Permit Information
Permit NumberBLD97-02481
StatusFinaled
Name 9TH STREET WAREHOUSES
Site Address 855 W BROAD ST
Project Name9TH STREET WAREHOUSES
Customer Number 
ePlanReviewNo
Description
(9TH STREET WAREHOUSE RENOVATION & ADDITION) Fire sprinkler system used to substitute for 1-hr fire-resistive construction. To complete shell and core improvements to an existing historic building. A 2-hr area separation wall will divide the building to resolve allowable building area issues. With the additions, the North half will have a 14,211 sq. ft. basement, 16,408 sq. ft. 1st floor, and 13,763 sq. ft. 2nd floor. The South half will have a 14,100 sq. ft. basement, 8,308 sq. ft. first floor, and 14,983 sq. ft. 2nd floor. Work is to include an addition and a below street level plaza on the North. Three elevators, a mechanical penthouse, a 2-hr area separation wall, 1-hr corridors, and ten (10) restrooms accessible to the disabled are proposed. All work shall comply with the approved drawings, engineering, and plan check conditions on file. The owner shall employ the engineer responsible for the structural design, or another engineer designated by him, to perform structural observation as defined by 1994 UBC Section 220. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. This permit does not establish a Certificate of Occupancy. Each individual tenant must independently apply for their own Certificate of Occupancy. Demolition work is covered under BLD97-3148. DRH#86-96 PC-550-97 **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/16/199912/17/199912/17/1999AFAIL
Details
skip ###-#### Still need P/Z ACHD.
BLD-Final12/2/199912/3/199912/3/1999PFAIL
Details
###-#### LATE PM Cancelled by contractor.
FIRE-Final Inspection11/30/199911/30/199911/30/1999PPASS
DetailsRick Jackson
INSP - Final4/16/19994/21/19994/23/1999PPART
Details
04/26/99 338 - ok for str with fire ok
INSP-Final Inspection4/22/19994/22/19994/22/1999PPART
DetailsRick Jackson
temp occ approved for shell; door holder at south end; basement doors and corridor not used or complete; perm address's;
INSP-Final Inspection4/21/19994/21/19994/21/1999PFAIL
DetailsRick Jackson
tested more alarms - okay; damper not working; retest exit and emergency lights; knox box; etc. c/n issued
INSP-Final Inspection4/16/19994/20/19994/16/1999P
DetailsRick Jackson
3:00
INSP - Final4/13/19994/14/19994/14/1999PFAIL
Details
need fire dept approval str walk through only with 306 and 340 04/14/99 338
INSP-Final Inspection4/13/19994/14/19994/14/1999PFAIL
DetailsRick Jackson
04/14/99 409 - ###-#### SKIP//###-#### FIRE & LIFE SAFETY 1:00 dampers on 2nd not working; smoke detector in elevator shaft; NFPA 72; a
INSP-Final Inspection4/9/19994/12/19994/12/1999PPART
DetailsRick Jackson
###-#### TRACY hydro of anti-freeze loop okay.
INSP-Conference3/30/19993/30/19993/30/1999APART
DetailsRick Jackson
profit meeting - requirements for shell and core were discussed
INSP-Alarm Testing3/3/19993/3/19993/3/1999P
Details
exiting requirements ###-####, ###-#### Jack
INSP-Conference3/3/19993/3/19993/3/1999PPART
DetailsRick Jackson
exiting sign requirements and corridor heights
INSP - Framing/Rough-in3/1/19993/1/19993/1/1999PPART
Details
03/01/99 338 - madok to drop in tiles this section
INSP - Framing/Rough-in2/25/19992/26/19992/26/1999PCANC
DetailsRick Jackson
acoustic ceiling ###-#### Jack this inspection was for the structural inspector - not fire
INSP - Framing/Rough-in2/19/19992/22/19992/22/1999ACANC
DetailsJoe Tawney
02/22/99 406 - ###-#### overhead Tracy CANCELLED WILL BE RESCHEDULED
INSP - Framing/Rough-in2/1/19992/2/19992/22/1999APART
Details
02/02/99 338 - made ok to drop in tiles need to check for diffuser attac
INSP - Framing/Rough-in2/18/19992/19/19992/19/1999APART
DetailsJim Storey
02/19/99 301 - severce hall ceilling ok, corridor south pending mech, c/
INSP - Framing/Rough-in1/29/19991/29/19991/29/1999PPART
DetailsCarl Dependahl
01/29/99 340 - jack house- ###-#### -acostical ceil insp; ok to begin la recall for complete insp when ready
INSP - Framing/Rough-in1/15/19991/19/19991/19/1999APART
Details
01/19/99 338 - ok for to lay in the ceiling at the hall
INSP - Framing/Rough-in1/5/19991/6/19991/6/1999APASS
Details
01/06/99 333 - frame ok
INSP-Sprinkler Rough-in/Hydro1/5/19991/6/19991/6/1999AFAIL
DetailsRick Jackson
01/06/99 409 - JACK- ###-#### R/I FOR FIRE basement area heqads still obstructed by conduit in bldg 2
INSP - Framing/Rough-in12/31/199812/31/199812/31/1998 PART
Details
12/31/98 333 - all but exterior walls on addition
INSP-Sprinkler Rough-in/Hydro12/21/199812/22/199812/22/1998PFAIL
DetailsRick Jackson
Tracy wants an inspection at 1pm ###-#### basement not to cover corridor - hangers, wrong heads, conduit obstructing. second floor: steel brace causing overspacing,
INSP - Framing/Rough-in12/17/199812/18/199812/18/1998APART
Details
12/18/98 333 - NEED DETAIL AND ENGINEERING FOR CONNECTIONS AT NORTH WALL
INSP - Framing/Rough-in12/1/199812/2/199812/2/1998APART
Details
12/02/98 333 - restrooms and corridors ok
INSP - Framing/Rough-in10/13/199810/14/199810/14/1998PPART
Details
10/14/98 333 - south end
INSP - Concrete10/8/199810/8/199810/8/1998PPART
DetailsJim Storey
10/08/98 301 - jack ###-#### covered w/special insp. ì
INSP-Final Inspection10/7/199810/8/199810/8/1998PPART
DetailsRick Jackson
TRACY ###-#### 3PM sprinkler rough-in only - okay to cover building 4 2nd floor
INSP - Concrete10/2/199810/2/199810/2/1998PPART
Details
rebar ok
INSP - Concrete9/22/19989/23/19989/23/1998APART
Details
09/23/98 333 - north slab ok
INSP - Framing/Rough-in9/22/19989/22/19989/22/1998PPART
Details
09/22/98 333 - south roof and cn ok
INSP - Framing/Rough-in9/21/19989/21/19989/21/1998PPART
Details
south half basement ok
INSP - Framing/Rough-in9/17/19989/17/19989/18/1998PPART
DetailsJim Storey
09/17/98 301 - bldg#4 c/n basement restroom posted. ok for plumbing chas and all but west corner of basementc/n
INSP-Sprinkler Rough-in/Hydro9/11/19989/15/19989/15/1998PFAIL
DetailsRick Jackson
TRACY ###-#### 1 PM bldg 4 - corridors require heads above grid (exposed combustibles), duct chase requires heads, space under loading dock needs sprinklers or combustibles covered, heads in bathrooms/corridor problems
INSP - Framing/Rough-in9/8/19989/8/19989/8/1998 PART
Details
09/08/98 333 - looked at wall locations
INSP - Framing/Rough-in9/4/19989/8/19989/8/1998APART
Details
09/08/98 333 - talked about wall locations
INSP - Foundation9/3/19989/4/19989/4/1998PPASS
Details
09/04/98 333 - FRMS-OK FORMS-REBAR
INSP-Sprinkler Rough-in/Hydro8/31/19989/1/19989/1/1998APART
DetailsRick Jackson
9:00 AS PER 409 / TRACY ###-#### okay to cover bathrooms - sprinklers installed above hard lid
INSP-Sprinkler Rough-in/Hydro8/26/19988/28/19988/28/1998AFAIL
DetailsRick Jackson
SPRINKLER OVERHEARD INSPECTION TRACY ###-#### concealed space in corridor and bathrooms not sprinklered above lid. not approved for cover until sprinklered
INSP-Conference8/26/19988/26/19988/26/1998PPASS
Details
08/26/98 333 - firestopping issues
INSP - Concrete8/25/19988/25/19988/25/1998PPART
Details
08/25/98 333 - pour ok
INSP - Framing/Rough-in8/20/19988/21/19988/21/1998APART
Details
08/21/98 333 - CORRIDORS SECOND AND FIRST FLOOR NORTH PLUSS BATHS ANS SO
INSP - Concrete8/18/19988/19/19988/19/1998APART
Details
08/19/98 333 - retain wall ok
INSP - Concrete8/13/19988/17/19988/17/1998APART
Details
08/17/98 333 - retaining wall
INSP - Concrete8/13/19988/14/19988/14/1998APART
Details
08/14/98 333 - ok pend spec insp reports
INSP - Concrete8/7/19988/7/19988/7/1998 PASS
Details
08/07/98 333 - moment frame ok
INSP - Concrete8/4/19988/7/19988/7/1998APART
Details
08/07/98 333 - moment frame foot ok
INSP - Concrete8/4/19988/6/19988/6/1998APART
Details
08/06/98 333 - moment frame foot ok pend spec insp reports
INSP - Framing/Rough-in8/5/19988/6/19988/6/1998APART
Details
08/06/98 333 - talked about damper and corridor requirements
INSP - Concrete8/4/19988/5/19988/5/1998APART
Details
08/05/98 333 - footing ok pend special insp
INSP - Foundation7/27/19987/31/19987/30/1998APART
Details
07/31/98 333 - exterior ok
INSP - Concrete7/29/19987/30/19987/30/1998APART
Details
07/30/98 333 - footing ok
INSP - Foundation7/27/19987/29/19987/29/1998APART
Details
07/30/98 333 - stem wall ok
INSP - Concrete7/22/19987/24/19987/24/1998APART
DetailsJim Storey
07/24/98 301 - jack ###-#### rebar concrete placed w/special insp.pending report.
INSP - Concrete7/21/19987/23/19987/23/1998APART
DetailsJim Storey
07/22/98 301 - rebar special inspector on site. ###-#### placed w/ special insp. pending report.
INSP - Concrete7/21/19987/21/19987/21/1998PPART
DetailsJim Storey
07/21/98 301 - pending special insp.job re-bar ###-####
INSP - Foundation7/17/19987/20/19987/20/1998APART
DetailsJim Storey
07/20/98 301 - ready at 10 a.m. re-bar and concrete/ jack ###-#### FRMS-OK FORMS special insp report pending
INSP-Conference7/16/19987/16/19987/16/1998 PASS
Details
07/16/98 333 - talked corridors
INSP - Framing/Rough-in6/15/19986/15/19986/15/1998 PART
Details
/ / 333 - BOLTING EPOXY OK PEND SPECIAL INSP
INSP - Framing/Rough-in6/9/19986/9/19986/9/1998 PART
Details
/ / 333 - ROOF FRAMING COMPLETE
INSP - Framing/Rough-in6/8/19986/8/19986/8/1998 PART
Details
/ / 333 - ROOF ON NORTH HALF OK
INSP - Framing/Rough-in5/27/19985/27/19985/27/1998 PART
Details
/ / 333 - ROOF IN PROGRESS
INSP - Framing/Rough-in5/19/19985/19/19983/19/1998PPART
Details
05/19/98 333 - north half of roof ok to cover