To remodel an existing 48,782 sq.ft. warehouse/office/fabrication building to bring the building into code compliance as per approved plans on file. Work to include replacment of exterior stairway on west side, construction of a new stairway and landing with access door on the west side (to comply with Fire Dept. requirements), installation of smoke and heat vents and draft curtains in warehouse area, upgrade of 1-hr. tenant demising walls, upgrade to the shell of the structure per attached engineering, installation of exit signage and illumination and miscellaneous. NOTE: This building is to be fully fire sprinklered. High piled combustible storage in the warehouse area to a maximum height of 15 ft. THE ENGINEER TO PROVIDE A FINAL REPORT TO THE STRUCTURAL INSPECTOR CERTIFYING SATISFACTORY COMPLETION OF THE REQUIRED UPGRADES PRIOR TO FINAL OF THE BUILDING PERMIT. NO OCCUPANCY OF THE OFFICE AREA ON THE NORTH SIDE OF THE 1ST FLOOR IS ALLOWED WITHOUT FURTHER PERMITS AND APPROVALS. (P.C.#522-96/mys)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 6/11/19976/11/1997 DONE
Details
INSP - Final6/3/19976/3/19976/3/1997PPASS
DetailsJim Storey
06/03/97 301 - LATE P.M. FNL -OK FINAL UNABLE TO ACESS THE MICRON SIDE OF THE BLDG. BUT VERIFIED C/N ON THE SMOKEGUARD SIDE. CARD OK FOR SIGN OFF.
INSP-Final Inspection6/3/19976/3/19976/3/1997PPASS
Details
EARLY P.M.
INSP-Final Inspection5/28/19975/28/19975/28/1997APASS
Details
storage lowered to under 15 ft by Micron
INSP - Final5/6/19975/6/19975/6/1997PFAIL
DetailsJim Storey
05/06/97 301 - THEY WOULD LIKE YOU TO BE THERE AT THE SAME TIME AS THE F CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP-Final Inspection5/5/19975/6/19975/6/1997PPART
Details
3pm alarms, cooler smoke vent, storage height temp occ. OK, need to lower storage height for perm
INSP - Final4/25/19974/25/19974/25/1997PNR
DetailsJim Storey
04/25/97 301 - late p.m OTH-OTHER AGENCIES NOT APPROVED
INSP-Final Inspection4/25/19974/25/19974/25/1997PFAIL
Details
fire alarm controller battery found disconnected bu no trouble was transmitted off site, this is the same condition as found the last time I was called for alarm testing. Smoke vent not installed above cooler, storage exceeds permit limit of 15 ft.
INSP - Final4/21/19974/22/19974/25/1997PNR
DetailsJim Storey
04/22/97 301 - OTH-OTHER AGENCIES NOT APPROVED
INSP - Wall cover1/2/19971/2/19971/2/1997 PASS
DetailsJim Storey
/ / 301 - GWB -OK SHEETROCK NAILING tenent demizing wall north side.
INSP - Final12/30/199612/30/199612/30/1996PFAIL
Details
inspected sprinkler system and alarms, no monitoring, no piv, no coverage in old cooler, no door to old cooler, compressor room has no occ sep from balance of building. sprinkler plans claimed non comb construction, actual is type V. high piled storage being practiced without completion of art 81 required items.
INSP-Sprinkler Rough-in/Hydro12/9/199612/9/199612/9/1996APART
Details
examined in rack sprinklers for obstructions - advised on relocations to avoid being struck by towmotors, advised that pallet loads are resting on pipes