BLD-Final | 1/20/2015 | 1/20/2015 | 1/20/2015 | P | PASS |
Jim Storey
|
|
|
Mike Phone #: ###-####
|
BLD-Final | 1/14/2015 | 1/15/2015 | 1/15/2015 | A | PART |
Jim Storey
|
|
|
Mike Phone #: ###-#### final ok pending ele sign off
|
FIRE-Final Inspection | 1/13/2015 | 1/14/2015 | 1/14/2015 | A | PASS |
Forrest France
|
|
|
Noted correction items verified for completion. Fire life safety inspection passed.
|
FIRE-Final Inspection | 1/12/2015 | 1/13/2015 | 1/13/2015 | P | NR |
Forrest France
|
|
|
Items noted include; missing ceiling tile at open office 124 and work room 113, need to repair EM light at hall 102, repair exit sign/EM light at both the east and west exit doors, exit sign at open office 107 does not operate on backup power source. Remainder of life safety inspection items okayed.
|
BLD-Framing/Rough-in | 11/24/2014 | 11/25/2014 | 11/25/2014 | A | PASS |
Jim Storey
|
|
|
call before// mike Phone #: ###-####
|
BLD-Framing/Rough-in | 11/21/2014 | 11/24/2014 | 11/24/2014 | A | PART |
Jim Storey
|
|
|
Mike Phone #: ###-#### rated wall not compliant to rated const opening protection
|