BLD-Final | 3/4/2015 | 3/5/2015 | 3/5/2015 | P | PASS |
Jim Sly
|
|
|
Mike Phone #: ###-#### OK for Perm Occ.
|
FIRE-Final Inspection | 3/4/2015 | 3/5/2015 | 3/5/2015 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. Owner to provide correct single action hardware on the new doors. (Wrong hardware installed)
|
FIRE-Final Inspection | 2/25/2015 | 2/25/2015 | 2/25/2015 | P | FAIL |
Troy Cobbley
|
|
|
Still need to address fire extinguishers and door hardware. See notes on plan
|
FIRE-Final Inspection | 2/23/2015 | 2/24/2015 | 2/25/2015 | A | FAIL |
Forrest France
|
|
|
Inspection completed 2/24 PM. Items noted include; remove surface bolt or remove non-required exit sign at the north door from the front office to the shop, post address numbers of min. required height, post "door to remain signage" at the main entry/exit, lower fire extinguishers to no higher than 48" AFF, provide verification the non-required fire alarm system is functional or remove. Refer to items 1,2, and 4 on the list of general requirements attatched to permit documents.
|
BLD-Final | 2/23/2015 | 2/24/2015 | 2/24/2015 | P | NR |
Jim Sly
|
|
|
Mike Phone #: ###-#### Called Mike.....Need fire final prior to calling for Bldg final.
|