BLD-Final | 12/10/2015 | 12/15/2015 | 12/15/2015 | A | PASS |
Tony Young
|
|
|
Bill Phone #: ###-####,, ok for c of o
|
FIRE-Final Inspection | 12/11/2015 | 12/14/2015 | 12/14/2015 | P | PASS |
Jim Page
|
|
|
Previously noted items addressed/repaired. No fire sprinklers, no fire alarm modifications. Life fire safety inspection passed/complete.
|
FIRE-Final Inspection | 12/10/2015 | 12/11/2015 | 12/11/2015 | P | FAIL |
Jim Page
|
|
|
Exit signs/lights must be illimunated at all times under normal building power. Exit signs/lights also need to have an emergency power supply able to provide not less than 90 minutes of power. Emergency egress lighting needs to be installed on the second level, currently the only emergency lighting on the floor is in the restrooms.
|
BLD-Conference | 12/9/2015 | 12/9/2015 | 12/9/2015 | P | PASS |
Jim Storey
|
|
|
Bill Phone #: ###-#### final ok pending other signoffs.
|
BLD-Framing/Rough-in | 12/9/2015 | 12/9/2015 | 12/9/2015 | P | PASS |
Jim Storey
|
|
|
Bill Phone #: ###-####
|
BLD-Ceiling Grid Inspection | 11/24/2015 | 11/24/2015 | 11/24/2015 | P | PASS |
Jim Storey
|
|
|
John Phone #: ###-####
|
BLD-Framing/Rough-in | 11/3/2015 | 11/4/2015 | 11/4/2015 | A | PART |
Jim Storey
|
|
|
Partial framing on conf rm, break rm & three offices - Bill Phone #: ###-#### ok to cover walls
|