Permit Information
Permit NumberBLD17-01449
StatusFinaled
Name 10477 FAIRVIEW AVE LLC
Site Address 10477 W FAIRVIEW AVE
Project NameBelmont Plaza - Shell and Core
Customer Number 
ePlanReviewYes
Description
(BELMONT PLAZA – SHELL AND CORE – OLD K-MART BUILDING) (CZC17-00130) The fire sprinkler system is used for unlimited area of the building AND to allow 3-hr fire barrier walls in lieu of fire walls. The fire sprinkler system is NOT allowed to be used for building area increase for A Occupancies. To do some shell and core work to an existing 83,904 square foot building in anticipation of future tenants. Work is to include structural modifications to the roof (beams and joists) to support roof top HVAC equipment, new openings in exterior masonry walls with new 2-hr steel beams or lintels supported by new 2-hr steel columns and concrete footings, new storefront glazing and entrance doors, new egress doors and overhead doors, 3-hr fire barrier walls per the 2012 IEBC in lieu of fire walls to create separate buildings, interior nonbearing walls, 4 toilet rooms accessible to the disabled, and an assisted-use toilet room accessible to the disabled. Special Inspection is required for welding and for anchors post installed in hardened concrete (epoxy and/or expansion). The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. This permit is for shell and core work only. This permit is not intended to establish a Certificate of Occupancy for any tenant or for any portion of this building. Each tenant is required to apply for their own permit to do tenant improvement work and to establish occupancy. The fire sprinkler system is required to comply with NFPA 13 (including quick-response heads in light-hazard occupancies) and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/8/20185/9/20185/9/2018APASS
DetailsMike Jordan
DOC - Permit Finaled5/9/20185/9/20185/9/2018PPASS
DetailsMike Jordan
BLD-Final5/7/20185/8/20185/8/2018ANR
DetailsMike Jordan
Cody Phone #: ###-####
BLD-Final5/7/20185/7/20185/7/2018PCANC
DetailsMike Jordan
Cody Phone #: ###-####
BLD-Final5/4/20185/4/20185/4/2018PNR
DetailsMike Jordan
BLD-Final5/3/20185/4/20185/4/2018AFAIL
DetailsMike Jordan
Cody Phone #: ###-####. Needs to complete all firecaulking.
FIRE-Final Inspection5/3/20185/3/20185/3/2018PPASS
DetailsTroy Cobbley
Life safety passed. Per verbal agreement the existing red fire lane painting will be extended to the west end of the building complex next week when stripping occurs.

Cody Phone #: ###-####
BLD-Conference4/26/20184/26/20184/26/2018PDONE
DetailsMike Jordan
Cody Phone #: ###-####
BLD-Final2/14/20182/14/20182/14/2018PPEND
DetailsMike Jordan
BLD-Final2/1/20182/2/20182/2/2018APART
DetailsMike Jordan
BYRON - Phone #: ###-####. Temp on shell and core until plumbing, elec. and life safety final. All listed trades have given temp. Contractor to repair holes and mark 3hr. fire barrier walls.
FIRE-Final Inspection1/30/20181/31/20182/1/2018PPART
DetailsTroy Cobbley
A temporary occupancy is being given on life safety only until the exit discharge lights have been installed for all tenant spaces as shown on the plans
BLD-Final1/30/20181/31/20181/31/2018PNR
DetailsMike Jordan
Egor Phone #: ###-####
BLD-Conference11/17/201711/20/201711/20/2017ADONE
DetailsMike Jordan
Jim Raines Phone #: ###-####. Discussed the removal of the half wall in the storage room to the exit door in the youth ranch space. Architect has submitted a change for approval. Noted to contractor ok to hold off on construction of half wall until plan mod has been reviewed.
BLD-Framing/Rough-in11/9/201711/9/201711/9/2017PPASS
DetailsMike Jordan
Jim Phone #: ###-####. Completion of fitre caulking on rated walls in churc T.I.
BLD-Framing/Rough-in10/24/201710/24/201710/24/2017PPASS
DetailsMike Jordan
Jim Phone #: ###-####. Demissing walls for T.I. spaces 5 and 6. 2nd and 3rd layers of 5/8 type C sheetrock for all 3 hour fire barries. All rock wool installed as per 3m E.J. Also framing for 3rh. fire barrier at back of house on either side of Johnny's fit club.
BLD-Framing/Rough-in10/10/201710/11/201710/11/2017APASS
DetailsMike Jordan
Jim Phone #: ###-####. Store front wraps of 2layers of 5/8 dense glass on exterior ok. Rock wool on demissing wall for church installed as per EJ from 3m ok.
BLD-Other10/3/201710/4/201710/4/2017APASS
DetailsMike Jordan
fire wall // Jim Phone #: ###-####. New store front framingeast end ok. Door fromes for church in 3hr. fire barrier ok. Went over fircaulking details and engineered judgement for membrane penetration of 4x4 steel electrical boxes in 3hr. fire barrier.
BLD-Framing/Rough-in9/26/20179/26/20179/26/2017PPASS
DetailsMike Jordan
Jim Phone #: ###-####. Interior steel stud framed 3hr. fire barrier wall south end of building at and under mezz.
BLD-Conference9/22/20179/22/20179/22/2017PDONE
DetailsMike Jordan
Jim Phone #: ###-####. Reviewed UL listing for 3M putty pads for membrane protection of 3hr. fire barier wall. Per the listing, The puuty pads will only achieve a maxiumum of 2hr rating. Contractor will pursue with 3m on getting an engineer judgement for alternate to achieve the 3hr. rating and submit to building official for approval.
BLD-Framing/Rough-in9/14/20179/15/20179/15/2017PPASS
DetailsMike Jordan
Jim Phone #: ###-####. Interior steel stud framed 3hr. fire walls for suite C and at storage for arera at rear of church.
BLD-Footing9/6/20179/6/20179/6/2017PPASS
DetailsMike Jordan
Jim Phone #: ###-####. Footings for new store front.
BLD-Framing/Rough-in9/6/20179/6/20179/6/2017PPASS
DetailsMike Jordan
Jim Phone #: ###-####. Interior steel stud framed 3 hr. fire barier wall, 2nd from the east.
BLD-Framing/Rough-in8/31/20178/31/20178/31/2017PPASS
DetailsMike Jordan
Jim Phone #: ###-####. Interior 3hr. fire barrier steel stud wall for tenant #1 ok.
BLD-Framing/Rough-in8/28/20178/28/20178/28/2017PPASS
DetailsMike Jordan
Jim-steel stub framing Phone #: ###-####. Interior steel stud 3hr. fire barrier demissing wall at TI #1(Victory Church). Ok to rock one base layer on one side. Will need to box out 4x4 electrical boxes fro membrane penetration protection.