BLD-Final | 7/14/2014 | 7/14/2014 | 7/14/2014 | P | PASS |
Mike Jordan
|
|
|
Jesse Phone #: ###-####. ok for perm occ.
|
BLD-Final | 7/11/2014 | 7/11/2014 | 7/11/2014 | P | FAIL |
Mike Jordan
|
|
|
late as poss per electrical is also scheduled for this pm // Jesse Phone #: ###-####. Provide handrails at the south man door.
|
FIRE-Final Inspection | 6/23/2014 | 6/24/2014 | 6/24/2014 | A | PASS |
Troy Cobbley
|
|
|
life safety passed. Signs have been posted
|
FIRE-Final Inspection | 6/20/2014 | 6/23/2014 | 6/23/2014 | P | FAIL |
Troy Cobbley
|
|
|
Need fire lane signs as per the fire dept review comments.
|
BLD-Framing/Rough-in | 6/16/2014 | 6/17/2014 | 6/17/2014 | A | NR |
Tom Arcoraci
|
|
|
Jesse Phone #: ###-#### needs spec inspection for bolting
|
FIRE-Final Inspection | 6/3/2014 | 6/4/2014 | 6/4/2014 | A | FAIL |
Troy Cobbley
|
|
|
Need to provide all of the small documents. Exit signs and emergency lights are not installed and neither is the south exit door. Need fire extinguishers as well with current inspection tags.
|
BLD-Foundation | 5/5/2014 | 5/6/2014 | 5/6/2014 | A | PASS |
Tom Arcoraci
|
|
|
Rob Phone #: ###-####
|
BLD-Foundation | 4/24/2014 | 4/24/2014 | 4/24/2014 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Foundation | 4/23/2014 | 4/24/2014 | 4/24/2014 | A | CANC |
Tom Arcoraci
|
|
|
Matt Phone #: ###-####
|
BLD-Footing | 4/21/2014 | 4/22/2014 | 4/22/2014 | P | PASS |
Tom Arcoraci
|
|
|
Matt Phone #: ###-####
|