BLD-Final | 8/6/2018 | 8/7/2018 | 8/7/2018 | A | PASS |
Mike Jordan
|
|
|
Tito-ready for perm c of o Phone #: ###-#### OK for perm occ.
|
BLD-Aging Inspection | 7/11/2018 | 7/11/2018 | 7/11/2018 | | PEND |
Mike Jordan
|
|
|
Needs plumbing final. Called Nick to have him get ahold of plumber to schedule final.
|
BLD-Final | 5/7/2018 | 5/8/2018 | 5/8/2018 | A | PART |
Mike Jordan
|
|
|
Ok for temp occ.
|
BLD-Final | 5/7/2018 | 5/7/2018 | 5/8/2018 | P | CANC |
Mike Jordan
|
|
|
Please call ahead for access - Nick Phone #: ###-####
|
BLD-Final | 5/2/2018 | 5/3/2018 | 5/3/2018 | P | NR |
Mike Jordan
|
|
|
Nicholas Phone #: ###-####. Nees plumbing, mech and possible electrical permit.
|
FIRE-Final Inspection | 5/2/2018 | 5/3/2018 | 5/3/2018 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed.
Nicholas Phone #: ###-####
|
BLD-Wall cover | 4/30/2018 | 5/1/2018 | 5/1/2018 | A | PASS |
Mike Jordan
|
|
|
Dwayne if no answer call Nick ###-#### Phone #: ###-####. Ok to cover non combustible steel stud wall behind type 1 hood.
|
BLD-Framing/Rough-in | 4/26/2018 | 4/27/2018 | 4/27/2018 | A | PART |
Mike Jordan
|
|
|
Duane or Nick ###-#### Phone #: ###-####. Framing for new noncombustable wall behind type 1 hood ok. No cover as electrical still needs access.
|
FIRE-Final Inspection | 3/23/2018 | 3/26/2018 | 3/26/2018 | A | CANC |
Troy Cobbley
|
|
|
Veto Phone #: ###-####
|
BLD-Conference | 3/23/2018 | 3/23/2018 | 3/23/2018 | P | FAIL |
Mike Jordan
|
|
|
Tenant to obtain architect and submit plans. Current permit does not allow additional work. Additional work is being done. ie, mech, plumbing and new service counters were noted. Also possible work on type 1 hood also requires permit. Stop work has been issued until plan mod is submitted and approved.
|
BLD-Final | 3/13/2018 | 3/15/2018 | 3/15/2018 | P | NR |
Mike Jordan
|
|
|
NIcholas Phone #: ###-####
|
FIRE-Final Inspection | 3/13/2018 | 3/15/2018 | 3/15/2018 | A | FAIL |
Troy Cobbley
|
|
|
Need to provide testing of the smoke evac system, need to provide the two types of fire extinguishers, need to provide sprinkler canopies, need ADA hardware on the exit door, need permit and testing of the new hood suppression system
NIcholas Phone #: ###-####
|