INSP - Final | 6/22/1998 | 6/23/1998 | 6/23/1998 | A | PASS |
Jim Sly
|
|
|
06/23/98 316 - OK for Perm Occ.
|
Permanent Occupancy | | 6/23/1998 | 6/23/1998 | | DONE |
|
|
|
|
INSP - Final | 4/30/1998 | 4/30/1998 | 4/30/1998 | P | PASS |
Tom Arcoraci
|
|
|
04/30/98 408 - ok for perm occ if others ok
|
INSP-Final Inspection | 4/30/1998 | 4/30/1998 | 4/30/1998 | P | PASS |
Joe Tawney
|
|
|
04/30/98 406 - Scheduled by Hello!. Contact phone is [3911105]. REINSP OK FOR PERM OCC
|
INSP-Final Inspection | 4/23/1998 | 4/24/1998 | 4/24/1998 | P | FAIL |
Joe Tawney
|
|
|
04/24/98 406 - ILE - Suite 150 - Odie, ###-#### REINSP FAIL SMOKE DET ON ONE AHU DID NOT OPERATE
|
INSP-Final Inspection | 3/10/1998 | 3/10/1998 | 3/10/1998 | P | FAIL |
Joe Tawney
|
|
|
03/10/98 406 - final inspection 2:00 p.m. ron ###-#### REINSP FAIL DUCT DETECTORS
|
INSP - Temporary occupancy | 12/23/1997 | 12/23/1997 | 12/23/1997 | P | FAIL |
Jim Sly
|
|
|
12/23/97 316 - C/N left for shell and core....to be finalled prior to ca
|
INSP-Final Inspection | 12/23/1997 | 12/23/1997 | 12/23/1997 | P | FAIL |
Joe Tawney
|
|
|
12/23/97 406 - ILE/ FOR AROUND 1:30 FAIL SPKLR SYST NOT TESTED EXIT DOOR DUCT DETECTORS
|
INSP-Sprinkler Rough-in/Hydro | 12/23/1997 | 12/23/1997 | 12/23/1997 | P | FAIL |
Joe Tawney
|
|
|
12/23/97 406 - SPKLR SYSTEM NOT TESTED UNDER SHELL PERMIT
|
INSP - Final | 11/25/1997 | 11/28/1997 | 11/28/1997 | A | NR |
Tom Arcoraci
|
|
|
11/28/97 408 - ILE/ CALL BEFORE YOU GO OUT RICO-###-####
|
INSP-Final Inspection | 11/25/1997 | 11/26/1997 | 11/26/1997 | P | NR |
Joe Tawney
|
|
|
11/26/97 406 - ILE READY AFTER 2:00 NOT READY NO PLANS ON SITE FOR SHELL OR TI
|
INSP - Framing/Rough-in | 10/16/1997 | 10/16/1997 | 10/16/1997 | P | PASS |
Jim Sly
|
|
|
10/16/97 316 - Framing OK
|