code compliance4/7/20154/7/20154/7/2015PPASS
DetailsJim Storey
Gary-E hallway 2nd floor Phone #: ###-####
BLD-Other4/2/20154/2/20154/2/2015PPASS
DetailsJim Storey
Gary// soffit inspection 1st floor bldg. E Phone #: ###-####
BLD-Other3/13/20153/16/20153/16/2015PPASS
DetailsJim Storey
Gary-soffit-would like as late as possible-insepction-2nd floor of the E wing Phone #: ###-####
BLD-Other3/13/20153/13/20153/13/2015PFAIL
DetailsJim Storey
Gary-soffit-would like as late as possible-insepction-2nd floor of the E wing Phone #: ###-####
BLD-Wall cover3/6/20153/6/20153/6/2015PPASS
DetailsJim Storey
Gary-soffits-E wing 3rd floor Phone #: ###-####
BLD-Conference3/5/20153/6/20153/6/2015APASS
DetailsJim Storey
Gary-soffits-E wing 3rd floor Phone #: ###-####
BLD-Framing/Rough-in3/5/20153/5/20153/5/2015PPASS
DetailsJim Storey
Gary-soffits-E wing 3rd floor Phone #: ###-#### ok to cover
BLD-Other2/26/20152/27/20152/27/2015PPASS
DetailsJim Storey
Gary// D 2nd floor-fire soffit Phone #: ###-####
BLD-Energy code compliance2/13/20152/17/20152/17/2015APASS
DetailsJim Storey
Gary// E 4th floor Phone #: ###-#### f 4th ok airseal// e 1st ceillings ok insulation
BLD-Framing/Rough-in2/13/20152/17/20152/17/2015APASS
DetailsJim Storey
Hard lid ceilings Bldg D - John Phone #: ###-#### billing rm 107 strucral repair complet ok/ ceilling soffits ok to cover
BLD-Framing/Rough-in2/12/20152/13/20152/13/2015APART
DetailsTony Young
Hard lid ceilings Bldg D - John Phone #: ###-####,, not ready,, walk through conference only
BLD-Framing/Rough-in2/11/20152/12/20152/12/2015APASS
DetailsJim Storey
First floor of E building // Gary Phone #: ###-#### air sealant 1,2,3 floors ok to insulate walls// 1st floor first six rooms ceillings ok to gyp bld d
BLD-Energy code compliance2/10/20152/11/20152/11/2015ADEFR
DetailsJim Storey
First floor of E building // Gary Phone #: ###-####
BLD-Other2/4/20152/5/20152/5/2015APASS
DetailsJim Storey
Gary// one hour assembly inspecton for D corridor Phone #: ###-#### corridor side of occupancy wall installed fire dampers pending// colm. wip gyp protection.
BLD-Other1/29/20151/30/20151/30/2015APASS
DetailsJim Storey
Dimising wall, 1st Bldg E - Gary Phone #: ###-####
BLD-Ceiling Grid Inspection1/27/20151/28/20151/28/2015APASS
DetailsJim Storey
Gary// E wing-2nd floor Phone #: ###-#### ceilling insulation and rc channel ok
BLD-Energy code compliance1/20/20151/20/20151/20/2015PPASS
DetailsJim Storey
JC- 1st floor wing E Phone #: ###-#### pending mech submital
BLD-Energy code compliance1/14/20151/15/20151/15/2015APART
DetailsJim Storey
JC-east floor E wing Phone #: ###-#### ok to sheer
BLD-Energy code compliance1/9/20151/9/20151/9/2015PPASS
DetailsJim Storey
exterior insultaion // JC Phone #: ###-#### 2nd and third e
BLD-Framing/Rough-in1/5/20151/6/20151/6/2015PPART
DetailsJim Storey
JC-e wing trusses Phone #: ###-####
BLD-Other12/23/201412/24/201412/24/2014ANR
DetailsJim Storey
fire colcking // Jc Phone #: ###-####
BLD-Energy code compliance12/23/201412/24/201412/24/2014ANR
DetailsJim Storey
Jc Phone #: ###-####
BLD-Framing/Rough-in12/22/201412/23/201412/23/2014APART
DetailsJim Storey
Gary Phone #: ###-#### 2nd floor coridor ok
BLD-Framing/Rough-in12/18/201412/19/201412/19/2014APART
DetailsJim Storey
John// BLDG. D Phone #: ###-#### broken truss/ hangers/ fire blk/ ok to insulate exterior walls
BLD-Other12/18/201412/19/201412/19/2014APASS
DetailsJim Storey
John//1st floor soffitt inspection on C Phone #: ###-#### ok to cover
BLD-Framing/Rough-in12/17/201412/18/201412/18/2014ANR
DetailsJim Storey
Gary-soffit cover inspection first floor C Phone #: ###-####
Extend Permit 90/180 days12/15/201412/15/201412/15/2014APASS
DetailsJim Storey
exterior ok to cover
BLD-Framing/Rough-in12/9/201412/10/201412/10/2014APASS
DetailsJim Storey
late morning or early afternoon no rush//Gary Phone #: ###-#### e ok to cover ceilling of corridor
BLD-Wall cover12/2/201412/3/201412/3/2014APASS
DetailsJim Storey
Gary Phone #: ###-#### 2nd floor ceilling drops ok to cover.
BLD-Wall cover12/3/201412/3/201412/3/2014APASS
DetailsJim Storey
4th floor coridor ok to cover
BLD-Wall cover12/1/201412/2/201412/2/2014PDEFR
DetailsJim Storey
as early in pm as possible//Gary Phone #: ###-#### out of time
BLD-Other11/28/201412/1/201412/1/2014AFAIL
DetailsJim Storey
fire colt. // JC Phone #: ###-####
BLD-Ceiling Grid Inspection11/28/201411/28/201411/28/2014ANR
DetailsJim Storey
brett ###-#### - wing c 2nd floor
BLD-Wall Bracing11/28/201411/28/201411/28/2014APASS
DetailsJim Storey
brett ###-#### - exterior bld-e
BLD-Other11/19/201411/20/201411/20/2014APASS
DetailsJim Storey
ceiling insulation// JC Phone #: ###-####
BLD-Wall cover11/13/201411/13/201411/13/2014APASS
DetailsJim Storey
north wall ok to cover exterior.
BLD-Wall Bracing11/7/201411/10/201411/10/2014PPART
DetailsJim Storey
JC Phone #: ###-#### unit septration walls ok to cover.
BLD-Framing/Rough-in11/4/201411/4/201411/4/2014PPASS
DetailsJim Storey
JC Phone #: ###-#### truss repair ok
BLD-Wall Bracing11/4/201411/4/201411/4/2014PPASS
DetailsJim Storey
JC Phone #: ###-#### 2nd floor interior ok
BLD-Energy code compliance10/30/201410/31/201410/31/2014APASS
DetailsJim Storey
JC Phone #: ###-#### 3hird floor/ 2 nd floor ceillings 2nd floor c wing ok to cover.
BLD-Framing/Rough-in10/30/201410/31/201410/31/2014APASS
DetailsJim Storey
3st fl C wing soffits - JC Phone #: ###-####
BLD-Energy code compliance10/29/201410/30/201410/30/2014APART
DetailsJim Storey
JC Phone #: ###-####
BLD-Framing/Rough-in10/30/201410/30/201410/30/2014PFAIL
DetailsJim Storey
Late afternoon for 3st fl C wing soffits - JC Phone #: ###-#### need fire stopping
BLD-Framing/Rough-in10/28/201410/28/201410/29/2014PNR
DetailsJim Storey
JC Phone #: ###-####
BLD-Other10/23/201410/24/201410/24/2014APASS
DetailsJim Storey
JC-fire soffitt Phone #: ###-#### soffits ok 4th floor
BLD-Energy code compliance10/16/201410/17/201410/17/2014APART
DetailsJim Storey
2nd fl C wing - Gary Phone #: ###-#### air seal for iecc exterior wall and floor ok.
BLD-Energy code compliance10/6/201410/7/201410/7/2014ANR
DetailsJim Storey
JC Phone #: ###-#### need truss co. to provide field review of truss mods and provide letter of aproval.
BLD-Framing/Rough-in10/2/201410/3/201410/3/2014AFAIL
DetailsJim Storey
jc - late morning Phone #: ###-#### truss patch 409/407 and third floor/ header at bearing/ i joist hole from bearing 39 x 6 dia/ fire treat roof patch/ rated ceilling unusable spaces/ firestop per listing.
BLD-Framing/Rough-in10/1/201410/2/201410/2/2014ANR
DetailsDave Hannah
Gary-remainder of C wing 3rd floor Phone #: ###-#### needs to install air seal
BLD-Framing/Rough-in9/26/20149/29/20149/29/2014PCANC
DetailsJim Storey
Gary Phone #: ###-####
BLD-Energy code compliance9/25/20149/26/20149/26/2014APASS
DetailsDave Hannah
Gary Phone #: ###-#### c wing rms 307thru 310
BLD-Framing/Rough-in9/22/20149/23/20149/23/2014APART
DetailsDave Hannah
307-308-309-310 and C wing for energy and framing // JC Phone #: ###-#### ok to cover ceilings
BLD-Energy code compliance9/19/20149/22/20149/23/2014PPART
DetailsDave Hannah
Gary Phone #: ###-#### air seal 4 rooms third floor c wing
BLD-Framing/Rough-in9/11/20149/12/20149/15/2014ANR
DetailsJim Storey
JC-1:00 Phone #: ###-####
BLD-Framing/Rough-in9/12/20149/15/20149/15/2014PNR
DetailsJim Storey
Late afternoon - Gary Phone #: ###-#### need fire spk
BLD-Framing/Rough-in9/10/20149/11/20149/11/2014PDEFR
DetailsDave Hannah
JC-1:00 Phone #: ###-#### resceduled for 8/12 out of time today
BLD-Wall Bracing8/27/20148/27/20148/27/2014PPART
DetailsJim Storey
JC Phone #: ###-####missing misc. straps for exterior wall bracing/ interior wall bracing ok.
BLD-Wall Bracing8/21/20148/21/20148/21/2014PPART
DetailsJim Storey
Jason Phone #: ###-#### coridor ok to pre gyp/ exterior ok to cover/1st floor
BLD-Conference6/24/20146/25/20146/25/2014APASS
DetailsJim Storey
JC Phone #: ###-#### aproved rfi 00206/ copy archived
BLD-Framing/Rough-in6/23/20146/24/20146/24/2014ADEFR
DetailsJim Storey
JC Phone #: ###-####
BLD-Framing/Rough-in5/23/20145/23/20145/23/2014PPART
DetailsJim Storey
JC Phone #: ###-####
BLD-Other5/2/20145/5/20145/5/2014APASS
DetailsJim Storey
j.c. - slab on deck Phone #: ###-#### beam rebar per design