Permit Information
Permit NumberBLD98-00178
StatusFinaled
Name ROGER CARLSON
Site Address 6001 CASSIA ST
Project NameBORAH SCHOOL REROOF
Customer Number 
ePlanReviewNo
Description
BORAH HIGH SCHOOL REROOF WING # 3* THE WORK CONSISTS OF A COMPLETE PREMANUFACTURED WOOD TRUSS OVERBUILD WITH ASPHALT SHINGLE ROOF, FIBERGLASS INSULATION AND E.I.F.S. GABLE ENDS AND CORNICE, INCLUDING NEW CONCRETE COLUMN. INTERIOR WORK CONSISTS OF 1 HOUR FIRE RATED UPGRADES TO CHEMISTRY AND ADJOINING STORAGE ROOM. WORK ALSO INCLUDES MISCELLANEOUS ELECTRICAL, MECHANICAL AND A COMPLETE FIRE SPRINKLER SYSTEM. PC#783-97
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final1/29/19992/1/19992/1/1999PPASS
DetailsCarl Dependahl
02/01/99 340 - Dean- ###-#### early pm per carl for fn OK PER 338 & 406
INSP-Final Inspection1/28/19991/28/19991/28/1999PPASS
DetailsJoe Tawney
01/28/99 406 - BILL ###-#### REINSP OK FOR CERT OF COMPLETION ì
INSP - Final12/1/199812/1/199812/1/1998 FAIL
DetailsJoe Tawney
/ / 406 - REINSP FAIL SPARE PENDANT HEADS STILL NOT PROVIDED
INSP-Alarm Testing10/30/199810/30/199810/30/1998PPASS
Details
trip test and smoke detectors passed, need spare heads
INSP - Final8/31/19988/31/19988/31/1998 PART
Details
/ / 338 - MADE OK FOR TEMP OCC AS THE TEMP CONDITIONS ARE MED C/N IN F
INSP-Final Inspection8/28/19988/29/19988/29/1998 PART
Details
dry system converted to wet, dampers locked closed until alarms completed
INSP - Final8/27/19988/28/19988/28/1998AFAIL
Details
alarms/sprinks/dampers
INSP - Final8/28/19988/28/19988/28/1998 FAIL
Details
08/28/98 338 - c/n issued
INSP-Final Inspection8/27/19988/28/19988/28/1998AFAIL
Details
dry sprinklers failed trip time test, smoke dampers did not close, not connected to alarm system.
INSP - Final8/27/19988/27/19988/27/1998 NR
DetailsJoe Tawney
/ / 406 - FINAL NOT READY
INSP - Final8/26/19988/26/19988/26/1998 NR
DetailsJoe Tawney
/ / 406 - FINAL NOT READY
INSP-Sprinkler Rough-in/Hydro8/24/19988/24/19988/24/1998 PART
DetailsJoe Tawney
/ / 406 - OK ON ABOVE GROUND HYDRO TEST EXC FDC & SUPPLY LINE TO BE TE UNDERGOUND OK ON CORRIDOR & CLASSROOM ROUGH IN
INSP - Framing/Rough-in7/20/19987/20/19987/20/1998PPART
Details
07/20/98 338 - MADE OK TO RE-INSTALL LOCKERS
INSP - Framing/Rough-in7/15/19987/16/19987/16/1998APART
Details
07/16/98 338 - c/n issued truss eng etc.