BLD-Final | 2/5/2020 | 2/6/2020 | 2/6/2020 | A | PASS |
Dave Hannah
|
|
|
Brian Phone #: ###-####
|
FIRE-Final Inspection | 2/5/2020 | 2/5/2020 | 2/5/2020 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safetyy inspection for area of work complete, signatures provided on permit sign off card.
|
BLD-Final | 1/23/2020 | 1/24/2020 | 1/24/2020 | P | NR |
Dave Hannah
|
|
|
Brian Phone #: ###-#### needs fire lifesaftey first
|
FIRE-Final Inspection | 1/23/2020 | 1/24/2020 | 1/24/2020 | A | FAIL |
Jim Page
|
|
|
Provide access panels for in-duct smoke detectors. Sprinkler modifications are required in tenant space, multiple heads a less than 6 feet apart, multiple heads are blocked. Sprinkler head in female restroom has paint overspray on bulb as well as a painted upright next to main entry. Any and all modifications to fire sprinkler system requires a seperate permit before work can be started.
Brian Phone #: ###-####
|