INSP-Final Inspection | 4/20/1999 | 4/21/1999 | 4/21/1999 | A | PASS |
Rick Jackson
|
|
|
###-####//FIRE & LIFE SAFETY occ approved
|
Permanent Occupancy | | 4/21/1999 | 4/21/1999 | | DONE |
|
|
|
|
INSP - Final | 2/16/1999 | 2/16/1999 | 2/16/1999 | | PART |
|
|
|
02/12/99 338 - made ok for str. need P/W & CDHD signoffs
|
INSP-Final Inspection | 2/10/1999 | 2/12/1999 | 2/12/1999 | A | PART |
Rick Jackson
|
|
|
02/12/99 409 - bob ###-#### repair fire panel; remote indicators for duct detectors; knox box
|
INSP-Final Inspection | 1/15/1999 | 1/19/1999 | 1/19/1999 | A | PART |
Rick Jackson
|
|
|
01/19/99 409 - sprinkler hydro only - not a final. hydro pass
|
INSP-Final Inspection | 1/14/1999 | 1/15/1999 | 1/15/1999 | A | NR |
Rick Jackson
|
|
|
mike- ###-#### pager # fn insp backflow preventor problems - will call for rehydro of underground and overhead piping
|
INSP - Framing/Rough-in | 12/16/1998 | 12/16/1998 | 12/16/1998 | P | PASS |
|
|
|
12/16/98 333 - ###-#### FR- BOB- FIRE WALL INSP ok
|
INSP-Supply line flush | 11/12/1998 | 11/12/1998 | 12/12/1998 | P | PASS |
Mike Kinnear
|
|
|
MIKE ###-####
|
INSP - Framing/Rough-in | 11/13/1998 | 11/16/1998 | 11/16/1998 | A | PASS |
|
|
|
11/16/98 333 - FRAM-OK FRAMING
|
INSP-Sprinkler Rough-in/Hydro | 11/16/1998 | 11/16/1998 | 11/16/1998 | A | PART |
Rick Jackson
|
|
|
overhead and high ceiling areas checked - okay to cover restrooms. identified inspectors test to be in an accessible location (not above ceiling)
|
INSP - Framing/Rough-in | 11/12/1998 | 11/13/1998 | 11/13/1998 | P | FAIL |
|
|
|
11/13/98 333 - elec not passed
|
INSP-Sprinkler Rough-in/Hydro | 11/12/1998 | 11/12/1998 | 11/12/1998 | P | FAIL |
Mike Kinnear
|
|
|
Outside East canopy rouph-in for cover inspection had one sprinkler more than 6" below roof deck. Instructed fitter on raising same. Walked through and found blind spots of coverage due to roof ducts and possible underspacing in electrical room if sheetrocked to roof! Inspectors test valve above the ceiling! Was told to lower it for easy access.
|
INSP-Sprinkler Rough-in/Hydro | 11/12/1998 | 11/12/1998 | 11/12/1998 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 11/10/1998 | 11/10/1998 | 11/10/1998 | P | PART |
Rick Jackson
|
|
|
okay to cover north and south exterior soffit
|
INSP - Framing/Rough-in | 11/6/1998 | 11/9/1998 | 11/9/1998 | A | PART |
|
|
|
11/09/98 333 - EXTERIOR WALLS OK ONLY
|
INSP - Framing/Rough-in | 10/22/1998 | 10/23/1998 | 10/23/1998 | A | PART |
|
|
|
10/23/98 333 - SHEAR WALL ok
|
INSP - Foundation | 8/27/1998 | 8/28/1998 | 8/28/1998 | A | |
|
|
|
bob ###-####pager rebar
|