Permit Information
Permit NumberBLD98-00177
StatusFinaled
Name ROGER CARLSON
Site Address 6001 CASSIA ST
Project NameBORAH SCHOOL REROOF
Customer Number 
ePlanReviewNo
Description
BORAH HIGH SCHOOL REROOF WING # 2* THE WORK CONSISTS OF A COMPLETE PREMANUFACTURED WOOD TRUSS OVERBUILD WITH ASPHALT SHINGLE ROOF, FIBERGLASS INSULATION AND E.I.F.S. GABLE ENDS AND CORNICE, INCLUDING NEW CONCRETE COLUMN. INTERIOR WORK CONSISTS OF 1 HOUR FIRE RATED UPGRADES TO CHEMISTRY AND ADJOINING STORAGE ROOM. WORK ALSO INCLUDES MISCELLANEOUS ELECTRICAL, MECHANICAL AND A COMPLETE FIRE SPRINKLER SYSTEM. PC#783-97
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final1/29/19992/1/19992/1/1999PPASS
DetailsCarl Dependahl
02/01/99 340 - dean- ###-#### fn early pm if possible per carl
INSP-Final Inspection1/28/19991/28/19991/28/1999PPASS
DetailsJoe Tawney
01/28/99 406 - BILL ###-#### REINSP OK FOR CERT OF COMPLETION ì
INSP - Final12/1/199812/1/199812/1/1998 FAIL
DetailsJoe Tawney
/ / 406 - REINSP FAIL SPARE PENDANT HEADS STILL NOT PROVIDED
INSP-Alarm Testing10/30/199810/30/199810/30/1998PPASS
Details
trip test and smoke detectors passed need spare heads
INSP - Final8/31/19988/31/19988/31/1998 PART
Details
/ / 338 - SIGNED THE TEMP COL . FIRE LIFE SAFETY C/N IN FORCE.. OK FOR
INSP-Final Inspection8/28/19988/29/19988/29/1998 PART
Details
dry system converted to wet, dampers locked closed
INSP - Final8/27/19988/28/19988/28/1998AFAIL
Details
sprinks and alarms, and dampers not up to snuff
INSP - Final8/28/19988/28/19988/28/1998 FAIL
Details
08/28/98 338 - c/n issued
INSP-Final Inspection8/27/19988/28/19988/28/1998AFAIL
Details
dry sprinkler system failed trip test, smoke dampers would not close, not connected to fire alarm system
INSP - Final8/27/19988/27/19988/27/1998 NR
DetailsJoe Tawney
/ / 406 - FINAL NOT READY
INSP - Final8/27/19988/27/19988/27/1998 NR
DetailsJoe Tawney
/ / 406 - FINAL NOT READY
INSP-Sprinkler Rough-in/Hydro8/24/19988/24/19988/24/1998 PART
DetailsJoe Tawney
/ / 406 - OK ON ABOVE GROUND HYDRO TEST EXC FDC & SUPPLY LINE TO BE TE UNDERGROUND OK ON CORRIDOR & CLASSROOM ROUGH IN
INSP - Framing/Rough-in7/15/19987/16/19987/16/1998APART
Details
07/16/98 338 - c/n issued no hold up problems