Permit NumberBLD96-02886
StatusFinaled
Name RICE FAMILY DENTISTRY
Site Address 12426 W EXPLORER DR
Project NameBRIGHTON BLDG
Customer Number 
ePlanReviewNo
Description
To finish a 1618 sq. ft. space on the second floor of the Brighton Building for use as a dental office. Construction of interior nonbearing walls, wallcover, suspended ceiling system and one-hour occupancy separation around the medical gas room with a 1-hour shaft around the duct work providing make up air from the exterior per UFC and ventilation exhaust directly to the exterior (ducts can be within the one hour room walls if they extend to the deck & wall is firestopped at flutes) for the medical gas room, all per approved plans notes & attachments. Separate electrical, plumbing & mechanical permits are required. PC#631-96/drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 1/23/19971/23/1997 DONE
Details
INSP - Final1/22/19971/22/19971/22/1997 PASS
DetailsJim Sly
/ / 316 - C/N Removed..Perm. Occ.
INSP - Final1/16/19971/16/19971/16/1997PNR
DetailsCarl Dependahl
01/16/97 340 - 316 AREA, SENT TO JIM
INSP - Final1/16/19971/16/19971/16/1997 NR
DetailsJim Sly
/ / 316 - NR
INSP - Final1/15/19971/15/19971/15/1997PFAIL
DetailsCarl Dependahl
01/15/97 340 - RUSSELL MAYER - ###-#### (LATE PM.) 316 AREA, C/N, OK FOR T/O, NEED PLBG FINAL
INSP - Final1/15/19971/15/19971/15/1997PPASS
DetailsJoe Tawney
RUSSELL MAYER - ###-#### OK FOR PERM OCC
INSP - Final1/13/19971/13/19971/13/1997 FAIL
DetailsJim Sly
01/13/97 316 - C/N ...Needs fire dept sign off....
INSP - Carpentry12/16/199612/16/199612/16/1996 PASS
DetailsJim Sly
/ / 316 - Inspection of 1hr shaft....OK
INSP - Framing/Rough-in12/10/199612/10/199612/10/1996PPASS
DetailsJim Sly
12/10/96 316 - Frame OK.
INSP - Final1/14/19971/14/19971/14/1996PFAIL
DetailsJoe Tawney
HE WILL CALL TO SCHEDULE WITH YOU FINAL FAILED EXT VENT DUCTS IN MED GAS RM NOT 6" AS SHOWN ON PLAN TEST PAPERS ON GAS SYST PROTECT GAS CONNECTIONS AT FLOOR LEVEL