Permanent Occupancy | | 3/24/1997 | 3/24/1997 | | DONE |
|
|
|
|
INSP - Final | 3/21/1997 | 3/21/1997 | 3/21/1997 | P | PASS |
Carl Dependahl
|
|
|
03/21/97 340 - OK, CARD TO CATHY
|
INSP - Conference | 3/19/1997 | 3/20/1997 | 3/20/1997 | A | PASS |
Carl Dependahl
|
|
|
03/20/97 340 - W/TERRY RADER RE:ACHD SIGN OFF FOR FINAL...CONT TO CALL A
|
INSP - Conference | 3/19/1997 | 3/19/1997 | 3/19/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ TERRY RADER RE SIGN OFF FOR C/O...ACHD. HE'LL CHK W/ THEM
|
INSP - Conference | 3/19/1997 | 3/19/1997 | 3/19/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ TERRY RADER RE SIGN OFF FOR C/O...ACHD. HE'LL CHK W/ THEM
|
INSP - Conference | 3/18/1997 | 3/18/1997 | 3/18/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - CHK'D W/ ACHD RE FINAL, NEED SIG.
|
INSP - Conference | 3/13/1997 | 3/13/1997 | 3/13/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - INFORMED OWNER THAT ACHD HASNT SIGNED, CALLED ACHD TWICE, NO
|
INSP - Conference | 3/11/1997 | 3/11/1997 | 3/11/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ OWNER, TOLD TO CALL FOR FINAL WALK THRU, SUPT NOT ON JOB
|
INSP - Conference | 3/5/1997 | 3/5/1997 | 3/5/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ TERRY, SUPT. NEED VERIFY FIRE SIGN-OFF
|
INSP - Conference | 3/5/1997 | 3/5/1997 | 3/5/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ TERRY, SUPT. NEED VERIFY FIRE SIGN-OFF
|
INSP - Final | 2/28/1997 | 3/3/1997 | 3/3/1997 | P | NR |
Carl Dependahl
|
|
|
03/03/97 340 - FINAL FOR C/O nr
|
INSP - Final | 2/28/1997 | 3/3/1997 | 3/3/1997 | A | PASS |
Joe Tawney
|
|
|
03/03/97 406 - SIGNED OFF FOR PERM OCC 2/18/97 AFTER REC LETTER FROM ENG OF SLEEP ROOM DETECTORS
|
INSP - Carpentry | 2/11/1997 | 2/12/1997 | 2/12/1997 | A | PASS |
Carl Dependahl
|
|
|
02/12/97 340 - WINESSED SMOKE DAMPER OPERATION AT CORRIDORS, OK. STILL N FINAL C/O
|
INSP - Conference | 2/7/1997 | 2/7/1997 | 2/7/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ SUPT RE FINAL OK; NEED FIRE
|
INSP - Final | 1/29/1997 | 1/30/1997 | 1/30/1997 | P | FAIL |
Carl Dependahl
|
|
|
01/30/97 340 - REINSPECT FINAL; NR KEEP C/N, NEED FIRE SAFETY SIGN-OFF( CALL/ SMOKE DETS PER SUP'T. NEED SMOKE DAMPER DEMO
|
INSP - Final | 1/29/1997 | 1/29/1997 | 1/29/1997 | | FAIL |
|
|
|
REINSPECTION FOR OCC FAIL SLEEPING RM DETECTORS NOT CONNECTED TO NURSES STSTION
|
INSP - Conference | 1/27/1997 | 1/27/1997 | 1/27/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/SUPT. RE INSTALL OF SMOKE FIRE DAMPERS, TOLD TO CONTACT JO KEEP C/N
|
INSP-Conference | 1/6/1997 | | 1/6/1997 | | PASS |
|
|
|
FOLLOWED UP ON C/N FOR TEMP OCC CONTR STILL WAITING ON HDWRE FOR DOORS
|
INSP - Conference | 12/27/1996 | 12/27/1996 | 12/27/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - REC'D COMPLAINT RE DRAINAGE ONTO CORY LN. REFERRED TO PUB WK
|
INSP - Conference | 12/26/1996 | 12/26/1996 | 12/26/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE C/N ISSUED W/ TEMP OCC.
|
INSP - Conference | 12/23/1996 | 12/23/1996 | 12/23/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - C/N ISSUED 12-20-96; NEED ALL CORRECTIONS MADE FOR PERM C/O.
|
INSP - Final | 12/20/1996 | 12/20/1996 | 12/20/1996 | P | FAIL |
Carl Dependahl
|
|
|
FINAL REINSPECT...C/N OK FOR T/O,SUBJECT TO SMOKE DAMPER INSTALL BY 1-15-96
|
INSP - Conference | 12/19/1996 | 12/19/1996 | 12/19/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - RE DOOR HDWE AT A-3
|
INSP - Final | 12/18/1996 | 12/19/1996 | 12/19/1996 | P | FAIL |
Carl Dependahl
|
|
|
12/19/96 340 - fail, keep c/n. Need proper firestopping at penetrations, install of smoke/firedampers by 1-15-97.
|
INSP - Carpentry | 12/18/1996 | 12/18/1996 | 12/18/1996 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - CHK FOR PENETRATION FIRESTOPPING, KEEP C/N
|
INSP - Conference | 12/18/1996 | 12/18/1996 | 12/18/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ SUPT, MECH CONT, G.S.& BOB G. RE TEMP OCC: WILL REQUIRE C MADE, TIME AGREEMENT FOR SMOKE DAMPERS
|
INSP - Final | 12/16/1996 | 12/17/1996 | 12/17/1996 | P | FAIL |
Carl Dependahl
|
|
|
12/17/96 340 - C/N NEED SMOKE/FIRE DAMPERS,FLUSH BOLTS,1HR MEMBRANE PROT
|
INSP - Final | 12/16/1996 | 12/16/1996 | 12/16/1996 | | PART |
Joe Tawney
|
|
|
/ / 406 - OK FOR TEMP OCC DOOR FLUSH BOLTS & HDWRE CONNECT ROOM DETECTORS TO NURSES STATION SIGNAGE & MARKIN
|
INSP - Occupancy Sign-off | 12/16/1996 | 12/16/1996 | 12/16/1996 | | PASS |
|
|
|
Inspected by Art Yingling. Complies with CU-94-95/signed for Final Occupancy.
|
INSP - Final | 12/13/1996 | 12/13/1996 | 12/13/1996 | P | NR |
Joe Tawney
|
|
|
12/13/96 406 - JOE: SOMEONE ELSE TOOK THIS SO I CAN'T GIVE YOU ANY OF TH THIS IS ENOUGH.... NOT READY WILL SET UP APPT FOR NEXT WEEK
|
INSP - Conference | 12/10/1996 | 12/11/1996 | 12/11/1996 | P | PASS |
Carl Dependahl
|
|
|
12/11/96 340 - RE C/N FOR SMOKE-FIRE DAMPERS AT CORR...WILL INSTALL PER
|
INSP - Conference | 12/11/1996 | 12/11/1996 | 12/11/1996 | P | CANC |
Carl Dependahl
|
|
|
12/11/96 340 -
|
INSP - Miscellaneous | 12/9/1996 | 12/9/1996 | 12/9/1996 | | PASS |
Joe Tawney
|
|
|
/ / 406 - OK ON HYDRO TEST FOR SPKLR SYSTEM ADDITIONAL
|
INSP - Final | 12/6/1996 | 12/6/1996 | 12/9/1996 | P | NR |
Joe Tawney
|
|
|
12/06/96 406 - call office and set time ###-####/shelly RESCHEDULED FOR 12/9/96 8;OO AM
|
INSP - Framing/Rough-in | 11/25/1996 | 11/25/1996 | 11/25/1996 | P | PART |
Carl Dependahl
|
|
|
11/25/96 340 - PART, SMOKE BARRIER AT EXISTING OK, NEED RESUB ON SMOKE-F TO GARRISON) & UPGRADE AT EXISTING CLG PENETRATIONS
|
INSP - Framing/Rough-in | 11/21/1996 | 11/21/1996 | 11/21/1996 | P | FAIL |
Carl Dependahl
|
|
|
11/21/96 340 - PART, SMOKE BARRIER AT NEW-EXISTING INTERSECTION,VERBAL C FOR 1HR REQ'S. NEED PLAN NOTES RE ANY REQ'D UPGRADE OF EXISTING AREA
|
INSP - Framing/Rough-in | 11/15/1996 | 11/18/1996 | 11/18/1996 | P | PART |
Carl Dependahl
|
|
|
11/18/96 340 - FRAME REINSPECT...PART, REC'D TRUSS FIX FROM BRIGGS ENG. PLAN CHK RE SMOKE-FIRE DAMPERS AT CORR, REC'D LETTER FROM HVAC ENG. NEED COMPLETE SMOKE BARRIER AT EXISTING AREA
|
INSP - Framing/Rough-in | 11/14/1996 | 11/14/1996 | 11/14/1996 | P | PART |
Carl Dependahl
|
|
|
11/14/96 340 - PART, STILL NEED HVAC & ENG'S LETTER...KEEP C/N(S)
|
INSP - Framing/Rough-in | 11/12/1996 | 11/12/1996 | 11/12/1996 | P | NR |
Carl Dependahl
|
|
|
11/12/96 340 - NR, NEED FURTHER DOCUMENTS FROM ENG.
|
INSP - Conference | 10/29/1996 | 10/29/1996 | 10/29/1996 | A | PASS |
Carl Dependahl
|
|
|
REC'D REST OF TRUSS CALCS; TOLD TO CALL FOR REINSP.
|
INSP - Framing/Rough-in | 10/29/1996 | 10/29/1996 | 10/29/1996 | P | FAIL |
Carl Dependahl
|
|
|
10/29/96 340 - C/N, NEED ENG'S LETTERS: HVAC,STRUCT & TRUSSES
|
INSP - Carpentry | 10/25/1996 | 10/25/1996 | 10/25/1996 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - C/N, CONSULTED W/ ARCH JERRY TEAL & JOHN MENARD....NEED CL 2 CORRIDOR; FIRE DAMPERS AT ALL CLG PENETRATIONS FOR HVAC
|
INSP - Carpentry | 10/25/1996 | 10/25/1996 | 10/25/1996 | A | FAIL |
Carl Dependahl
|
|
|
C/N RE SMOKE-FIRE DAMPERS AT CORRIDORS; CONSULT W/ JERRY TEAL & JOHN MENARD
|
INSP - Carpentry | 10/24/1996 | 10/24/1996 | 10/24/1996 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - STILL NEED ENG'S LETTER & TRUSS ENG'G; KEEP CN
|
INSP - Framing/Rough-in | 10/23/1996 | 10/23/1996 | 10/23/1996 | P | FAIL |
Carl Dependahl
|
|
|
10/23/96 340 - frame reinspect...2ND C/N, NEED ENG'S OK FOR SUBSTITUTION
|
INSP - Framing/Rough-in | 10/22/1996 | 10/22/1996 | 10/22/1996 | P | FAIL |
Carl Dependahl
|
|
|
10/22/96 340 - V1HR...C/N,NEED ENG'S OK, ALL FIRE DAMPERS(FURNACE? COMB. SPECS, ETC. SEE C/N. OK TO ROCK 1ST LAYER RMS OFF SO. CORRIDOR AT LID
|
INSP - Framing/Rough-in | 10/18/1996 | 10/21/1996 | 10/21/1996 | P | PASS |
Jim Sly
|
|
|
10/21/96 316 - OK to insulate exterior walls only.
|
INSP-Sprinkler Rough-in/Hydro | 10/16/1996 | 10/18/1996 | 10/18/1996 | A | PASS |
Joe Tawney
|
|
|
10/18/96 406 - TRENT BICE-###-#### OR OFF.###-####. OK FOR SPKLR ROUGH IN
|
INSP - Conference | 10/11/1996 | 10/11/1996 | 10/11/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - REQUESTED RESUBMITTAL DRAWING(S) FROM J. TEAL, IN CONSULTATI EXISTING PORTION OF BLDG IS ACTUALLY DONE W/ INSUL AT ROOF SHEATHING...T PROTECT SPRINKLER PIPES IN ATTIC. HAS MECH COMPUTATIONS
|
INSP-Sprinkler Rough-in/Hydro | 10/8/1996 | 10/8/1996 | 10/8/1996 | P | FAIL |
Joe Tawney
|
|
|
10/08/96 406 - CALL TRENT BICE - ###-#### APPR PLANS NOT ON SITE
|
INSP - Carpentry | 10/3/1996 | 10/3/1996 | 10/3/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/GS RE ATTIC VENT REQ'D; NEED FURTHER DETAIL FROM ARCH.
|
INSP - Conference | 10/2/1996 | 10/2/1996 | 10/2/1996 | | PASS |
Carl Dependahl
|
|
|
TERRY RADER OF JAYO CONST WANTS TO INSUL AT SHEATHING, TOLD TO SUBMIT DETAIL; SPOKE W/ GS & CHK'D JOBSITE...EXISTING DONE AT CEILING. TOLD TERRY HE NEEDS ATTIC VENT. WILL RESEARCH
|
INSP - Framing/Rough-in | 9/6/1996 | 9/6/1996 | 9/6/1996 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - FAIL; NEED TO INSTALL SHEAR PANELS PER PLAN
|
INSP - Framing/Rough-in | 9/6/1996 | 9/6/1996 | 9/6/1996 | P | |
Carl Dependahl
|
|
|
|
INSP - Carpentry | 8/26/1996 | 8/26/1996 | 8/26/1996 | P | PART |
Carl Dependahl
|
|
|
08/26/96 340 - SHEAR WALL ...PART,WALLS NOT COMPLETE, TOLD TO RE CALL IN
|
INSP - Foundation | 8/22/1996 | 8/22/1996 | 8/22/1996 | | CANC |
Carl Dependahl
|
|
|
08/08/96 340 - BY 301 OR 316
|
INSP - Foundation | 8/12/1996 | 8/12/1996 | 8/12/1996 | P | PASS |
Jim Storey
|
|
|
08/12/96 301 - FRMS-OK FORMS-REBAR
|
INSP - Foundation | 8/12/1996 | 8/12/1996 | 8/12/1996 | | PASS |
Jim Storey
|
|
|
/ / 301 - FRMS-OK FORMS-REBAR
|
INSP - Footings | 8/8/1996 | 8/9/1996 | 8/9/1996 | A | PASS |
Jim Storey
|
|
|
08/08/96 301 - FRIDAY - 10 A.M. FRMS-OK FORMS-REBAR
|
INSP - Foundation | 8/7/1996 | 8/8/1996 | 8/8/1996 | A | PASS |
Jim Storey
|
|
|
08/08/96 301 - FRMS-OK FORMS-REBAR
|
INSP - Footings | 8/6/1996 | 8/6/1996 | 8/6/1996 | | PASS |
Jim Storey
|
|
|
/ / 301 - FTG -OK FOOTING FRMS-OK FORMS-REBAR
|
INSP - Footings | 8/5/1996 | 8/5/1996 | 8/5/1996 | P | NR |
Jim Storey
|
|
|
08/05/96 301 -
|