Permit Information
Permit NumberBLD13-02595
StatusFinaled
Name VERTICAL EVOLUTION
Site Address 4270 N EAGLE RD
Project NameMcNeel Eye Center
Customer Number 
ePlanReviewNo
Description
McNeel Eye Center - Permit for the construction of a new 3,367 sq. ft. one story wood framed office building including related site work. The building consists of a 3,367 sq. ft. first story and a 215 sq. ft. mezzanine to include B and M occupancies. There are four restrooms on the first story with two restrooms serving private offices and two fully accessible single user restrooms serving the public and staff. The areas to either side of the mezzanine include attic and mechanical rooms neither of these areas is approved for storage or any other use. In the event that either area is altered for other than the approved uses a new evaluation will need to be done based on the code in effect at the time of the alteration. All work per the approved plans and any notations and the attached plan review report. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final10/24/201410/27/201410/27/2014PPASS
DetailsJim Sly
Brandon Phone #: ###-####
FIRE-Final Inspection10/24/201410/27/201410/27/2014APASS
DetailsTroy Cobbley
Life safety passed
FIRE-Final Inspection10/20/201410/21/201410/21/2014PNR
DetailsForrest France
Incompleted C/N items. Exit discharge lighting not yet installed.
BLD-Conference8/5/20148/5/20148/5/2014PDONE
DetailsJim Sly
Received TCO sign off from zoning/landscape. Looking for structural TCO.
Hired new sider.
Hired new landscaper.
Roofer working and awaiting upper siding. Phone #: ###-#### Inspection requested via web by Brandon Juarez
BLD-Final8/5/20148/5/20148/5/2014PPART
DetailsJim Sly
OK for Temp Occ. OK for Perm Occ. when Roofing, Siding, is done. Fire, and zoning is finaled.
BLD-Final7/29/20147/29/20147/29/2014PNR
DetailsJim Sly
Requesting a TCO meeting. client needs to start moving in. Sider quit and roofer quit. need your help. Phone #: ###-#### Inspection requested via web by Brandon Juarez
Brandon to obtain Occ request card and complete req finals.
FIRE-Final Inspection7/29/20147/29/20147/29/2014PPART
DetailsTroy Cobbley
A temporary occupancy was given, with scott arellano's permission, until the correct exit discharge lights have been ordered, installed and tested.
FIRE-Final Inspection7/24/20147/25/20147/25/2014AFAIL
DetailsTroy Cobbley
Repair exit signs, provide indicator on the main exit door. Provide fire extinguisher on the upper level. Provide listed for the enviroment exit discharge lights. Provide building address
FIRE-Final Inspection7/16/20147/17/20147/17/2014AFAIL
DetailsCraig D. Hanson
Need emergency lighting and exit signs to illuminate. Hardware needs installed on back door. breaker box needs cover and labeles. outlets need covers. Extinguisher to be mounted in back hall.
BLD-Energy code compliance6/16/20146/16/20146/16/2014PPASS
DetailsMike Jordan
brandon Phone #: ###-####
BLD-Framing/Rough-in6/11/20146/11/20146/11/2014PPASS
DetailsJim Sly
brandon - ###-####
BLD-Energy code compliance6/10/20146/10/20146/10/2014PNR
DetailsJim Sly
Electrical inspection AM. Then cover shear panels for PM framing and energy inspection Phone #: ###-#### >> Inspection requested via web by Brandon Juarez
BLD-Framing/Rough-in6/10/20146/10/20146/10/2014PPEND
DetailsJim Sly
Electrical inspection AM. Then cover shear panels for PM framing and energy inspection Phone #: ###-#### >> Inspection requested via web by Brandon Juarez
Walk thru.....
BLD-Wall Bracing5/1/20145/1/20145/1/2014PPASS
DetailsJim Sly
EARLY PM OK. We need a sheer inspection so we can cover some sections of the building. we also want to install Tyvek over the exterior sheer. talk to KENT on site
thanks - Brandon ###-#### Phone #: ###-#### >> Inspection requested via web by Brandon Juarez
BLD-Foundation2/24/20142/25/20142/25/2014APASS
DetailsJim Sly
FOUNDATION WALL INSPECTION ON BUILDING Phone #: ###-#### >> Inspection requested via web by Brandon Juarez
BLD-Footing2/18/20142/19/20142/19/2014PPASS
DetailsJim Sly
Late AM or Early PM requested
Concrete expected at 1:30 pm Phone #: ###-#### >> Inspection requested via web by Brandon Juarez