FIRE-Final Inspection | 4/22/2013 | 4/23/2013 | 4/23/2013 | A | PASS |
Forrest France
|
|
|
Correction items verified for completion. Fire life safety passed.
|
BLD-Final | 4/22/2013 | 4/23/2013 | 4/23/2013 | P | PASS |
Jim Storey
|
|
|
brad Phone #: ###-####
|
FIRE-Final Inspection | 4/22/2013 | 4/22/2013 | 4/22/2013 | P | CANC |
Troy Cobbley
|
|
|
I left message on brads Phone #: ###-#### that I was over booked and would re-schedule his inspection for tomorrow morning.
|
BLD-Final | 4/3/2013 | 4/5/2013 | 4/5/2013 | P | NR |
Jim Storey
|
|
|
Wendell Phone #: ###-####
|
FIRE-Final Inspection | 4/5/2013 | 4/5/2013 | 4/5/2013 | P | NR |
Forrest France
|
|
|
Ref. correction items
|
FIRE-Final Inspection | 4/3/2013 | 4/4/2013 | 4/4/2013 | P | FAIL |
Forrest France
|
|
|
Correction items include; repair EM lights at several locations, post additional fire extinguishers per ft2 and travel distance requirements, provide approved hardware at the main entry/exit of suite C, reverse lockset at suite C interior office door.
|