Permit Number | BLD19-00668 |
Status | Finaled |
Name |
RR BUILDING SPECIALTIES LLC
|
Site Address |
1314 W GROVE ST
|
Project Name | Modern Hotel Door Replacement |
Customer Number | |
ePlanReview | No |
Description |
(MODERN HOTEL - DOOR REPLACEMENT) Permit to replace existing interior and exterior doors with new doors. Existing door hardware to be reused. The interior hallway is a 1-hour rated corridor with 20 min rated doors required. The exterior egress balcony on the second floor is required to have opening protectives as required for corridors (20-min rated doors), except where the balcony is served by two stairways and a dead-end travel condition does not require travel past an unprotected opening to reach a stairway per 1958 UBC and 2015 IBC 1021.2. The exterior walls are 1-hour fire resistance rated for VA construction. A certificate of completion is to be issued upon completion of the work. This building is NOT fire sprinklered. **JAR*
|