Permit Information
Permit NumberBLD98-01017
StatusExpired
Name BOISE HIGH SCHOOL
Site Address 1010 W WASHINGTON ST
Project NameBOISE HIGH SCHOOL
Customer Number 
ePlanReviewNo
Description
BOISE HIGH SCHOOL * RENOVATION OF MAIN CLASSROOM BUILDING ON ALL FLOORS AND BASEMENT. OCCUPANCY ON THE THRID FLOOR AND SUB BASEMENT WILL BE STORAGE ONLY. BUILDING WILL BE FULLY FIRE SPRINKLERED. ALL WORK IS PER APPROVED PLANS ON FILE. NO NEW SQUARE FOOTAGE PROPSOED UNDER THIS PERMIT. DR-106-93 MOD, CU-87-93 MOD PC#241-98. FIRE SPRINKLERS USED FOR ONE-HOUR SUBSTITUTION AND FOR NON-RATED CORRDIORS PER EXCEPTION IN THE UCBC. THIS BUILDING IS OFFICALLY CONSIDERED AS A HISTORICAL BUILDING.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final8/13/19998/16/19998/16/1999PPASS
Details
08/16/99 338 - made ok for finall/c issued # 16436
INSP-Final Inspection8/13/19998/16/19998/16/1999APASS
DetailsRick Jackson
DAN ###-#### (BOISE HIGH #-THEY WILL PAGE DAN) occupancy approved
INSP - Final8/4/19998/5/19998/5/1999AFAIL
Details
x-it signage not correct sub basement. doors in the exit path cannot lock c/n issued conference with stubbs
INSP-Conference8/5/19998/5/19998/5/1999PPART
DetailsRick Jackson
met with Perry about exit signs in sub-basement area; they wern't installed with the architects request
INSP-Final Inspection8/2/19998/2/19998/2/1999PFAIL
DetailsRick Jackson
exit signs still installed in wrong locations in sub-basement area
INSP-Conference7/22/19997/22/19997/22/1999PPART
DetailsRick Jackson
discussed with architect location of exit signs in sub-basement area
INSP-Final Inspection7/16/19997/16/19997/16/1999PFAIL
DetailsRick Jackson
exit signs
INSP-Final Inspection7/15/19997/15/19997/15/1999PPART
DetailsRick Jackson
LISA ###-#### sprinkler system all complete
INSP-Alarm Testing6/28/19996/28/19996/28/1999 FAIL
DetailsRick Jackson
/ / 409 - ALARMS COMPLETE EXCEPT FOR AHU DETECTORS FOR SHUTDOWM; FIRE
INSP - Framing/Rough-in5/25/19995/25/19995/25/1999PPART
Details
05/25/99 338 - ok for east wing border tiles to be dropped clouds need w
INSP - Framing/Rough-in4/26/19994/26/19994/27/1999PPART
Details
04/26/99 338 - madeok for the shaft
INSP - Framing/Rough-in4/22/19994/23/19994/23/1999APART
Details
04/23/99 338 - made ok to cover the shaft
INSP - Framing/Rough-in4/14/19994/14/19994/15/1999PPART
Details
04/14/99 338 - madeok to cover at the east wing
INSP - Framing/Rough-in3/31/19994/2/19994/5/1999APART
Details
04/02/99 338 - made ok for the west wing
INSP-Final Inspection3/26/19993/26/19993/26/1999PPART
DetailsRick Jackson
temp occ approved for limited areas; exiting okay
INSP-Alarm Testing3/22/19993/22/19993/22/1999APART
DetailsRick Jackson
tested elevator and recall -okay; alarm panels are networked and appear to work as main building has dialer and can silence from there. devices are "main" or "I/A" building
INSP-Alarm Testing3/18/19993/18/19993/18/1999PNR
DetailsRick Jackson
not ready for elevator, networking - rescheduled for 3/22
INSP-Conference3/16/19993/16/19993/16/1999APART
DetailsRick Jackson
standpipes to remain connected until fully sprinklered; informed jim Stubbs of alarm requirements for network
INSP - Framing/Rough-in2/26/19993/1/19993/2/1999APART
Details
03/01/99 338 - NOT READY FOR OK TO DROP IN TILES
INSP-Conference2/18/19992/18/19992/18/1999PPART
DetailsRick Jackson
requirements for occupying completed areas until project is completed
INSP - Framing/Rough-in2/8/19992/9/19992/9/1999APART
Details
###-#### JIM rescheduled for 7:00 02/10/99
INSP - Framing/Rough-in2/4/19992/5/19992/5/1999AFAIL
Details
02/05/99 338 - ###-#### jim\ceiling grid no answer in the contact # no r
INSP-Sprinkler Rough-in/Hydro2/2/19992/2/19992/2/1999 FAIL
DetailsRick Jackson
/ / 409 - EXPOSED COMBUSTIBLES NOT SPRINKLERED OR COVERED
INSP-Conference11/23/199811/24/199811/24/1998APART
DetailsRick Jackson
with architect and general to determine sprinklering or covering combustibles above dropped ceiling - they will cover
INSP-Sprinkler Rough-in/Hydro11/23/199811/23/199811/23/1998AFAIL
DetailsRick Jackson
basement and first floor only c/n to be issued
INSP-Sprinkler Rough-in/Hydro11/16/199811/16/199811/16/1998PFAIL
DetailsRick Jackson
checked sprinkler piping in basement - numerous problems. requested shilo to clean up areas and they requested us back to re-inspect on 11/20
INSP-Supply line flush11/13/199811/13/199811/13/1998APASS
DetailsRick Jackson
underground flush okay - new PIV installed needs hydro
INSP - Framing/Rough-in11/4/199811/5/199811/5/1998PPART
DetailsWes Worcester
11/05/98 342 - JIM ###-####- SMOKE CEILING AROUND PIPES-CHECK CHASES
INSP - Framing/Rough-in10/23/199810/23/199810/23/1998PPART
Details
10/23/98 333 - basement ceiling and second fl frame ok
INSP-Sprinkler Rough-in/Hydro10/5/199810/5/199810/5/1998PPART
DetailsRick Jackson
sprinklers not needed under south canopy (awaiting letter from school about keeping combustibles from under canopy); sway bracing needed in basement; heads overspaced in basement bathroom
INSP - Framing/Rough-in9/22/19989/23/19989/23/1998PPART
Details
09/23/98 333 - basement ok
INSP-Sprinkler Rough-in/Hydro9/11/19989/11/19989/11/1998AFAIL
DetailsRick Jackson
sprinkler system designed for over 100 psi - hangers not within 12 inches from end of pipe. obstructed heads in basement. c/n issued
INSP - Framing/Rough-in9/1/19989/1/19989/1/1998 PART
Details
09/01/98 333 - grid in baths ok
INSP - Framing/Rough-in8/31/19989/1/19989/1/1998APART
Details
09/01/98 333 - bath grid ok
INSP - Framing/Rough-in8/6/19988/6/19988/6/1998PPART
Details
08/06/98 333 - south wing ok
INSP - Framing/Rough-in7/30/19987/31/19987/31/1998APART
Details
07/31/98 333 - bath ok
INSP - Framing/Rough-in7/24/19987/27/19987/27/1998APART
Details
07/27/98 333 - east bathrooms ok to cover
INSP - Final7/23/19987/24/19987/24/1998ANR
DetailsJim Storey
07/24/98 301 - JIM STUBBS ###-#### ok to cover bathroom common plumbing floor
INSP - Framing/Rough-in7/15/19987/16/19987/16/1998APART
Details
07/16/98 333 - first floor
INSP - Framing/Rough-in7/1/19987/2/19987/2/1998APART
Details
07/02/98 333 - ceiling in east half of south wing ok
INSP - Framing/Rough-in6/29/19986/29/19986/29/1998PPART
Details
06/29/98 333 - corridor wall ok
INSP - Framing/Rough-in6/26/19986/26/19986/26/1998PPASS
Details
06/26/98 333 - south east side of corridor ok
INSP - Framing/Rough-in6/17/19986/17/19986/17/1998PPASS
Details
06/17/98 333 - EAST SIDE OF SOUTH WING OFFICES
INSP - Foundation6/12/19986/15/19986/15/1998APASS
Details
06/15/98 333 - FTG -OK FOOTING
INSP - Foundation6/10/19986/10/19986/10/1998APART
Details
06/10/98 333 - in progress