Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberBLD18-01890
StatusIssued
Name EKC INC
Site Address 360 E MALLARD DR Unit: 200
Project NameAdvantage Solutions
Customer Number 
ePlanReviewYes
Description
(Advantage Solutions) Ste #200 - To remodel an existing 14,233 sq ft office tenant space. Work to include, removal systems furniture layout, install new systems furniture, construction of interior noncombustible partitions, miscelanous mill work and finishes, relocate lighting and diffusers, this building is fully fire sprinklered any alteraterations or modifications to the sprinkler system will require a separate permit. RmH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final9/26/20199/27/20199/27/2019PCANC
DetailsBrandon Shaw
Bill Phone #: ###-####
FIRE-Final Inspection9/26/20199/27/20199/27/2019PFAIL
DetailsJim Page
Provide fire sprinkler in area as discussed outside of phone room. Items are stored closer than 18 inches to ceiling, per NFPA13, section 8.5.6, a minimum of 18 inches of clearance is required from bottom of deflector to top storage.

Bill Phone #: ###-####
BLD-Aging Inspection7/15/20197/15/20197/16/2019 DEFR
DetailsBrandon Shaw
Extend Permit 90/180 days7/16/20197/16/20197/16/2019PDEFR
DetailsBrandon Shaw