Permit Information
Permit NumberBLD18-02762
StatusFinaled
Name RRC CONTRACTORS
Site Address 5804 W FAIRVIEW AVE
Project NameWallaroos Furniture
Customer Number 
ePlanReviewYes
Description
**(WALLAROOS FURNITURE)** This building is fire sprinkled for area increase. Permit is to remodel an existing 22,430 sq. ft. retail building for furniture tenant with supporting warehouse/storage areas. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls, removal of select door/door frames, construction of interior non-bearing wall to separate the warehouse from the retail area, select new door/door frame, electrical work and interior finishes in compliance with Ch. 8 of the current IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final9/4/20189/4/20189/4/2018PPASS
DetailsJim Sly
Dave Phone #: ###-####
OK for Perm Occ.
FIRE-Final Inspection9/4/20189/4/20189/4/2018PPASS
DetailsTroy Cobbley
Life safety passed. Signs are to be posted reminding the employees that the matteress must be stored under 5'


Dave Phone #: ###-####
BLD-Final8/30/20188/31/20188/31/2018PNR
DetailsMike Jordan
Please call before arrival. Thank you. Phone #: ###-#### Inspection requested via web by David Sferle
FIRE-Final Inspection8/30/20188/31/20188/31/2018PFAIL
DetailsTroy Cobbley
Storage for the Group A (mattresses) can not exceed 5' and needs to be reduced, repair the exit discharge light, repair the fire alarm panel which currently is showing a "trouble" conditon.


Please call before arrival. Thank you. Phone #: ###-#### Inspection requested via web by David Sferle
BLD-Ceiling Grid Inspection8/30/20188/31/20188/31/2018ACANC
DetailsMike Jordan
Please call before arrival. Thank you. Phone #: ###-#### Inspection requested via web by David Sferle
FIRE-Conference8/30/20188/30/20188/30/2018PDONE
DetailsTroy Cobbley
we went over the general life safety requirements. Additionally I will need a sprinkler analysis stating the exact commodity and storage arrangement that will be allowed. I noted encapsulated foam mattereses stacked flat up to 7'6"
Please call before arrival Phone #: ###-#### Inspection requested via web by David Sferle
BLD-Conference8/30/20188/30/20188/30/2018PDONE
DetailsDave Hannah
please call before arival Phone #: ###-#### Inspection requested via web by David Sferle
BLD-Conference8/30/20188/30/20188/30/2018PCANC
DetailsJim Sly
Phone #: ###-#### >> Inspection requested via web by David Sferle Inspection cancelled from web by: David Sferle