BLD-Final | 2/11/2019 | 2/12/2019 | 2/12/2019 | P | PASS |
Tony Young
|
|
|
Call 30 min befor for access. Phone #: ###-#### Inspection requested via web by Tyson Jardine
|
DOC - Permit Finaled | 2/12/2019 | 2/12/2019 | 2/12/2019 | P | PASS |
Tony Young
|
|
|
|
FIRE-Final Inspection | 2/11/2019 | 2/12/2019 | 2/12/2019 | A | PASS |
Jim Page
|
|
|
Fire sprinkler modifications are complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for vanilla TI complete, no occupancy under this permit.
Call 30 min befor for access Phone #: ###-#### Inspection requested via web by Tyson Jardine
|
FIRE-Final Inspection | 1/14/2019 | 1/15/2019 | 1/15/2019 | A | FAIL |
Jim Page
|
|
|
Provide fire sprinkler in new restroom. Fire sprinkler heads are to close to beam that has been covered with sheetrock, need a minimum of 4 inches from center of sprinkler head to wall. Install addressing for tenant space.
Call 30 min before for access. Phone #: ###-#### Inspection requested via web by Tyson Jardine
|
BLD-Final | 1/14/2019 | 1/15/2019 | 1/15/2019 | A | CANC |
Tony Young
|
|
|
Call 30 min before for access. Phone #: ###-#### >> Inspection requested via web by Tyson Jardine Inspection cancelled from web by: Tyson Jardine
|
BLD-Final | 1/11/2019 | 1/14/2019 | 1/14/2019 | A | CANC |
Tony Young
|
|
|
Call Tyson 30 min before for access. Phone #: ###-#### >> Inspection requested via web by Tyson Jardine Inspection cancelled from web by: Tyson Jardine
|
BLD-Framing/Rough-in | 12/10/2018 | 12/11/2018 | 12/11/2018 | A | PART |
Tony Young
|
|
|
Call 30 min before so I can make sure it''s open. Thanks. Phone #: ###-#### Inspection requested via web by Tyson Jardine,, needs trades,, then ok to cover restroom walls
|