INSP - Final | 10/16/1997 | 10/17/1997 | 10/17/1997 | A | PASS |
|
|
|
signed the perm col for the occ req card
|
Permanent Occupancy | | 10/17/1997 | 10/17/1997 | | DONE |
|
|
|
|
INSP-Final Inspection | 10/15/1997 | 10/16/1997 | 10/16/1997 | A | PASS |
Joe Tawney
|
|
|
10/16/97 406 - REINSP FOR FINAL OK FOR PERM OCC
|
INSP - Final | 10/13/1997 | 10/13/1997 | 10/13/1997 | | FAIL |
Joe Tawney
|
|
|
/ / 406 - REINSP FOR FINAL FAIL ALARM SYSTEM
|
INSP-Final Inspection | 10/7/1997 | 10/8/1997 | 10/9/1997 | P | FAIL |
Joe Tawney
|
|
|
10/08/97 406 - READY 3:00 REINSP FOR FINAL FAIL STROBES AND DACT
|
INSP - Final | 9/16/1997 | 9/17/1997 | 9/17/1997 | P | PART |
|
|
|
09/17/97 338 - fire made ok life safety still not sure, will wait for th occ req signoff
|
INSP-Final Inspection | 9/16/1997 | 9/17/1997 | 9/17/1997 | A | PART |
Joe Tawney
|
|
|
09/17/97 406 - REINSP FOR FINAL OK FOR TEMP OCC FOR ENTIRE BLDG ALARM S
|
INSP - Final | 9/12/1997 | 9/12/1997 | 9/15/1997 | P | NR |
|
|
|
09/15/97 338 - not ready will call for wed
|
INSP-Final Inspection | 9/12/1997 | 9/12/1997 | 9/12/1997 | P | PART |
Joe Tawney
|
|
|
09/12/97 406 - REINSP FOR FINAL OK FOR TEMP OCC ALARM SUBMITTAL 2ND FLR EGRESS CONTROL DOORS
|
INSP - Temporary occupancy | 9/9/1997 | 9/11/1997 | 9/11/1997 | A | NR |
|
|
|
09/11/97 338 - OTH-OTHER AGENCIES NOT APPROVED
|
INSP-Final Inspection | 9/9/1997 | 9/11/1997 | 9/11/1997 | A | FAIL |
Joe Tawney
|
|
|
09/11/97 406 - 9 A.M. FINAL FAIL EXIT DOORS TAPE ON HEADS ALARM SUBMITTAL TEST EMERG LIGHTS
|
INSP-Sprinkler Rough-in/Hydro | 9/9/1997 | 9/9/1997 | 9/9/1997 | | PART |
|
|
|
OK ON HYDRO TEST
|
INSP - Ceiling grid | 9/4/1997 | 9/4/1997 | 9/4/1997 | | PASS |
|
|
|
/ / 338 - CEILING GRIDS OK SOME LIGHTS POSSIBLY NOT IN
|
INSP - Wall cover | 9/4/1997 | 9/4/1997 | 9/4/1997 | P | CANC |
|
|
|
09/04/97 338 - CEILING GRID MADE OK
|
INSP-Supply line flush | 9/2/1997 | 9/3/1997 | 9/3/1997 | A | PART |
Joe Tawney
|
|
|
09/03/97 406 - AT 10:30 A.M. OK ON UNDERGROUND FLUSH AND ROUGH IN OF SPKLR SYSTEM
|
INSP - Wall cover | 8/14/1997 | 8/15/1997 | 8/15/1997 | A | PART |
|
|
|
08/15/97 338 - 1 HOUR RATED WALLS c/n issued will re check at the final
|
INSP - Conference | 7/31/1997 | 7/31/1997 | 7/31/1997 | P | PART |
|
|
|
07/31/97 338 - ramp ok no access to trailer to get resubmittal
|
INSP - Conference | 7/29/1997 | 7/29/1997 | 7/29/1997 | | PASS |
|
|
|
/ / 338 - on the approved resubmittals and the details for the ul desi
|
INSP - Conference | 7/29/1997 | 7/29/1997 | 7/29/1997 | | PASS |
|
|
|
/ / 338 - on the approved resubmittals and the details for the ul desi
|
INSP - Framing/Rough-in | 7/28/1997 | 7/28/1997 | 7/29/1997 | P | PART |
|
|
|
07/29/97 338 - made ok on the front entry canopies
|
INSP - Framing/Rough-in | 7/23/1997 | 7/23/1997 | 7/22/1997 | P | NR |
|
|
|
07/23/97 338 - HE LEAVES AT 3:30 OTH-OTHER AGENCIES NOT APPROVED
|
INSP - Conference | 7/22/1997 | 7/22/1997 | 7/22/1997 | P | PASS |
Carl Dependahl
|
|
|
W/ TOM A....COVERING FOR 338; CHK OTHER INSPS, ETC
|
INSP - Framing/Rough-in | 7/22/1997 | 7/22/1997 | 7/22/1997 | P | NR |
Tom Arcoraci
|
|
|
07/22/97 408 - no one on site left note to recall for next day
|
INSP - Masonry | 7/3/1997 | 7/7/1997 | 7/7/1997 | A | PASS |
|
|
|
07/07/97 338 - made ok with sp insp approval
|
INSP - Masonry | 7/2/1997 | 7/3/1997 | 7/3/1997 | A | PASS |
|
|
|
07/03/97 338 - made ok with sp insp approval
|
INSP - Set-back | 7/3/1997 | 7/3/1997 | 7/3/1997 | | PASS |
|
|
|
/ / 338 - made okwith sp insp approval
|
INSP - Masonry | 7/1/1997 | 7/2/1997 | 7/2/1997 | A | PASS |
|
|
|
07/02/97 338 - r-bar placed made okwith sp insp approval
|
INSP - Miscellaneous | 7/1/1997 | 7/2/1997 | 7/2/1997 | A | PASS |
|
|
|
07/02/97 338 - made ok with other agencies approvaland sp insp ok
|
INSP - Masonry | 6/27/1997 | 6/30/1997 | 6/30/1997 | A | PASS |
|
|
|
06/30/97 338 - madeok with sp insp approval
|
INSP - Masonry | 6/25/1997 | 6/27/1997 | 6/27/1997 | A | PASS |
|
|
|
06/27/97 338 - made ok with sp insp approval
|
INSP - Masonry | 6/25/1997 | 6/26/1997 | 6/26/1997 | A | PASS |
|
|
|
/ / 338 - made ok with sp insp approval esubs will be attached to file and drawings
|
INSP - Masonry | 6/20/1997 | 6/23/1997 | 6/23/1997 | A | PASS |
|
|
|
06/23/97 338 - made ok with sp insp approval
|
INSP - Masonry | 6/18/1997 | 6/19/1997 | 6/19/1997 | A | PASS |
|
|
|
06/19/97 338 - r-bar placed in the south 1/2 to the 4' level and frond p to pour with sp insp approval
|
INSP - Masonry | 6/17/1997 | 6/17/1997 | 6/17/1997 | P | PASS |
|
|
|
06/17/97 338 - MADE OK WITH SP INSP APPROVAL
|
INSP - Conference | 6/11/1997 | 6/12/1997 | 6/12/1997 | A | PASS |
|
|
|
06/12/97 338 - 9:30 A.M. resubmittal changesmust review with the plan r
|
INSP - Masonry | 6/11/1997 | 6/12/1997 | 6/12/1997 | A | PASS |
|
|
|
06/12/97 338 - made ok r-bar placed ok with sp insp blessing top lift
|
INSP - Masonry | 6/9/1997 | 6/11/1997 | 6/10/1997 | P | PASS |
|
|
|
06/11/97 338 - made ook with sp insp approval
|
INSP - Masonry | 6/6/1997 | 6/10/1997 | 6/10/1997 | A | PASS |
|
|
|
06/10/97 338 - r-bar placed ok after sp insp blessing
|
INSP - Masonry | 6/3/1997 | 6/4/1997 | 6/4/1997 | P | PASS |
|
|
|
06/04/97 338 - MASONARY REBAR OK WITH SP INSP APPR.
|
INSP - Masonry | 6/2/1997 | 6/3/1997 | 6/3/1997 | A | PASS |
|
|
|
06/03/97 338 - made ok with the sp insp blessing
|
INSP - Masonry | 5/27/1997 | 5/28/1997 | 5/27/1997 | A | PASS |
|
|
|
05/28/97 338 - r-bar placed k after sp insp signoff
|
INSP-Conference | 5/27/1997 | 5/27/1997 | 5/27/1997 | P | PASS |
|
|
|
alarm plans drop off/ discuss w/ general
|
INSP - Masonry | 5/22/1997 | 5/23/1997 | 5/22/1997 | A | PASS |
|
|
|
05/23/97 338 - r-bar placed made ok
|
INSP - Masonry | 5/20/1997 | 5/21/1997 | 5/21/1997 | A | PASS |
|
|
|
05/21/97 338 - in progress pour almost complete ok with sp insp blessing
|
INSP - Miscellaneous | 5/15/1997 | 5/16/1997 | 5/16/1997 | A | PASS |
|
|
|
05/16/97 338 - FLOOR SLAB INSPECTION made ok
|
INSP - Foundation | 5/13/1997 | 5/14/1997 | 5/13/1997 | P | CANC |
|
|
|
05/14/97 338 -
|
INSP - Flatwork | 5/13/1997 | 5/13/1997 | 5/13/1997 | | PASS |
|
|
|
/ / 338 - FRMS-OK FORMS-REBAR
|
INSP - Footings | 5/5/1997 | 5/5/1997 | 5/5/1997 | P | PART |
Carl Dependahl
|
|
|
05/05/97 340 - part, spec insp logged ok, pending report
|
INSP - Footings | 5/2/1997 | 5/2/1997 | 5/2/1997 | P | PART |
Carl Dependahl
|
|
|
05/02/97 340 - PART, HAS SPEC INSP
|
INSP - Foundation | 5/2/1997 | 5/2/1997 | 5/2/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - PART, INT FTGS, DRAINAGE AT FND PERIMETER; PENDING SPEC INSP
|
INSP - Foundation | 5/1/1997 | 5/1/1997 | 5/1/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - FDN, PENDING SPEC INSP REPORT
|
INSP - Foundation | 5/1/1997 | 5/1/1997 | 5/1/1997 | | PART |
Carl Dependahl
|
|
|
/ / 340 - FDN, PENDING SPEC INSP REPORT
|
INSP - Framing/Rough-in | 4/29/1997 | 5/1/1997 | 5/1/1997 | P | NR |
Carl Dependahl
|
|
|
05/01/97 340 - NR, FTG, FDN INSP CALLED
|
INSP - Foundation | 4/29/1997 | 4/30/1997 | 4/30/1997 | P | PART |
Carl Dependahl
|
|
|
04/30/97 340 - AM, INT FTG; APPEARS OK AT CENTER CONT FTG,COL FTGS NR
|
INSP - Conference | 4/28/1997 | 4/28/1997 | 4/28/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - MET W/ VANAUKER SUPT & SPEC INSP
|
INSP - Footings | 4/28/1997 | 4/28/1997 | 4/28/1997 | P | PART |
Carl Dependahl
|
|
|
04/28/97 340 - HAS STRATA SPEC INSP. EXT FTG BAR & FORMS
|
INSP - Footings | 4/22/1997 | 4/23/1997 | 4/23/1997 | P | PASS |
|
|
|
04/23/97 338 - FTG -OK FOOTING
|