Information based on query as of Wednesday, July 3, 2024.
Permit Information
Permit NumberBLD18-03875
StatusFinaled
Name DONALD R BORG CONSTRUCTION CO INC
Site Address 802 W IDAHO ST
Project NameThe North Face
Customer Number 
ePlanReviewYes
Description
(THE NORTH FACE) **NO EARLY START ALLOWED** **REFER TO BLD19-00122 FOR 2ND FLOOR SPACE AND STAIR DESIGN** Fire Sprinklers used for 1-hour subsitition. Permit to remodel the existing tenant suite, relocate the stair, and reduce the second-floor retail space that is currently occupied by the tenant. 1st floor space will continue to be used as retail while the 2nd floor space will be used as storage. Work to include: construction of interior non-bearing walls to create one accessible fitting room and one non-accessible fitting room, point of sale counter, stockroom located on the 2nd floor, mechanical, plumbing, electrical, and installation of interior finishes in compliance with chapter 8 of the IBC. This building is fully fire sprinklered and any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **JHB**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/23/20195/24/20195/24/2019PPASS
DetailsDave Hannah
Marty Phone #: ###-#### (please verify if plumbing signature required for CO//leg) (per David H on the phone, plumbing signature is a N/A-TCH)
FIRE-Final Inspection5/23/20195/24/20195/24/2019APASS
DetailsJim Page
Fire sprinkler inspection is comlpete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Marty Phone #: ###-####
BLD-Final5/22/20195/23/20195/23/2019ANR
DetailsDave Hannah
Marty Phone #: ###-####
FIRE-Final Inspection5/22/20195/22/20195/22/2019PFAIL
DetailsJim Page
Fire alarm work was completed without an issued permit, fire alarm modifications will need to be permitted, inspected and finaled before life fire safety inspection can be completed.

Marty Phone #: ###-####
FIRE-Final Inspection5/20/20195/21/20195/21/2019AFAIL
DetailsJim Page
Fire sprinkler inspection failed due to a painted head and texture mud all the way up to the base of the sprinkler head. An FIR permit is required for fire alarm work, currently there is a wall mounted device mounted on the ceiling, was informed by the GC that the devices were lowered from their original location, any modifications to the fire alarm system requires a permit, including lowering devices from the original location.

Marty Phone #: ###-####
BLD-Framing/Rough-in4/26/20194/30/20194/30/2019APASS
DetailsDave Hannah
Marty Phone #: ###-####