Permit Information
Permit NumberBLD17-04114
StatusIssued
Name BOISE PUBLIC SCHOOLS
Site Address 1507 N 28TH ST
Project NameLowell Elementary
Customer Number 
ePlanReviewYes
Description
(LOWELL ELEMENTARY) ""PLAN MODOFICATION TO EXTEND THE WALLS UP TO THE EXISTING CEILING"" Permit for the construction of partial height partition wall with padding, (MF-SILTEC see specifications) and a new door to classroom for a de-escalation room per the approved plans. This is a scope of work permit only with a certificate of completion to be issued upon completion of the project. This building is fully fire sprinklered. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection12/13/201912/13/201912/19/2019 FAIL
DetailsTony Young
BLD-Aging Inspection12/12/201912/12/201912/19/2019 FAIL
DetailsTony Young
BLD-Final7/31/20198/1/20198/1/2019ACANC
DetailsTony Young
Call ahead // Gavin Phone #: ###-####,, needs f/l/s 1st
FIRE-Final Inspection7/31/20197/31/20197/31/2019PFAIL
DetailsJim Page
Fire sprinkler modifcations were completed without a permit. Provide fire alarm notification in de-escalation room and room lobby. Mag locks on door to de-escalation room needs to release during fire alarm activation, need to verify if this actually does happen during a fire alarm event.

Call ahead // Gavin Phone #: ###-####
BLD-Final7/9/20197/10/20197/10/2019ANR
DetailsTony Young
Nick Phone #: ###-####,, needs fire inspection 1st
FIRE-Final Inspection7/9/20197/10/20197/10/2019AFAIL
DetailsJim Page
Called point of contact at 8:50AM, left a voicemail stating that I would give 15 minutes and then I would have to proceed to next inspection, waited until 9:15 with no call back, proceeded to next inspection. Inspection request will need to be rescheduled.

Nick Phone #: ###-####