Permit Information
Permit NumberBLD98-00550
StatusFinaled
Name ADA COUNTY
Site Address 650 W MAIN ST
Project NameADA COUNTY - BASEMNT
Customer Number 
ePlanReviewNo
Description
To remove existing 100 ton chiller unit from existing pad site in mechanical room an operating control. To install a new 100 ton chiller unit, controls, refrigerant detection system, fresh air and exhaust air ducts and accessory equipment while maintaining the integrity of the existing 2-hour shaft / mechanical room construction and existing opening protection into these areas. All per 1997 UMC, Chapter 11 and 1994 UFC, Article 64. New refrigerant to be used is R134a. This is not a Refrigeration Machinery Room per reported data from Musgrove Engineering, Preston Nance. Copy of report attached to plans. Prior to use of the new system, final inspection and approval is required from the electrical, plumbing, mechanical, fire departments and then structural inspector. Separate permits required. (P.C.#126-98)/drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/13/20001/18/20001/18/2000APASS
Details
per george maeok per plan 1/18/00 12:00:19 PM
BLD-Final1/12/20001/13/20001/13/2000ACANC
DetailsJim Storey
###-#### WARD
FIRE-Final Inspection1/11/20001/11/20001/11/2000PPASS
DetailsRick Jackson
Ada Co Basement Rick Emerson ###-####\###-#### ward
INSP - Final6/14/19996/15/19996/15/1999PFAIL
Details
06/15/99 338 - need to build per the approved assys
INSP-Final Inspection6/14/19996/15/19996/15/1999PFAIL
DetailsRick Jackson
MEETING 3:00 ###-#### need resubmittal
INSP-Final Inspection2/18/19992/18/19992/18/1999AFAIL
DetailsRick Jackson
requested by contractor - will go with Perry not installed per engineers plans - requesting compliance from manufacturer/engineer - per inspector 338
INSP-Final Inspection2/11/19992/11/19992/11/1999AFAIL
DetailsRick Jackson
damper frames bent; mullion installed per 2 hr requirement; sleeves not installed