Permit Information
Permit NumberBLD19-04702
StatusFinaled
Name CARROLL CONSTRUCTION
Site Address 855 W BROAD ST Unit: STE 100
Project NameNatural Intelligence
Customer Number 
ePlanReviewNo
Description
(NATURAL INTELLIGENCE – BASEMENT – NORTHWEST CORNER) The fire sprinkler system substitutes for 1-hr fire-resistance-rated construction. To remodel an existing 4,293 square foot office tenant space located in the basement of an existing building. This tenant space was formerly occupied by “Idaho Business Review” under permit BLD06-00759. Work is to include removing interior nonbearing walls and interior finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The existing egress system is required to be maintained. The five parcels on this site will be consolidated into one parcel through a separate process. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/5/20202/6/20202/6/2020APASS
DetailsDave Hannah
Brian Phone #: ###-####
FIRE-Final Inspection2/5/20202/5/20202/5/2020PPASS
DetailsJim Page
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safetyy inspection for area of work complete, signatures provided on permit sign off card.
BLD-Final1/23/20201/24/20201/24/2020PNR
DetailsDave Hannah
Brian Phone #: ###-#### needs fire lifesaftey first
FIRE-Final Inspection1/23/20201/24/20201/24/2020AFAIL
DetailsJim Page
Provide access panels for in-duct smoke detectors. Sprinkler modifications are required in tenant space, multiple heads a less than 6 feet apart, multiple heads are blocked. Sprinkler head in female restroom has paint overspray on bulb as well as a painted upright next to main entry. Any and all modifications to fire sprinkler system requires a seperate permit before work can be started.

Brian Phone #: ###-####