DOC - Permit Expired | | | 3/6/2014 | | DONE |
Barbara Stitt
|
|
|
Temp occupancy is expired and the tennant has moved out of the space prior to 3/4/14 per Mike Jordan
|
BLD-Other | 3/3/2014 | 3/4/2014 | 3/4/2014 | A | DONE |
Mike Jordan
|
|
|
Please check to see if they have moved out and let Barb @ permit desk know. Thanks Phone #: ###-####. Hickory farms has vacated the space.
|
BLD-Final | 11/12/2013 | 11/13/2013 | 11/13/2013 | P | PASS |
Mike Jordan
|
|
|
Joan Phone #: ###-####. Ok for temp occ.
|
FIRE-Final Inspection | 11/12/2013 | 11/13/2013 | 11/13/2013 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
BLD-Final | 11/4/2013 | 11/5/2013 | 11/5/2013 | P | NR |
Mike Jordan
|
|
|
Joan Larsen Phone #: ###-####. Fire/life/safety failed.
|
FIRE-Final Inspection | 11/4/2013 | 11/5/2013 | 11/5/2013 | A | FAIL |
Troy Cobbley
|
|
|
Sprinkler pendants are overspaced near the front of the store, smoke detector for the smoke evac system has been disabled, sprinkler protection is required in the walk-in cooler, fire extinguishers need annual inspection, missing ceiling tile, floor plan does not match
|