Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberBLD18-00374
StatusFinaled
Name CBH HOMES
Site Address 9612 W BURNETT DR
Project NameMonterey 2-1 Diamante
Customer Number 
ePlanReviewYes
Description
***Prescriptive component approach*** Permit for the construction of a new 2000 sq. ft., one story single family dwelling with 4 bedrooms, 2 bathrooms, approximately 104 sq. ft. of covered patio/porch and a 673 sq. ft. attached garage per the approved plans, plan review report and any notations. R-1A zoning and setbacks per planning. MDH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final7/9/20187/9/20187/9/2018PPASS
DetailsMike Jordan
garage door code is 2468 Phone #: ###-#### Inspection requested via web by Joel Hirtle
DOC - Permit Finaled7/9/20187/9/20187/9/2018PPASS
DetailsMike Jordan
BLD-Blower Door Test Results7/9/20187/9/20187/9/2018PDONE
DetailsMike Jordan
garage door code is 2468 Phone #: ###-#### Inspection requested via web by Joel Hirtle.
4.7ACH
BLD-Energy code compliance5/22/20185/22/20185/22/2018PPASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Joel Hirtle
BLD-Framing/Rough-in5/22/20185/22/20185/22/2018PPASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Joel Hirtle
BLD-Framing/Rough-in5/21/20185/21/20185/21/2018PFAIL
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Joel Hirtle. Complete lateral bracing on A6 truss. LAteral bracing on B2, B3 and B4 trusses connected to wrong member, attach to webs, not top chord. Fireblock at ceiling level in closet in main hallway. Provide additional bracing on top chords of A3 trusses were roof sheathing is stooped. Also roll block. Insuffucient bearing on at sleepers on over builds. Ok to insulate. Correction notice posted.
BLD-Energy code compliance5/17/20185/21/20185/21/2018PCANC
DetailsMike Jordan
Phone #: ###-#### >> Inspection requested via web by Joel Hirtle Inspection cancelled from web by: Joel Hirtle
BLD-Framing/Rough-in5/17/20185/18/20185/18/2018PNR
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Joel Hirtle.Mech rough in inspection has failed.
BLD-Wall Bracing4/25/20184/25/20184/25/2018PPASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Joel Hirtle
BLD-Footing4/11/20184/12/20184/12/2018PPASS
DetailsMike Jordan
Dane Phone #: ###-####