Permit Information
Permit NumberBLD96-01074
StatusFinaled
Name TCI COMMUNICATIONS
Site Address 5800 N MEEKER AVE
Project NameTCI PHASE 4
Customer Number 
ePlanReviewNo
Description
(TCI COMMUNICATIONS) (PHASE 4 - TENANT IMPROVEMENT VANILLA FINISH PACKAGE) Fire sprinklers used for unlimited area of the building. To construct the vanilla finish interior improvements for a new existing 151,365 square foot 2 story building. Work is to include 1-hr fire-resistive corridors, access floor system, restrooms accessible to the disabled, kitchen with grease hoods, and interior nonbearing walls all per approved drawings and plan check notes on file. Separate electrical, plumbing, and mechanical permits are required. The occupant load of the dining room (270) shall be posted. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. PC-216-96 **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final8/4/19988/4/19988/4/1998APASS
DetailsCarl Dependahl
PHASE 4 TCI; CARD NOT SIGNED IN ERROR. (CLEAN-UP PENDING OCCUPANCY CARDS PER GS.)
INSP - Final8/4/1998 8/4/1998 PASS
final ok/ card not signed in error (wrong permit #'s may have been used during construction...this permit for "finish package" only... phased permit (#4)
Permanent Occupancy 4/4/19974/4/1997 DONE
Details
INSP - Final3/31/19974/2/19974/2/1997APASS
DetailsCarl Dependahl
04/02/97 340 - FINAL FOR C/O, OK CARD TO CONT
INSP - Conference3/10/19973/10/19973/10/1997 PASS
DetailsCarl Dependahl
/ / 340 - ACHD PAID PER SUPT...NEED P&Z & OTHER OK FOR C/O.
INSP - Conference2/10/19972/10/19972/10/1997 PASS
DetailsCarl Dependahl
/ / 340 - REC'D LETTER FROM CONT STATING THAT TCI STILL HAS NO AGREEME
INSP - Conference2/4/19972/4/19972/4/1997 PASS
DetailsCarl Dependahl
/ / 340 - W/ CONT RE FINAL, STILL NEED ACHD & P& Z OK...
INSP - Final1/29/19971/30/19971/30/1997PCANC
DetailsCarl Dependahl
01/30/97 340 - REINSPECT FOR C/O.
INSP - Conference1/7/19971/7/19971/7/1997 PASS
DetailsCarl Dependahl
/ / 340 - DISCUSSED PERM FINAL W/ JOE TAWNEY & STAN JOHNSON, NEED PLBG
INSP - Conference12/23/199612/23/199612/23/1996 PASS
DetailsCarl Dependahl
/ / 340 - RE PERM OCCUPANCY, NEED ALL SIGN OFFS
INSP - Conference12/13/199612/13/199612/13/1996 PASS
DetailsCarl Dependahl
/ / 340 - DISCUSSED EGRESS CONTROLL DEVICES, CITY POLICY
INSP - Carpentry11/26/199611/26/199611/26/1996 PASS
DetailsCarl Dependahl
/ / 340 - walk thru w/ supt.& Steve Duren; need ACHD, plbg.oks & respo control devices
INSP - Conference11/22/199611/22/199611/22/1996PPASS
DetailsCarl Dependahl
11/22/96 340 - DISCUSSED FINAL REQ'S, SIGN OFFS
INSP - Conference11/15/199611/15/199611/15/1996 PASS
DetailsCarl Dependahl
/ / 340 - REC'D LETTER FROM ARCH RE SMOKE TEST...NOT REQ'D PER BOB G. FLOOR ONLY
INSP - Carpentry11/7/199611/7/199611/7/1996 PART
DetailsCarl Dependahl
/ / 340 - CHK'D HOLD OPENS AT DBL DOORS AT CORR, REPAIR OF DOORS NOT L FOR T/O...NOT ALL COMPLETE, NEED TO SEE EGRESS CONTROL SYSTEM
INSP - Conference11/7/199611/7/199611/7/1996 PASS
DetailsCarl Dependahl
/ / 340 - TEL CONF W/ SUPT
INSP - Final11/1/199611/4/199611/6/1996APASS
DetailsCarl Dependahl
11/04/96 340 - W/ G.S. RE C/N ISSUED 11-4-96
INSP - Conference11/5/199611/5/199611/5/1996PPASS
DetailsCarl Dependahl
11/05/96 340 - HE WILL CALL FOR A TIME...CONSULTED W/ G SLANE RE C/N OF FOR T/O
INSP - Temporary occupancy11/5/199611/5/199611/5/1996 PASS
DetailsCarl Dependahl
/ / 340 - PARTIAL,ATRIUM,THEATER & KITCHEN NOT COMPLETED. C/N ISSUED. TO CONTRACTOR.
INSP - Final11/4/199611/4/199611/4/1996 FAIL
DetailsCarl Dependahl
11/01/96 340 - DOORS EARLY A.M...C/N, WILL CONSULT MGMT. PRIOR TO ISSUE COMPLETE AT ATRIUM, THEATER, & KITCHEN. NEED GENERATOR FOR TEST OF EMER. & SECURITY LOCKS & SMOKE CONTROL ACCEPTANCE
INSP - Final11/4/199611/4/199611/4/1996 NR
DetailsCarl Dependahl
11/01/96 340 - DOORS EARLY A.M...NEED F.DEPT. SIGN OFF PRIOR TO FINAL
INSP - Conference11/1/199611/1/199611/1/1996 PASS
DetailsCarl Dependahl
/ / 340 - W/MEL, SUPT. RE T/O FOR MAIN BLDG EXC. ATRIUM & THEATRE...W
INSP - Conference10/30/199610/31/199610/31/1996APASS
DetailsCarl Dependahl
10/31/96 340 - EARLY A.M. PLEASE!!!WANTS T/O, WILL CONSULT W/ MGMT
INSP - Conference10/29/199610/29/199610/29/1996APASS
DetailsCarl Dependahl
W/ STEVE DUREN RE: TEMP OCC. REQ'S
INSP - Framing/Rough-in10/25/199610/28/199610/28/1996APART
DetailsCarl Dependahl
10/25/96 340 - NORTH EAST STAIR TOWER - EARLEY MON. A.M. looks ok
INSP - Framing/Rough-in10/23/199610/24/199610/24/1996APART
DetailsCarl Dependahl
10/23/96 340 - FRAME & FIRE CAULKING FOR SOUTH STAIR TOWER. FIRE CAULING FLOOR.STAIR OK, CORRIDOR OK; NEED FILL IN GYP AT ROOMSIDE,2ND FL FRONT S QUAD 1
INSP - Conference10/23/199610/23/199610/23/1996PPASS
DetailsCarl Dependahl
W/ BOB A. RE:ENG'G LETTER FOR BEAM PROTECTION AS PER TIM HOGLAND
INSP - Framing/Rough-in10/22/199610/23/199610/23/1996PNR
DetailsJim Sly
10/23/96 316 - SOUTH STAIR TOWER. NR.
INSP - Carpentry10/22/199610/22/199610/22/1996 PART
DetailsJim Sly
/ / 316 - Partial inspection of corridors and ceiling grid.
INSP - Ceiling grid10/21/199610/22/199610/22/1996APART
DetailsCarl Dependahl
10/21/96 340 - FIRE CAULKING AND CEILING GRID...NEED TO COMPLETE CAULKIN LID AT SO. STAIRS...CLG SEISMIC OK AT CAFETERIA
INSP - Carpentry10/18/199610/21/199610/21/1996APART
DetailsJim Sly
10/21/96 316 - EARLY A.M. FIRE CAULING SOUTH CORRIDORS. MISC. AREAS SEIZ CEILING GRID. Partial OK.
INSP - Carpentry10/17/199610/17/199610/17/1996PCANC
Details
10/17/96 333 - FIRE CAULKING SOUTH HALF. SEIZMIC ON CEILING GRID - SOUT Jim Sly did this morning
INSP - Carpentry10/16/199610/17/199610/17/1996ANR
DetailsCarl Dependahl
10/16/96 340 - FIRECAULKING - SOUTH HALF SEIZMIC ON CEILING GRID -SOUTH SIDE...sent in error, referred to 316
INSP - Framing/Rough-in10/17/199610/17/199610/17/1996 PART
DetailsJim Sly
/ / 316 - Corridor Caulking. Ceiling Grid....PART.
INSP - Conference10/16/199610/16/199610/16/1996 PASS
DetailsCarl Dependahl
/ / 340 - 1HR DETAIL FOR STAIR LIDS IN SPEC BOOK...OK AS FRAMED
INSP - Carpentry10/15/199610/15/199610/15/1996 PART
DetailsCarl Dependahl
/ / 340 - CHK ROOF AT ATRIUM ENCLOSURE
INSP - Carpentry10/11/199610/14/199610/14/1996APART
Details
10/11/96 230 - FIRE CAULING ON NORTH/SOUTH CORRIDORS. CEILING GRID QUAD PART, NEED COMPLETE CAULKING AT 1ST FL CORR, SEAL AT STAIR & CORR 2ND FL WALLS AT ROOMSIDE WEST/FRONT STAIR
INSP - Framing/Rough-in10/14/199610/14/199610/14/1996APART
DetailsCarl Dependahl
CHK'D FIRESTOPS & CLG, VARIOUS AREAS, MET W/ SLY. INSP SENT VIA LAPTOP HAS DISAPPEARED FROM PPLAN SCREENS???
INSP - Framing/Rough-in10/14/199610/14/199610/14/1996 PART
DetailsJim Sly
/ / 316 - Inspection of misc....Carl D, Lamar, and J Sly.
INSP - Conference10/11/199610/11/199610/11/1996 PASS
DetailsCarl Dependahl
/ / 340 - EXAMINED FIRE PROTECTION ENGR'S SUBMITTAL FOR SPRINKLER PROT CORRIDOR AREAS; ALTERNATE PER TIM HOGLAND. APPEARS OK. CONSULTED W/ BOB DAVE MILLER (FD)
INSP - Miscellaneous10/10/199610/11/199610/11/1996AFAIL
DetailsJim Sly
10/10/96 316 - FIRE CAULKING IN CORRIDORS ASAP 2HR walk thru of corridors with Mech, Elect, and gyp subs, and Lamar.
INSP - Carpentry10/9/199610/10/199610/11/1996APART
DetailsCarl Dependahl
10/10/96 340 - FIRE CAULKING - CORRIDORS 1ST FLR. SEISMIC CEILING. 2ND FLR. SEISMIC CEILING....EARLY A.M.
INSP - Framing/Rough-in10/8/199610/9/199610/9/1996PPART
DetailsCarl Dependahl
10/09/96 340 - STAIR TOWERS CHK LID FRAMING & FIRESTOPPING, OK
INSP - Conference10/8/199610/8/199610/8/1996 PASS
DetailsCarl Dependahl
/ / 340 - W/ DAVE MILLER & BOB G...NEED CLARIFICATION OF F.P. ENG'S SU PROTECTION; IS LETTER ADEQUATE?
INSP-Sprinkler Rough-in/Hydro10/7/199610/8/199610/8/1996 PASS
PARTIAL ROUGH IN OF SPKLR SYSTEM
INSP - Framing/Rough-in10/4/199610/7/199610/7/1996AFAIL
DetailsJim Sly
10/07/96 316 - EARLY A.M. STAIR TOWER CEILING-FRONT ENTRY LOBBY-SKYBRIDG CAULKING CORRIDORS. C/N For APPROV OF RE-SUB DRAW FOR SPRINK CORR, STA
INSP - Framing/Rough-in10/3/199610/4/199610/4/1996APART
DetailsJim Sly
10/03/96 316 - ROOM OFFICE 10-60 10-61 10-62 GRID D-6 7-4, ENTRENCE TO T BATH COR 10-89 OPEN OFFICE 10-81 AND COR 10-14 AND AJOINING OFFICES. C/N for misc penitrations and safing insulation.
INSP - Conference10/3/199610/3/199610/3/1996 PASS
DetailsCarl Dependahl
/ / 340 - discussed finish & c/o reqs w/ Lavar, ass't supt
INSP - Framing/Rough-in10/2/199610/3/199610/3/1996AFAIL
DetailsCarl Dependahl
10/02/96 340 - 1ST THING THURS.A.M. HALL ADJACENT TO THEATRE.BATHRMS.1117 - 1010. left c/n to fasten gyp, tie lites, seal penetrations
INSP - Miscellaneous10/1/199610/2/199610/3/1996AFAIL
DetailsJim Sly
10/02/96 316 - FIRE CAULKING, COORIDOR #1014 ETC. ALSO SEE FRAMING/ROUGH-IN AND CEILING GRID INSPECTIONS SCHEDULED AT SAME BUILDING, SAME TIME Carl and I ...Misc insp.....C/N.
INSP - Ceiling grid10/1/199610/2/199610/2/1996ACANC
DetailsJim Sly
10/01/96 316 - CEILING GRID -- ALSO SEE FRAMING ROUGH-IN AND MISC. INSPE SAME BUILDING, SAME TIME. CANCEL TO PM........ I WAS GIVEN AREAS TO INSPECT, BUT FOR SOME REASON THEY DIDN'T SHOW UP IN NOTES. THERE WAS A LARGE COORIDOR AREA AND ADJOI
INSP - Conference10/2/199610/2/199610/2/1996 PASS
DetailsCarl Dependahl
/ / 340 - W/ JIM SLY, HE WAS SENT INSP'S IN ERROR...CHK'D HIS NOTES FO
INSP - Framing/Rough-in10/1/199610/2/199610/2/1996ACANC
DetailsJim Sly
10/01/96 316 - THEATER CEILING, WOMEN'S #1091, COORIDOR #1089 ALSO SEE CEILING GRID AND MISCELLANEOUS INSPECTIONS SCHEDULE FOR SAME BUILDING, SAME TIME. CANCEL TIL PM.....
INSP - Letter of compliance10/2/199610/2/199610/2/1996 CANC
DetailsJim Sly
/ / 316 - Cancel to PM.
INSP - Letter of compliance10/2/199610/2/199610/2/1996 CANC
DetailsJim Sly
/ / 316 - Cancel to PM.
INSP-Sprinkler Rough-in/Hydro10/2/199610/2/199610/2/1996PNR
DetailsJoe Tawney
10/02/96 406 - CALL JASON LANDON - ###-####
INSP - Framing/Rough-in9/30/199610/1/199610/1/1996APART
DetailsJim Sly
09/30/96 316 - CEILING - HALL ADJACENT TO THEATRE BATHRMS.1###-####. Misc Inspections complete....Log sheet at job shack. C/N Need detail for attachment of framed ceiling in theater.
INSP - Framing/Rough-in9/27/19969/30/19969/30/1996APART
DetailsJim Sly
09/27/96 316 - Inspection of rated wall penitrations in misc restrooms, and misc. List on back of occ. card. Inspection of frame ceiling in theater...Need mechanical rough-in inspection.
INSP - Conference9/27/19969/27/19969/27/1996 PASS
DetailsCarl Dependahl
/ / 340 - W/ CARL WESTFALL RE STAIR LID
INSP - Conference9/27/19969/27/19969/27/1996 PASS
DetailsCarl Dependahl
/ / 340 - W/ CARL WESTFALL RE STAIR LID
INSP - Carpentry9/26/19969/26/19969/26/1996 PART
DetailsCarl Dependahl
/ / 340 - NEED ARCHS DETAIL RE LID AT STAIRS,PLAN SHOWS GYP W/O DETAIL
INSP - Carpentry9/26/19969/26/19969/26/1996 PART
DetailsCarl Dependahl
/ / 340 - NEED ARCHS DETAIL RE LID AT STAIRS,PLAN SHOWS GYP W/O DETAIL
INSP - Conference9/24/19969/24/19969/24/1996 PASS
DetailsCarl Dependahl
/ / 340 - W/ MEL S. SUPT. RE ENG'S FIRE PROTECTION REPORT AT CORRIDORS
INSP - Framing/Rough-in9/24/19969/24/19969/24/1996 PART
DetailsCarl Dependahl
/ / 340 - GREASE DUCT PABCO LINER OK, SHAFT AT 2ND FL PART SEALED ,OK INSTALL 1" SHAFTWALL SYSTEM TO DECK; STILL NEED FIRESTOP RATED WALL PENETRATIONS, MANY MISSED. REQUESTED DETAIL RE GYP LID AT STAIRS AT END BLDG, NO DETAIL W/ PLAN
INSP - Carpentry9/23/19969/23/19969/23/1996PPASS
DetailsCarl Dependahl
PART, SENT RESPONSE TO ARCH. TO MEL SCHUMAKER AT JOB & RAY HOOBING AT CM CO.
INSP - Ceiling grid9/20/19969/23/19969/23/1996APASS
DetailsJim Sly
09/20/96 316 - Ceiling grid OK at 2nd floor northwest corner...large roo 2nd floor south west corner...large room to beam (divider). Both sections exclude adjacent small rooms.
INSP - Conference9/23/19969/23/19969/23/1996PPASS
DetailsCarl Dependahl
W/ BOB G. RE LETTERSENT BY RAY HOOBING OF CM CO. WE'VE REQUESTED FIRE PROTECTION ENG'S APPROVAL AS ALTERNATE TO ENCLOSING 1HR. CORRIDORS & T RATING PER TIM H.
INSP - Conference9/19/19969/19/19969/19/1996 PASS
DetailsCarl Dependahl
/ / 340 - CONF RE C/N OF 9-11 W/ GS
INSP - Carpentry9/17/19969/18/19969/18/1996PPART
DetailsCarl Dependahl
09/17/96 340 - FIRE INSULATION ON KITCHEN DUCT/TCI PART, NEED TO COMPLETE MASTIC AND CLEAN-OUT ACCESS COVERS PER PABCO SPEC
INSP - Conference9/17/19969/17/19969/17/1996 PASS
DetailsCarl Dependahl
/ / 340 - MET W/ ARCH. RODNEY MORRISON; HE PRESENTED HIS RATIONALE FOR RATING AT PENETRATIONS. WILL ALSO HAVE "CODE EXPERT" CHK. IWILL TAKE UND ADVISEMENT. INFORMED GS & DNH. NO RESOLUTION AS YET. KEEP CN
INSP - Conference9/17/19969/17/19969/17/1996PCANC
DetailsJim Sly
09/17/96 316 - WANTS TO TALK TO CARL - I called Carl...Carl to do.
INSP - Conference9/13/19969/13/19969/13/1996PPASS
DetailsCarl Dependahl
09/13/96 340 - CONF W/ MEL S, STEVE DUREN, & LAVAR RE C/N OF 9-11-96...C MORRISEY RE CORR & SHAFT PENETRATIONS. KEEP C/N
INSP - Framing/Rough-in9/11/19969/11/19969/11/1996 FAIL
DetailsCarl Dependahl
/ / 340 - C/N, NEED T RATING AT STRUCTURAL PENETRATIONS AT CORRIDORS A DETAIL FOR ALTERNATE. UBC 711 & 1004
INSP - Framing/Rough-in9/11/19969/11/19969/11/1996PCANC
DetailsJim Sly
09/11/96 316 - DUCT WORK AND SHAFTS AND FIRE COCKING LET OPEN Cancel....Gave to C. Dependahl.
INSP - Conference9/9/19969/9/19969/9/1996 PART
DetailsCarl Dependahl
/ / 340 - FIREMASTER BLANKET SUBMITTAL INFO
INSP - Conference9/9/19969/9/19969/9/1996 PART
DetailsCarl Dependahl
/ / 340 - FIREMASTER BLANKET SUBMITTAL INFO
INSP - Conference9/5/19969/5/19969/5/1996 PASS
DetailsCarl Dependahl
/ / 340 - w/DICK BREWER OF 3M CO; WILL SEND CREDENTIALS OF POSSIBLE SP FACTORY TECH ENG'S FOR FIREMASTER INSUL SYSTEM...ALSO DISCUSSED W/ BOB GARRISON
INSP - Conference9/4/19969/4/19969/4/1996 PASS
DetailsCarl Dependahl
/ / 340 - DISCUSSED FIREMASTER GREASE DUCT PROTECTION SYSTEM W/ BOB GA ICBO, THE PRODUCT HAS SBCCI OK AND PENDING ICBO OK. ALSO OK FOR PROTECTI STRUCT MEMBERS. GAVE CONT TENTATIVE OK TO USE IF SPEC. INSP USED
INSP - Conference9/4/19969/4/19969/4/1996 PASS
DetailsCarl Dependahl
/ / 340 - DISCUSSED FIREMASTER GREASE DUCT PROTECTION SYSTEM W/ BOB GA ICBO, THE PRODUCT HAS SBCCI OK AND PENDING ICBO OK. ALSO OK FOR PROTECTI STRUCT MEMBERS. GAVE CONT TENTATIVE OK TO USE IF SPEC. INSP USED
INSP - Conference9/3/19969/3/19969/3/1996 PART
DetailsCarl Dependahl
/ / 340 - SUBMITTAL DOC'S FOR FIREMASTER DUCT INSUL SYSTEM W/ BARRY HO CALL IN TO ICBO
INSP - Conference8/30/19968/30/19968/30/1996 PASS
DetailsCarl Dependahl
/ / 340 - W/YMC RE SHAFT & DUCT INSUL...NEED ARCH'S LETTER RE SHAFT, M FIREMASTER SYSTEM
INSP - Carpentry8/29/19968/29/19968/29/1996 FAIL
DetailsCarl Dependahl
/ / 340 - chk'd shaft at grease ducts & hvac; rec'd resub for grease d NER for ok. Asked for arch's clarification of shafts thru floor
INSP - Conference8/28/19968/28/19968/28/1996 PASS
DetailsCarl Dependahl
/ / 340 - NEED MANUF'S INSTRUCTION FOR PABCO DUCT SYSTEM; RESUBMITTAL DUCT SYSTEM FOR APPROVAL...KEEP FRAME C/N
INSP - Carpentry8/26/19968/27/19968/27/1996AFAIL
DetailsCarl Dependahl
08/27/96 340 - DUCT INSULATION - GENERAL TYPE INSP....... KEEP C/N, NEED CLARIFICATION ON SHAFT
INSP - Framing/Rough-in8/26/19968/26/19968/26/1996PNR
Details
08/26/96 333 - given to jim
INSP - Framing/Rough-in8/8/19968/8/19968/8/1996 PART
DetailsJim Storey
/ / 301 - framing ok for one side cover of fire rated const. bottom of completed
INSP - Framing/Rough-in8/6/19968/6/19968/7/1996PPART
DetailsJim Storey
08/06/96 301 - 1ST & 2ND FLOORS... FRAM-OK FRAMING CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Framing/Rough-in7/23/19967/24/19967/24/1996APART
DetailsJim Storey
07/24/96 301 - trans carl
INSP - Conference7/19/19967/19/19967/19/1996 PASS
DetailsCarl Dependahl
/ / 340 - CONF W/ MEL SHUMAKER, FLOYD V. & JOE TAWNY
INSP - Conference7/16/19967/16/19967/16/1996 PART
DetailsCarl Dependahl
/ / 340 - REQ'S FOR FIRESTOPPING & ENG'S ACCEPTANCE. KEEP CN
INSP - Framing/Rough-in7/12/19967/12/19967/12/1996PFAIL
DetailsCarl Dependahl
07/12/96 340 - 2nd flr. n/w & s/w quadrant p.m. C/N, NEED ENG'S OK, FIRESTOPS,ID STEEL STUDS,COMPLETE SHAFTS
INSP - Footings7/11/19967/11/19967/11/1996PNR
DetailsCarl Dependahl
07/11/96 340 - 2nd flr. n/w & s/w quadrant TCI...NOT FTG BUT FRAME INSP...NEED MECH OK. HAS BACK ORDERED SMOKE-FIRE DAMPERS. MULTIPLE PERMITS
INSP - Conference6/28/19966/28/19966/28/1996 PASS
DetailsCarl Dependahl
/ / 340 - T/I ISSUED?...CHK'D PLAN DETAIL RE PRECAST "GUTTER" W/ MEL S