Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberBLD97-00348
StatusFinaled
Name 8TH STREET MARKETPLACE
Site Address 405 S 8TH ST
Project Name8TH ST MARKETPLACE
Customer Number 
ePlanReviewNo
Description
(PHASE II) To bring into code compliance the stairtower/elevator and exit passageway leading to the 8th street exit as Phase II of the upgrade in accordance with approved plans on file. Work to include demolition of existing elevator and stairway to 3rd floor and construction of new stairway in the previous elevator tower, installation of new elevator in the previous stair tower, installation of handicap lift to create a accessible route between 8th street level and restaurant/retail level, and upgrade of 1-hr. exit passageway between stair tower and 8th street exit/entry. NOTE: Fire sprinklers substitute for 1-hr. construction. (P.C.#97-0348) MYS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final3/27/19983/27/19983/27/1998PPASS
Details
03/27/98 333 - will sign card in office
INSP - Final3/18/19983/19/19983/19/1998AFAIL
Details
03/19/98 333 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP-Final Inspection2/25/19982/25/19982/25/1998PPASS
DetailsRick Jackson
full occ approved. all items on correction notice completed.
INSP-Alarm Testing2/18/19982/18/19982/18/1998AFAIL
DetailsRick Jackson
tested elev. recall, sprink. tampers, pulls and detectors. strobes below min height, door jamb smokes not in FACP, fire ext mounted, sprink head problems in 1st floor lobby (within 6 ft/upright in pendant position)
INSP - Conference10/31/199711/3/199711/3/1997APART
DetailsRick Jackson
conference with contractor concerning fire alarm plan resubmittal requirement.
INSP - Framing/Rough-in10/20/199710/21/199710/21/1997APASS
Details
10/21/97 333 - REIN FRAM-OK FRAMING
INSP - Framing/Rough-in10/15/199710/16/199710/16/1997ANR
DetailsJim Storey
10/16/97 301 - OTH-OTHER AGENCIES NOT APPROVED ele CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ele boxes need protected back back at stait tower.
INSP - Framing/Rough-in9/22/19979/22/19979/22/1997PPASS
Details
09/22/97 333 - partial r/i shaft ok
INSP - Carpentry9/8/19979/8/19979/8/1997APASS
Details
09/08/97 333 - talked about dampers in entry
INSP - Conference9/4/19979/5/19979/8/1997APASS
Details
09/05/97 333 - ok