Permit Information
Permit NumberBLD96-01865
StatusFinaled
Name IDAHO INDEPENDENT BANK
Site Address 317 N 9TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
To remodel an existing 8,660 sq.ft. office building for new bank tenant per approved plans on file and DDR-68-96. Work to include erecting approximatly 104lf on new interior partition wall with 5 doors and 7 interior windows, infill approximatly 28lf of exterior wall, installing two new storefront entry doors with sidelights and installing new EIFS on entire exterior. The 2600_sq.ft. basement to remain unchanged except for ceiling to be upgraded to 1-hr and rated door enclosures added to access's and to be used for storage only. (P.C.#363-96) PRP (Note: Demolition of interior and exterior finished, interior partitions, 9 doors,and 15 windows permitted under DEMO Permit # BLD96-2077)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 7/1/19977/1/1997 DONE
Details
INSP - Final3/14/19973/17/19973/16/1997APASS
Details
03/17/97 333 - FNL -OK FINAL OTH-OTHER AGENCIES NOT APPROVED
INSP - Final3/14/19973/14/19973/14/1997APASS
Details
exit signs provided with batteries, occ card signed
INSP - Final3/6/19973/7/19973/7/1997APART
Details
AFTER 9:30 all items on c/n complete except basement exit signs need battery back-up
INSP - Final2/26/19972/26/19972/26/1997PPART
Details
reinspected, still items missing from first c/n, reviewed with bank manager, adjusted first c/n and left copy with bank manager
INSP - Final2/11/19972/11/19972/11/1997AFAIL
Details
PLANS LIMIT BASEMENT TO STORAGE, USED FOR BREAK ROOM, FE'S OUT OF DATE, BASEMENT SPRINKLER SYSTEM OUT OF DATE (93), BASEMENT DOOR CLOSERS NOT FUNCTIONAL occupied w/o CO
INSP-Conference12/4/199612/4/199612/4/1996PPASS
Details
sent letter to TVFP that joist obstructions would be allowed, listed other problems not resolved including: no flushing of ug and duct/door obstructions. Also pointed out problem of sharing control valves with bldg 2.
INSP - Conference12/2/199612/2/199612/2/1996 PASS
Details
/ / 405 - dropped off copy of c/n for sprinklers. discussed possible problems with common control valves to system with building 1160 ngowen
INSP - Framing/Rough-in11/6/199611/6/199611/6/1996 PASS
DetailsJim Storey
/ / 301 - FRAM-OK FRAMING ON CIELLING OF DOCK BAYS NORTH SIDE OF BLDG.
INSP - Final10/28/199610/29/199610/29/1996PFAIL
Details
10/29/96 333 - OTH-OTHER AGENCIES NOT APPROVED not ready
INSP - Ceiling grid10/1/199610/1/199610/1/1996PPASS
DetailsWes Worcester
main floor ok
INSP - Framing/Rough-in10/1/199610/1/199610/1/1996PNR
DetailsWes Worcester
INSP - Framing/Rough-in9/13/19969/16/19969/16/1996PPART
Details
Items # 1&3 will require reinspection at final.
INSP - Framing/Rough-in9/11/19969/12/19969/12/1996APART
DetailsJim Storey
09/12/96 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED particial.
INSP - Framing/Rough-in8/22/19968/23/19968/23/1996PPASS
Details
08/23/96 333 - soffitts ok