Permit Information
Permit NumberBLD18-02176
StatusFinaled
Name K2 CONSTRUCTION
Site Address 6772 W TARGEE ST
Project NameDennis Dillon RV and Marine
Customer Number 
ePlanReviewYes
Description
(DENNIS DILLON RV AND MARINE) **This building is fire sprinklered in accordance with NFPA 13 with 60 ft yards for unlimited area.** // 01/02/20 PLAN MOD TO DOOR HARDWARE, LOCATIONS OF INTERIOR NON-BEARING PARTITION WALLS. JAR // Permit for the construction of a new 95,334 sq. ft, 1-story pre-engineered shell RV dealership showroom and service building and related site improvements. Scope of work includes: construction of slab on grade concrete foundation, pre-engineered shell with insulation, log-framed exterior canopies, interior non-bearing partitions, doors, restrooms, electrical, mechanical, plumbing, millwork and interior finishes to be in compliance with Ch. 8 of the 2015 IBC. All work shall comply with the approved plans, geotech report dated 9/10/2018, DRH18-00097 and all applicable codes. Complies with 2015 IECC. Special Inspections Required, see form 310. A separate racking permit is required if racks are installed over 8 feet in height. Separate permits will be required for the building fire protection systems, as regulated by the Fire Department. **JAR**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/30/20201/31/20201/31/2020PPASS
DetailsMike Jordan
nACHO Phone #: ###-####. All issues resolved. Ok for perm occ.
FIRE-Final Inspection1/30/20201/31/20201/31/2020APASS
DetailsTroy Cobbley
Life safety passed. Panic hardware to be installed on door 106A prior to the building inspection. Anthony at boise fire station #6 verified that the optican for both gates was functional.

nACHO Phone #: ###-####
BLD-Final12/26/201912/27/201912/27/2019APART
DetailsDave Hannah
Nacho Phone #: ###-#### ok for tco needs other trades to go perm also needs to finish signage and mill work
FIRE-Final Inspection12/26/201912/27/201912/27/2019APART
DetailsJim Page
Previously noted items have been corrected with exception to the door that was notated by Troy, opticon sensors not in place for access gates but gates are left open for fire truck access until opticon is operational. Fire alarm inspection has been completed, fire sprinkler inspections have been completed, fire extinguishers are placed with current inspection tags. A partial final inspection for life fire safety is complete, per conversation with Ron Johnson, a 90 TCO is authorized for life fire safety.

Nacho Phone #: ###-####
FIRE-Final Inspection12/17/201912/17/201912/17/2019PFAIL
DetailsTroy Cobbley
The associated Grading permit needs scheduled/inspected/passed, need the emergency lights added and other repaired as per plans, need exit sign added as per plans, need panic hardware provided as per plans, need permanant address, need electric gates/opticon installed and tested.

Nacho Phone #: ###-####
FIRE-Final Inspection12/5/201912/6/201912/6/2019AFAIL
DetailsTroy Cobbley
Not ready for a final yet. This inspection was for the Boise Fire dept determination of an Operational Permit for a Christmas Party. The Sales area, south portion, of the new building has its life safety inspection approved. I contacted Chief Ron with the Boise Fire Dept. and let him know. Nacho Phone #: ###-####
BLD-Final12/5/201912/6/201912/6/2019ADONE
DetailsMike Jordan
Nacho Phone #: ###-####
BLD-Conference12/3/201912/4/201912/4/2019ADONE
DetailsMike Jordan
Nacho ###-####
FIRE-Final Inspection12/3/201912/3/201912/3/2019PFAIL
DetailsTroy Cobbley
Inspection was actually for a conference to provide guide lines for the use of the south end/sales are for a Christmas function. It appears the gate for the existing fire hydrant needs installed, building address, Riser and Electrical Room signage, grading permit sign off, fire extinguishers mounted and a fire dept approved temp barrier to the rest of the building. Also needed is a building inspection and approval for the use of the building/area.

Nacho Phone #: ###-####
BLD-Ceiling Grid Inspection11/12/201911/12/201911/12/2019PPASS
DetailsMike Jordan
Nacho Phone #: ###-####
BLD-Final10/29/201910/30/201910/30/2019ACANC
DetailsMike Jordan
Nacho Phone #: ###-####
BLD-Framing/Rough-in10/30/201910/30/201910/30/2019APASS
DetailsMike Jordan
Nacho Phone #: ###-####. Steel stud framing for fireplace ok.
BLD-Framing/Rough-in8/9/20198/12/20198/12/2019APASS
DetailsMike Jordan
Nacho Phone #: ###-####. Interior steel stud framed walls for restroom on mezz. and west vestibule. Also screw pattern for shear walls.
BLD-Other8/9/20198/9/20198/9/2019PPASS
DetailsMike Jordan
fire wall // nicho Phone #: ###-####. 5/8 sheet rock on underside of decking.
BLD-Framing/Rough-in8/6/20198/7/20198/7/2019APASS
DetailsMike Jordan
Nacho Phone #: ###-####. Interior steel stud framed walls, hardlids and mezzanines ok per approved plans and RFI's from engineer of record.
BLD-Framing/Rough-in7/30/20197/31/20197/31/2019AFAIL
DetailsMike Jordan
Macho Phone #: ###-####. Provide the web stiffeners in joists in restroom in area A. Ok to one side walls only.
BLD-Framing/Rough-in7/30/20197/30/20197/30/2019PPASS
DetailsMike Jordan
Nacho Phone #: ###-####. Ok to sheet rock bottom of joist only.
FIRE-Conference7/29/20197/29/20197/29/2019PDONE
DetailsTroy Cobbley
We discussed the combustible concealed spaces.

Nacho Phone #: ###-####
BLD-Wall cover6/13/20196/13/20196/13/2019PFAIL
DetailsMike Jordan
Sheer wall Phone #: ###-#### Inspection requested via web by Steve Mitchell. Interior shear wall next to restroom. Needs to install 5/8" anchor bolts, HDU4 hold down and provide atachment of sheetrock at 4 inches OC
BLD-Framing/Rough-in6/11/20196/12/20196/12/2019ACANC
DetailsMike Jordan
Framing for break room and bathrooms and sheet rock screw pattern Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Framing/Rough-in5/29/20195/30/20195/30/2019PPASS
DetailsMike Jordan
Late after noon West, East, South walls of show room Phone #: ###-#### Inspection requested via web by Steve Mitchell. West exterior wall in showroom ok.
BLD-Foundation5/23/20195/24/20195/24/2019APASS
DetailsMike Jordan
Grout under columns. Early A M please thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Concrete5/22/20195/23/20195/23/2019ACANC
DetailsMike Jordan
Early A M please. Grout under columns Phone #: ###-#### >> Inspection requested via web by Steve Mitchell Inspection cancelled from web by: Steve Mitchell
BLD-Concrete4/18/20194/19/20194/19/2019APART
DetailsBrandon Shaw
Grid L-A, Wesr side...
Grid A-G, East side...
BLD-Concrete4/15/20194/16/20194/16/2019PPASS
DetailsMike Jordan
Late after noon slab on grade grids G to K and 1 to 3
Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Concrete4/10/20194/15/20194/15/2019ACANC
DetailsMike Jordan
slab on grade grids 1 to 3 and S to DD Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Concrete4/12/20194/12/20194/12/2019PPASS
DetailsMike Jordan
Reinforcing slab on grade grids 1 to 3 S to DD Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Concrete4/8/20194/9/20194/9/2019PCANC
DetailsMike Jordan
Early after noon. slab on grade grids S to DD,3 thru 6 Phone #: ###-#### Inspection requested via web by Steve Mitchell. rreinforcment for interior slab on grade at above location ok.
BLD-Concrete3/26/20193/27/20193/27/2019PPART
DetailsMike Jordan
Slab on grade Phone #: ###-#### Inspection requested via web by Steve Mitchell. reinforcemet for interior slab on graded anfd interior thickend footings.on gridlines k to S and gridlines 1 to 6. Noted that dobes need to be installed for rebar at thickend footings.. Special inspector to verify prior to placment.
BLD-Footing3/19/20193/20/20193/20/2019APART
DetailsMike Jordan
Early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell. work in progress.
BLD-Foundation3/8/20193/11/20193/11/2019APASS
DetailsMike Jordan
Early am please we are scheduled to pore at 10:00 AM Thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell. Frost wall and column pedestals on gridline DD between grids 1 to 6 and remainder of frost walls and column pedestals on gridline 6.
BLD-Footing3/8/20193/8/20193/8/2019PPASS
DetailsMike Jordan
Exterior column pad footings on grtidlline 7.
BLD-Footing3/4/20193/8/20193/8/2019ACANC
DetailsMike Jordan
Early AM Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing3/4/20193/7/20193/7/2019ACANC
DetailsMike Jordan
Early AM Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing3/4/20193/6/20193/6/2019ACANC
DetailsMike Jordan
Early AM Phone #: ###-#### >> Inspection requested via web by Steve Mitchell Inspection cancelled from web by: Steve Mitchell
BLD-Footing3/4/20193/5/20193/5/2019ADEFR
DetailsMike Jordan
Early AM Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/25/20193/1/20193/1/2019ADEFR
DetailsMike Jordan
early am Phone #: ###-#### Inspection requested via web by Steve Mitchell. West service bays frost wall, special inspector on site.
BLD-Footing2/25/20192/28/20192/28/2019ACANC
DetailsMike Jordan
early am Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/25/20192/27/20192/27/2019ACANC
DetailsMike Jordan
early am Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/25/20192/26/20192/26/2019ADEFR
DetailsMike Jordan
early am Phone #: ###-#### Inspection requested via web by Steve Mitchell. OK pending special inspection.
BLD-Footing2/18/20192/22/20192/22/2019APASS
DetailsMike Jordan
early am Phone #: ###-#### Inspection requested via web by Steve Mitchell. Interior column pad footings on grids 2 and 3 between grids n to W. Frost wall on gridline 1 between grids N to CC.
BLD-Footing2/18/20192/21/20192/21/2019ANR
DetailsMike Jordan
early am Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/18/20192/20/20192/20/2019ACANC
DetailsMike Jordan
early am Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/18/20192/19/20192/19/2019APART
DetailsMike Jordan
early am Phone #: ###-#### Inspection requested via web by Steve Mitchell. Interior column pad footings on grid line 3, work in progress.
BLD-Footing2/11/20192/15/20192/15/2019APART
DetailsJim Sly
early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell
Select stem walls....OK pending Geotek special inspection, tests and approvals.
BLD-Footing2/11/20192/14/20192/14/2019ADEFR
DetailsMike Jordan
early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/11/20192/13/20192/13/2019APART
DetailsMike Jordan
early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell. Column pad footings on grid 6 between grids W to AA. Work in progress. Needs to install verts. Ok to place concrete pending special inspection.
BLD-Footing2/11/20192/12/20192/12/2019ACANC
DetailsMike Jordan
early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/2/20192/8/20192/8/2019ADEFR
DetailsBrandon Shaw
Work in progress on column pedestals, ok for conc. pending Special inspection...
North East corner...
BLD-Footing2/2/20192/7/20192/7/2019ADEFR
DetailsMike Jordan
Early AM please Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/2/20192/6/20192/6/2019ACANC
DetailsMike Jordan
Early AM please Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/6/20192/6/20192/6/2019PDEFR
DetailsMike Jordan
Conc. placement in progress. Special inspector on site.
BLD-Footing2/2/20192/5/20192/5/2019ACANC
DetailsMike Jordan
Early AM please Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing2/2/20192/4/20192/4/2019ANR
DetailsMike Jordan
Early AM please Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing1/28/20192/1/20192/1/2019APART
DetailsMike Jordan
Request early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell. Work in progress on column pedestals and frost walls. ok for conc. pending Special inspection.
BLD-Footing1/28/20191/31/20191/31/2019APASS
DetailsMike Jordan
Request early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell. Coloumn pad footings for log canopy ok per Tammarack Grove enginnering RFI.
BLD-Footing1/28/20191/30/20191/30/2019APASS
DetailsMike Jordan
Request early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell. exterior column pad footings on gridline 9 for west canopy.
BLD-Footing1/28/20191/29/20191/29/2019ADEFR
DetailsMike Jordan
Request early am please Phone #: ###-#### Inspection requested via web by Steve Mitchell. Special inspector on site.
BLD-Foundation1/21/20191/25/20191/25/2019APASS
DetailsMike Jordan
we would like as early as we can thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell. Frost walls and column pedestals on gridline k and 8.
BLD-Foundation1/21/20191/24/20191/24/2019APART
DetailsJim Sly
we would like as early as we can thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell
OK.....pending Geotek special inspection, tests and approvals.
BLD-Foundation1/21/20191/23/20191/23/2019ACANC
DetailsMike Jordan
we would like as early as we can thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Foundation1/21/20191/22/20191/22/2019APART
DetailsJim Sly
we would like as early as we can thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell
foundation walls and piers at South side of bldg. OK pending Geotek special inspection, tests and approvals.
BLD-Footing1/16/20191/18/20191/18/2019APART
DetailsMike Jordan
Early AM please Phone #: ###-#### Inspection requested via web by Steve Mitchell. column pedestals and frost wall on gridline 1. Column pad footings on gridline 6. Work in progress, special inspector on site. Noted cold weather conc. practices being followed.
BLD-Footing1/16/20191/17/20191/17/2019ADEFR
DetailsMike Jordan
Requesting early am thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell. Special inspector on site.
BLD-Footing1/15/20191/16/20191/16/2019APART
DetailsMike Jordan
We would like an early AM inspection thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell. Interior column pad footings on gridline L. Needs to be following cold weather concrete standard. Special inspector will be on sit and will verify form temps prior to placing concrete.
BLD-Footing1/14/20191/15/20191/15/2019APART
DetailsMike Jordan
we would like an early A M inspection on rebar for an after noon pore thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell. Column pad footings for canopy. Per contractor, will be tented and heated, forms will be pre heated with a weed burner. Special inspector on site.
BLD-Footing1/7/20191/10/20191/10/2019APART
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Steve Mitchell
BLD-Footing1/8/20191/9/20191/9/2019APASS
DetailsJim Storey
Request for inspection around 8:00 a.m. if possible. Steve Mitchell Phone #: ###-#### Phone #: ###-#### Inspection requested via web by Jaron Dowalter rebar pad ft ok pending si reports
BLD-Footing1/8/20191/8/20191/8/2019PNH
DetailsMike Jordan
we would like a inspection around 2:00 this after noon if possible Phone #: ###-#### Inspection requested via web by Steve Mitchell. No access. on site, gates closed and locked. No inspection performed.
BLD-Footing12/26/201812/27/201812/28/2018PPASS
DetailsDave Hannah
We need a 2:30 inspection of rebar thanks Phone #: ###-#### Inspection requested via web by Steve Mitchell ftgs also spec inspection will be on site
BLD-Footing12/20/201812/21/201812/21/2018PCANC
DetailsMike Jordan
we will be poring at 2;00 pm with special inspections for rebar Phone #: ###-#### >> Inspection requested via web by Steve Mitchell ***per Steve, cancel inspection. will not be ready today and will call in to reschedule***
BLD-Conference9/26/20189/27/20189/27/2018ADONE
DetailsMike Jordan
No current permit for excavation and backfill of building footprint area. Current grading permit for parking lots only.. Building footing footprint is completed. Notified K@ project manager and project super to contact Jason Taylor for further direction. Also stop work on building pad. Noted no work on building paad was being conducted while on site. No excavators were on site either.