Permit Information
Permit NumberBLD15-03464
StatusFinaled
Name WRIGHT BROTHERS THE BLDG CO
Site Address 3033 W ELDER ST
Project NameWells Fargo - Self-Mini Market
Customer Number 
ePlanReviewYes
Description
(WELLS FARGO SERVICE CENTER – SELF SERVE MINI MARKET) Permit is to remodel 393 sq. ft. within an existing cafeteria space. This permit is approved contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls , construction of select interior non-bearing walls to create a new self-serve mini market area, new interior wall glazing, some suspended ceiling work, relocation of light fixtures, new 8’ wide motorized overhead coil door, electric work and interior finishes in compliance with chapter 8 of the 2012 IBC. This building is fully fire sprinklered any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection3/16/20163/17/20163/16/2016APASS
DetailsTroy Cobbley
Life safety passed.
BLD-Final1/6/20161/6/20161/6/2016APASS
DetailsJim Storey
Tom Phone #: ###-####
FIRE-Final Inspection1/6/20161/6/20161/6/2016PPART
DetailsTroy Cobbley
A temp is being given until the sync module is installed. I had a conversation with State Fire the general contractor and the building maintenance supervisor about what has been installed to match existing does not meet current code for syncing of visual and audio devices and that when another remodel is this area all devices will need to be brought up to current code. All parties agreed and the building supervisor stated that a total alarm upgrade was in the works.
FIRE-Final Inspection12/29/201512/29/201512/29/2015PFAIL
DetailsTroy Cobbley
Need fire alarm modifications as per the plans, and review comments. Sprinkler permit has been finaled and life safety appears ok when fire alarm issues are addressed.
FIRE-Final Inspection12/23/201512/23/201512/23/2015PCANC
DetailsJim Page
Spoke with POC Kevin Phone #: ###-####, approved plans/small documents not on site, cancelled inspection request per conversation with Kevin, inspection request will be rescheduled when approved plans/small documents are on site.
BLD-Framing/Rough-in12/7/201512/8/201512/8/2015PPASS
DetailsJim Storey
Tom Phone #: ###-#### walls ok