Information based on query as of Tuesday, June 25, 2024.
Permit Information
Permit NumberBLD15-04336
StatusFinaled
Name INTERMOUNTAIN PROPERTY SERVICE
Site Address 11849 W EXECUTIVE DR
Project NameHarrington Plastics
Customer Number 
ePlanReviewYes
Description
(HARRINGTON PLASTICS – NORTH END OF BUILDING) This building does not have a fire sprinkler system. To create a 5,409 square foot warehouse and office tenant space from a larger space in an existing 23,100 square foot building. Work is to include an interior nonbearing 3-hr fire-resistance-rated fire barrier wall to create separate fire areas and to function as a tenant demising wall. Since this building does not have a fire sprinkler system, plastics are not allowed to be stored above 6 feet. A separate permit is required for racks over 8 feet in height. A fire sprinkler system is required throughout this tenant space (i.e. the fire area) before storage of plastics over 6 feet will be allowed. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/8/20162/9/20162/9/2016PPASS
DetailsMike Jordan
Scott Phone #: ###-####. Ok for perm occ.
FIRE-Final Inspection2/8/20162/9/20162/9/2016APASS
DetailsTroy Cobbley
Life safety passed
FIRE-Final Inspection2/4/20162/5/20162/5/2016AFAIL
DetailsTroy Cobbley
Mount and tag fire extinguishers as shown on the plans, provide sticker at the Room 100 exit door, provide ADA single action hardware on the warehouse store front door, provide ADA single action hardware on Office 101 door, repaire emergency light in warehouse.
BLD-Framing/Rough-in2/4/20162/4/20162/4/2016PPASS
DetailsMike Jordan
Scott Phone #: ###-####
BLD-Framing/Rough-in2/2/20162/3/20162/3/2016APEND
DetailsMike Jordan
Scott Phone #: ###-####. Contractor noted that 3m product used for membrane and through penetration protection. Need UL data to verify instalation.
BLD-Framing/Rough-in1/28/20161/29/20161/29/2016APASS
DetailsMike Jordan
Scott Phone #: ###-####. All isues have been resolved. ok to cover.
BLD-Conference1/26/20161/27/20161/27/2016ADONE
DetailsMike Jordan
Scott Phone #: ###-####
BLD-Framing/Rough-in1/25/20161/26/20161/26/2016AFAIL
DetailsJim Storey
Scott Phone #: ###-#### /n isuedc
BLD-Framing/Rough-in1/20/20161/20/20161/20/2016PFAIL
DetailsMike Jordan
Scott Phone #: ###-####. Architect to provide additional framing details for 3hr. fire barrier wall from bottom chord of roof joist to underside of steel deck.. Also provide Approved listed through penetration protection for steel beam, electrical conduits and copper water line.