Permit Information
Permit NumberBLD13-00861
StatusFinaled
Name KANA GIRLS HAWAIIAN BBQ
Site Address 3912 W STATE ST
Project NameKANA GIRLS HAWAIIAN BBQ
Customer Number 
ePlanReviewNo
Description
(KANA GIRLS HAWAIIAN BBQ) Application for inspection to determine the requirements for the issuance of a certificate of occupancy. No new work is allowed under this permit with the exception of a new handwash sink required by CDHD. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/30/20134/30/20135/1/2013PPASS
DetailsTony Young
Kana Tyler Phone #: ###-####
FIRE-Final Inspection4/29/20134/30/20134/30/2013APASS
DetailsTroy Cobbley
life safety passed
FIRE-Final Inspection4/25/20134/29/20134/29/2013PCANC
DetailsTroy Cobbley
Hood suppression system is not ready yet. To be rescheduled. kana Phone #: ###-####
FIRE-Final Inspection4/22/20134/25/20134/25/2013PFAIL
DetailsTroy Cobbley
The hood suppression system is going to take so work to make code compliant per the contractor. When this work is complete the life safety can be finaled.
FIRE-Final Inspection4/18/20134/19/20134/19/2013AFAIL
DetailsTroy Cobbley
Repair the exit sign at the rear exit, provide exit sign at the front exit, provide emergency lighting in the Dining area, provide sticker at the main exit, provide re-certification/annual inspection for the hood suppression system, provide one 2a,10bc fire extinguisher and a K class for the kitchen, provide occupant load sign for "67" at the main exit in the Dining room.