INSP-Conference | 7/2/1998 | 7/2/1998 | 7/2/1998 | | PART |
Joe Tawney
|
|
|
/ / 406 - CONF ON EXIT DOORS FROM ALTZHEIMER'S WING OWNER HAD CHANGED
|
INSP - Final | 5/12/1997 | 5/12/1997 | 5/12/1997 | P | PASS |
Carl Dependahl
|
|
|
05/12/97 340 - he said he only had two but gave me three numbers C/N OK, CARD TO CONT.
|
INSP - Final | 5/12/1997 | 5/12/1997 | 5/12/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - REINSP FOR FINAL OK FOR PERM OCC
|
INSP - Final | 5/12/1997 | 5/12/1997 | 5/12/1997 | | PART |
Joe Tawney
|
|
|
/ / 406 - FINAL PARTIAL SPKLR SYSTEMS OK ALARM SYSTEM & DOORS STILL
|
INSP - Framing/Rough-in | 5/12/1997 | 5/12/1997 | 5/12/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - FIRESTOPS OK
|
INSP - Final | 5/9/1997 | 5/9/1997 | 5/9/1997 | P | FAIL |
Carl Dependahl
|
|
|
05/09/97 340 - D & C WING, KEEP C/N
|
INSP - Carpentry | 5/7/1997 | 5/8/1997 | 5/8/1997 | P | PASS |
Carl Dependahl
|
|
|
05/08/97 340 - THIS GUY SAID YOU SAID TO BE SURE & HAVE ME GIVE THIS TO recarpet, rise, run look ok; keep c/n other items
|
INSP - Conference | 5/7/1997 | 5/7/1997 | 5/7/1997 | P | PASS |
Carl Dependahl
|
|
|
05/07/97 340 - RE STAIRS, SPOKE W/ BILL HARDT, SUPT. TOLD TO FINISH WORK
|
INSP - Conference | 5/7/1997 | 5/7/1997 | 5/7/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE STAIRS, LIFE SAFETY, KEEP CN
|
INSP - Final | 4/30/1997 | 5/6/1997 | 5/6/1997 | A | FAIL |
Joe Tawney
|
|
|
HE WOULD LIKE THIS AT 10 A.M. A MAN FROM HEALTH DEPT.WANTS TO MEET THERE AT THIS TIME. BILL HART ###-####. FINAL INSP FAIL DP SYSTEM DID NOT MEET TIME DOOR HDWRE & SMOKE SEALS NOT INSTALLED SPKLR PROTECTION NEEDED IN STAIR WELLS ALARMS IN HANDICAP ROOMS STROBES NOT PROP PLACED IN CORRIDORS PAINT & STRIPE CURBS ROTATE HYDRANT
|
INSP - Final | 4/30/1997 | 5/6/1997 | 5/6/1997 | A | FAIL |
Carl Dependahl
|
|
|
05/06/97 340 - BILL HART - ###-####. WANTS TO MEET AT 10 A.M. C/N, NEED FIRESTOPS, ETC PARTONLY, C WING
|
INSP - Conference | 5/5/1997 | 5/5/1997 | 5/5/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - D WING; FINAL REQS, NEED FIRE, HEALTH ETC
|
INSP-Final Inspection | 5/2/1997 | 5/2/1997 | 5/2/1997 | | FAIL |
|
|
|
TRIP TEST ON DRY SYSTEM FAIL 87 SEC TO FIRST WATER/AIR 125 SEC TO SOLID STREAM
|
INSP - Conference | 4/24/1997 | 4/25/1997 | 4/25/1997 | A | PASS |
Carl Dependahl
|
|
|
04/25/97 340 - STAIR RAILS, TREADS
|
INSP-Sprinkler Rough-in/Hydro | 4/22/1997 | 4/23/1997 | 4/23/1997 | P | PART |
Joe Tawney
|
|
|
04/23/97 406 - HYDRO TEST OF WET SYSTEMS OK ON HYDRO TEST
|
INSP-Supply line flush | 4/21/1997 | 4/21/1997 | 4/21/1997 | | PART |
Joe Tawney
|
|
|
/ / 406 - FLUSH TEST OK
|
INSP - Carpentry | 4/17/1997 | 4/17/1997 | 4/17/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - FIRESTOPS, 1HR FINISH, STAIRS
|
INSP - Conference | 4/14/1997 | 4/15/1997 | 4/15/1997 | A | PASS |
Carl Dependahl
|
|
|
04/15/97 340 - CONF. ON FIRE CAULKING, ETC.
|
INSP - Wall cover | 4/9/1997 | 4/9/1997 | 4/9/1997 | P | PART |
Carl Dependahl
|
|
|
04/09/97 340 - corridor lids for fire penetrations
|
INSP - Carpentry | 4/8/1997 | 4/8/1997 | 4/8/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - CHK PROGRESS
|
INSP - Carpentry | 4/8/1997 | 4/8/1997 | 4/8/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - CHK PROGRESS FOR FINAL
|
INSP - Conference | 4/7/1997 | 4/7/1997 | 4/7/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - HANDRAIL REQ'S FOR FINAL
|
INSP - Set-back | 4/1/1997 | 4/1/1997 | 4/1/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - D WING FINAL REQ'S
|
INSP - Conference | 3/28/1997 | 3/28/1997 | 3/28/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/SUPT. RE REQ'D SIGNAGE, ADDRESSES ETC FOR FINAL
|
INSP - Carpentry | 3/19/1997 | 3/20/1997 | 3/20/1997 | A | FAIL |
Carl Dependahl
|
|
|
03/20/97 340 - KEEP C/N RE FIRESTOPS, D WING CORRIDOR SIDE WALLS
|
INSP - Carpentry | 3/18/1997 | 3/18/1997 | 3/18/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - FIRESTOPPING AT CORR WALLS, GEN'L WALK THRU; NEED COMPLETE S
|
INSP-Conference | 3/18/1997 | 3/18/1997 | 3/18/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - CONF ALARM SYSTEMS GC ADV SIMPLEX IS WORKING ON SUBMITTAL
|
INSP - Conference | 3/13/1997 | 3/13/1997 | 3/13/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/SUPT. RE REQUEST FOR SHAFT DETAIL
|
INSP - Carpentry | 3/11/1997 | 3/11/1997 | 3/11/1997 | P | PART |
Carl Dependahl
|
|
|
03/11/97 340 - 2 HR. WALL AND CHECK VENTILATION SHAFT FOR HOOD IN KITCHE SHAFT
|
INSP - Carpentry | 3/10/1997 | 3/10/1997 | 3/10/1997 | P | PART |
Carl Dependahl
|
|
|
03/10/97 340 - 2 HR. WALL; PART, STILL NEED COMPLETE DETAIL; 1ST LAYER O
|
INSP - Carpentry | 3/6/1997 | 3/6/1997 | 3/5/1997 | P | CANC |
|
|
|
03/06/97 338 - DRYWALL cancelled by dixie
|
INSP - Carpentry | 3/4/1997 | 3/5/1997 | 3/5/1997 | P | PART |
Carl Dependahl
|
|
|
03/05/97 340 - D WING CORR, NEED COMPLETE FIRESTOP AT SPRINKLER & ELEC,P
|
INSP - Conference | 2/28/1997 | 3/3/1997 | 3/3/1997 | A | FAIL |
Carl Dependahl
|
|
|
03/03/97 340 - C/N, NEED SMOKE /FIRE AT 2HR WALL E. SIDE ASSY AREA D WIN
|
INSP - Carpentry | 2/28/1997 | 2/28/1997 | 2/28/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - FIRESTOPS AT PLBG THRU 2ND FL; NEED FURHER INSP
|
INSP - Conference | 2/25/1997 | 2/25/1997 | 2/25/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - DISCUSSED 2HR WALL DETAIL REJECTED W SUPT.
|
INSP - Conference | 2/20/1997 | 2/20/1997 | 2/20/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE PREVIOUS C/N, STILL NEED 2HR WALL DETAILS
|
INSP - Carpentry | 2/14/1997 | 2/14/1997 | 2/14/1997 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - NEED ADD'L FIRESTOP AT SHOWERS, P-TRAPS THRU 1HR FLOORS. THR SPRINKLER R/I. C WING
|
INSP - Conference | 2/14/1997 | 2/14/1997 | 2/14/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - w/ lenny of debest plbg re firestops
|
INSP - Carpentry | 2/11/1997 | 2/11/1997 | 2/11/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - C WING; OK TO INSUL & PLACE 1ST LAYER LIDS; INSUL CAT WALK F
|
INSP - Conference | 2/11/1997 | 2/11/1997 | 2/11/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - SPOKE W/ SODERSTROM ARCH'S: WILL SUBMIT DETAIL RE 2 HR WALLS INCREASE BY YARD SEPARATION. WILL CONSULT W/ JOHN MENARD
|
INSP - Carpentry | 2/10/1997 | 2/10/1997 | 2/10/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - 1hr ext. d wing
|
INSP - Carpentry | 2/7/1997 | 2/7/1997 | 2/7/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - lath & ext gyp; need spec for 1hr
|
INSP - Conference | 2/5/1997 | 2/5/1997 | 2/5/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE 2HR WALL REQ'S; NEED ARCH'S DETAIL TO MODIFY
|
INSP - Carpentry | 2/4/1997 | 2/4/1997 | 2/4/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - DWING & KITCHEN AREA, SHEAR NAILING AT CROSS WALL OK
|
INSP - Conference | 2/3/1997 | 2/3/1997 | 2/3/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE 1HR AT D WING
|
INSP - Carpentry | 1/30/1997 | 1/30/1997 | 1/30/1997 | | NR |
Carl Dependahl
|
|
|
/ / 340 - NEED PROPER NAILING AT GYP SHEAR PANELS, DISCUSSED W/ FOREMA
|
INSP - Wall cover | 1/30/1997 | 1/30/1997 | 1/30/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - 1ST LAYER LIDS AT UNIT BATHS OK, D WING
|
INSP - Carpentry | 1/29/1997 | 1/29/1997 | 1/29/1997 | P | PASS |
Carl Dependahl
|
|
|
01/29/97 340 - chk plbg penetrations; all ok on unit side D wing
|
INSP - Carpentry | 1/28/1997 | 1/28/1997 | 1/29/1997 | P | PASS |
Carl Dependahl
|
|
|
01/28/97 340 - FIRESTOPS AT PLBG, OK TO COVER BATH LIDS, D WING
|
INSP - Carpentry | 1/27/1997 | 1/27/1997 | 1/27/1997 | P | PART |
Carl Dependahl
|
|
|
01/27/97 340 - D WING, OK FOR 1ST LAYER LIDS AT UNITS, EXCEPT 123 AND AD
|
INSP - Carpentry | 1/23/1997 | 1/24/1997 | 1/24/1997 | A | FAIL |
Carl Dependahl
|
|
|
01/24/97 340 - KEEP C/N
|
INSP - Carpentry | 1/23/1997 | 1/23/1997 | 1/23/1997 | P | FAIL |
Carl Dependahl
|
|
|
01/23/97 340 - KEEP C/N, NEED COMPLETE FIRESTOPPING AT WALL PENETRATIONS
|
INSP - Wall cover | 1/22/1997 | 1/22/1997 | 1/22/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - D WING, 1ST LAYER LID OK AT UNITS EXCEPT AT BATHS...NEED COM AT PENETRATIONS & NEW DETAIL FROM DEBEST PLBG.
|
INSP - Energy code compliance | 1/21/1997 | 1/21/1997 | 1/21/1997 | P | PART |
Carl Dependahl
|
|
|
01/21/97 340 - PART. EXT WALLS
|
INSP - Framing/Rough-in | 1/21/1997 | 1/21/1997 | 1/21/1997 | P | PART |
Carl Dependahl
|
|
|
01/21/97 340 - PART, NEED COMPLETE FIRESTOPPING AT UNIT SIDE WALLS AT BA EXCPT LIDS THAT AREA OF D WING. REC'D RESUBMITTAL FOR DELETION OF 2 HR. WALL AT S.E. D WING, OK PER JOHN MENARD
|
INSP - Carpentry | 1/17/1997 | 1/17/1997 | 1/17/1997 | P | PART |
Carl Dependahl
|
|
|
01/17/97 340 - NEED CHK DETAIL FOR 1HR LID
|
INSP - Energy code compliance | 1/17/1997 | 1/17/1997 | 1/17/1997 | P | FAIL |
Carl Dependahl
|
|
|
01/17/97 340 - NR, NEED COMPLETE INS AT EXT WALLS
|
INSP - Conference | 1/16/1997 | 1/16/1997 | 1/16/1997 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - c/n, req'd revised plan for deletion of 2 hr. area wall at s
|
INSP - Framing/Rough-in | 1/15/1997 | 1/16/1997 | 1/16/1997 | P | FAIL |
Carl Dependahl
|
|
|
01/16/97 340 - KEEP C/N, OK TO INSUL; NEED ACCESS PANELS AT SPRINLER DRI
|
INSP-Sprinkler Rough-in/Hydro | 1/15/1997 | 1/16/1997 | 1/16/1997 | P | PART |
Joe Tawney
|
|
|
RANDY - ###-#### OK ON ROUGH IN AND HYDRO TESTS FOR WET AND DRY SYSTEMS IN WING D ONLY
|
INSP - Conference | 1/15/1997 | 1/15/1997 | 1/15/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE SPRINKLER R/I OK, NEED PRIOR TO OK OF FRAME...D WING
|
INSP - Framing/Rough-in | 1/14/1997 | 1/15/1997 | 1/15/1997 | P | FAIL |
Carl Dependahl
|
|
|
01/15/97 340 - NEED FIRE SPRINKLER R/I & RESUB FOR 2HR AREA WALL. ETC
|
INSP - Carpentry | 1/10/1997 | 1/10/1997 | 1/10/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - CHK1ST LAYER ROCK AT CORR. LID WEST OF MULTI PURPOSE RM OK. STRAPS & STUD SHOES W/ PLBR
|
INSP - Framing/Rough-in | 1/9/1997 | 1/9/1997 | 1/9/1997 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - C/N, NEED RESUBMITTAL AT AREA SEP. WALL EAST SIDE D WING, CO FIRESTOP ALL WALL & LID PENETRATIONS
|
INSP - Conference | 1/6/1997 | 1/6/1997 | 1/6/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE C/N & 2 HR WALLS
|
INSP - Framing/Rough-in | 1/3/1997 | 1/6/1997 | 1/6/1997 | A | FAIL |
Carl Dependahl
|
|
|
01/06/97 340 - NEED TO COMPLETE FIRESTOPPING AT 2HR WALL PENETRATIONS... CORRIDOR SIDE, D WING
|
INSP - Carpentry | 12/31/1996 | 12/31/1996 | 12/31/1996 | P | PASS |
Carl Dependahl
|
|
|
12/31/96 340 - OK TO COVER CORR. SIDE ONLY D WING
|
INSP - Carpentry | 12/30/1996 | 12/30/1996 | 12/30/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE CORRIDOR OR EXIT PASSWAY AT ALZHEIMERS WING...WILL DISCUS
|
INSP - Conference | 12/23/1996 | 12/23/1996 | 12/23/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE INSP PROCESS, NEED OTHER TRADES PRIOR TO FULL FRAME INSP
|
INSP - Carpentry | 12/19/1996 | 12/19/1996 | 12/19/1996 | P | PASS |
Carl Dependahl
|
|
|
12/19/96 340 - REQESTED DETAIL FOR FIRESTOPPING AT PLBG PENETRATIONS. 2N PANELS ON 2HR WALL. OK TO ROCK CORRIDOR LIDS & WRAP BEAMS AT ALZHEIMER W
|
INSP - Conference | 12/19/1996 | 12/19/1996 | 12/19/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE RATED CLG ACCESS PANELS
|
INSP - Carpentry | 12/18/1996 | 12/18/1996 | 12/18/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 - FACE LAYER GYP AT 2HR WALL AT ELECPANELS, PART
|
INSP - Carpentry | 12/17/1996 | 12/17/1996 | 12/17/1996 | P | PART |
Carl Dependahl
|
|
|
12/17/96 340 - 2HR WALL PRE ROCK AT ELEC PANELS
|
INSP - Carpentry | 12/12/1996 | 12/12/1996 | 12/12/1996 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - CHK PENETRATIONS....NEED COMPLETE FIRESTOPPING
|
INSP - Framing/Rough-in | 12/12/1996 | 12/12/1996 | 12/12/1996 | P | NR |
Carl Dependahl
|
|
|
12/12/96 340 -
|
INSP - Carpentry | 12/10/1996 | 12/11/1996 | 12/11/1996 | P | NR |
Carl Dependahl
|
|
|
12/11/96 340 - DRY WALL, NR, NEED TO WRAP BEAMS ACROSS CORRIDOR
|
INSP - Framing/Rough-in | 12/9/1996 | 12/10/1996 | 12/10/1996 | A | PART |
Carl Dependahl
|
|
|
12/10/96 340 - part, 1st layer corridor lid d sec...2nd layer ok,keep c/ wall "jog"
|
INSP - Conference | 12/9/1996 | 12/9/1996 | 12/9/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - TOLD TO SUBMIT DETAIL FOR COMM'L TYPE 1 HOOD, WILL SEND
|
INSP - Framing/Rough-in | 12/4/1996 | 12/4/1996 | 12/5/1996 | P | NR |
Jim Sly
|
|
|
12/04/96 316 - Not Ready
|
INSP - Framing/Rough-in | 11/27/1996 | 11/27/1996 | 11/27/1996 | P | FAIL |
Carl Dependahl
|
|
|
11/27/96 340 - SEC. D; C/N, NOT FULL FRAME INSP, NEED SCREWS AT GYP LID RESUBMIT
|
INSP - Conference | 11/25/1996 | 11/25/1996 | 11/25/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/SUPT. & GRISHAM DRYWALL: NEED APPROVED DETAIL FOR 1HR LID SUBMIT
|
INSP - Carpentry | 11/21/1996 | 11/21/1996 | 11/21/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 - VERBAL C/N TO FOLLOW 1HR CLG DETAIL SUBMITTED; OK TO PRE ROC CORRIDOR AT SECTION D (ALZHEIMERS WING) PART OK GAS TEST AT SAME BY S.Y.
|
INSP - Framing/Rough-in | 11/20/1996 | 11/21/1996 | 11/21/1996 | P | CANC |
|
|
|
11/21/96 338 - EARLY PM PLEASE
|
INSP - Framing/Rough-in | 11/20/1996 | 11/20/1996 | 11/20/1996 | P | FAIL |
Carl Dependahl
|
|
|
11/20/96 340 - NR, NEED ARCH'S DETAIL. KEEP C/N
|
INSP - Conference | 11/19/1996 | 11/19/1996 | 11/20/1996 | P | PASS |
Carl Dependahl
|
|
|
11/19/96 340 - NR, KEEP C/N, NEED ARCH'S DETAIL.WILL RECALL
|
INSP - Framing/Rough-in | 11/18/1996 | 11/18/1996 | 11/18/1996 | P | FAIL |
Carl Dependahl
|
|
|
11/18/96 340 - C/N NEED FIRESTOP SPECS & DETAIL FOR 2HR WALL JOG W/ TRUS
|
INSP - Conference | 11/15/1996 | 11/15/1996 | 11/15/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/BOB, SUPT. RE SHEAR WALLS
|
INSP - Conference | 11/15/1996 | 11/15/1996 | 11/15/1996 | P | CANC |
|
|
|
11/15/96 338 - CALL BOB ALVERSON ###-#### done by 340
|
INSP - Conference | 11/7/1996 | 11/8/1996 | 11/8/1996 | A | FAIL |
Carl Dependahl
|
|
|
11/07/96 340 - C/, NEED DETAIL FOR 2HR WALL AND FIRESTOPS
|
INSP - Conference | 11/7/1996 | 11/7/1996 | 11/7/1996 | P | PASS |
Carl Dependahl
|
|
|
11/07/96 340 - W/ SUPT RE ELEC PENETRATIONS
|
INSP - Conference | 11/5/1996 | 11/5/1996 | 11/5/1996 | P | PASS |
Carl Dependahl
|
|
|
1HR CONST...PRE ROCK FOR CORRIDOR WALL AREA. TOLD SUPT. WE NEED INSP PRIOR TO COVER
|
INSP - Carpentry | 10/28/1996 | 10/28/1996 | 10/28/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 - BEGINNING FRAMING; 1HR THRU-OUT,PRE ROCK BEHIND TUBS ETC.
|
INSP - Conference | 10/24/1996 | 10/24/1996 | 10/24/1996 | P | PASS |
Carl Dependahl
|
|
|
10/24/96 340 - NEED RESUB. FOR PROPOSED CHANGES TO FLOOR/CLG ASSY...
|
INSP - Conference | 10/15/1996 | 10/15/1996 | 10/15/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - NEED FURTHER DETAIL FOR SUBSTITUTION OF JOIST MAT'L. DETAILS
|
INSP - Conference | 10/8/1996 | 10/8/1996 | 10/8/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - PRE ROCK & 1HR REQ'S
|
INSP - Conference | 10/3/1996 | 10/3/1996 | 10/3/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - PRE-CONST CONF RE PROTECTION OF PENETRATIONS; 1HR BLDG
|
INSP - Conference | 9/3/1996 | 9/3/1996 | 9/3/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - B,C,D SECTIONS OF ASSISTED LVG COMPLEX; 2 HR WALLS, FLOOR/CL RESUBMITTAL FOR "WARMING KITCHEN" ADDED TO PLAN
|
INSP - Footings | 8/6/1996 | 8/6/1996 | 8/6/1996 | P | PART |
Jim Storey
|
|
|
08/06/96 301 - 1:30 P.M. - IF POSSIBLE.... HAS SPEC. INSP. PENDING REPORT.
|