FIRE-Final Inspection | 10/8/2013 | 10/8/2013 | 10/8/2013 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 9/16/2013 | 9/18/2013 | 9/18/2013 | A | NR |
Mike Jordan
|
|
|
Christine Phone #: ###-####. Fire/life/safety failed inspection.
|
FIRE-Final Inspection | 9/16/2013 | 9/18/2013 | 9/18/2013 | A | FAIL |
Troy Cobbley
|
|
|
Just need the "request to exit" button installed and tested to final the life safety.
|
FIRE-Conference | 7/10/2013 | 7/11/2013 | 7/10/2013 | A | DONE |
Troy Cobbley
|
|
|
I stopped at the job site and spoke to Christine. I let her know that for the temporary to be official the proper documentation needs to be processed by the permit tech's down town. As far as the racking permit she stated that she is still waiting on Treasure Valley Fire to provide her with a sprinkler system analysis. I left her some competitors phone numbers and I also left jeff with TVFP a voice message. Also upon looking into the warehouse I saw that the racks were being used so I reminded Christine that per our previous agreement the area under them could be used (floor space) but the racks them selves could not. She said that she had misunderstood me. She is going to remove the product.
|
BLD-Final | 7/3/2013 | 7/3/2013 | 7/3/2013 | P | PART |
Mike Jordan
|
|
|
Matt Phone #: ###-####. Temp occ. granted. Will be ok for perm occ. once fire/life/safety sings perm.
|
FIRE-Final Inspection | 7/2/2013 | 7/3/2013 | 7/3/2013 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy is approved by both scott and romeo until the access control and the high piled storage/racking is addressed.
|
FIRE-Final Inspection | 6/27/2013 | 6/27/2013 | 6/27/2013 | P | FAIL |
Troy Cobbley
|
|
|
Repair the high exit sign on the east wall, remove or repair the exit sign on the west wall in the warehouse, provide racking permit for the racking that exceeds 8', relocate the exit sign at the main exit to be over the door, provide request to exit button and verification of tie in to the facp of the access controled egress doors, provide small documents and mount the fire extinguishers as discussed.
|
BLD-Framing/Rough-in | 6/13/2013 | 6/14/2013 | 6/14/2013 | A | PASS |
Mike Jordan
|
|
|
jamel Phone #: ###-####. INterior steel stud walls for tenant seperation only.
|
BLD-Framing/Rough-in | 6/12/2013 | 6/13/2013 | 6/13/2013 | P | NR |
Mike Jordan
|
|
|
JEMEL Phone #: ###-####. Provide approved plans.
|