Permit Information
Permit NumberBLD19-00739
StatusIssued
Name DOUGLAS STAPLEY
Site Address 1830 W AIRPORT WAY
Project NameIntermountain Wind & Solar LLC
Customer Number 
ePlanReviewNo
Description
(INTERMOUNTAIN WIND AND SOLAR, LLC) Application for inspection to determine requirements for issuance of a Certificate of Occupancy for a 2,040 sq ft existing office/warehouse tenant. Warehouse will house solar inventory and commercial vehicles. This space was previously occupied by "TrialSource LLC" under MIS03-00219. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. There will be no change to the occupancy. No storage racking exceeding 8' in height allowed in the space under this permit. This building is NOT fire sprinklered **JHB**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final3/28/20193/29/20193/29/2019PFAIL
DetailsBrandon Shaw
Failed Fire and Life...
FIRE-Final Inspection3/28/20193/29/20193/29/2019AFAIL
DetailsTroy Cobbley
Repair or remove the exit sign, Provide single action lever type hardware on the rear exit, Provide fire sprinkler modifications or consult with the plan reviewer, Provide verification of a fire sprinkler monitoring system, Provide one 2A, 10BC fire extinguisher with current inspection tag, provide sticker at the main exit as discussed.

Jeff-please call to meet Phone #: ###-####