INSP - Final | 3/4/1999 | 3/5/1999 | 3/5/1999 | A | PASS |
Russ Owen
|
|
|
03/05/99 407 - tom ###-####
|
INSP - Final | 3/1/1999 | 3/1/1999 | 3/1/1999 | P | PART |
|
|
|
03/01/99 338 - need to remove or protect vapor barrier on the roof insul
|
INSP-Final Inspection | 2/26/1999 | 2/26/1999 | 2/26/1999 | A | PASS |
Rick Jackson
|
|
|
occ approved
|
INSP-Final Inspection | 1/21/1999 | 1/21/1999 | 1/21/1999 | P | PART |
Rick Jackson
|
|
|
hydrant must be turned to face driveway
|
INSP - Final | 1/19/1999 | 1/19/1999 | 1/19/1999 | P | FAIL |
Wes Worcester
|
|
|
01/19/99 342 - PUMP HOUSE...TOM ###-#### need fire
|
INSP-Final Inspection | 1/19/1999 | 1/19/1999 | 1/19/1999 | A | FAIL |
Rick Jackson
|
|
|
01/19/99 409 - alarm panel not working
|
INSP-Final Inspection | 11/18/1998 | 11/19/1998 | 11/19/1998 | A | FAIL |
Rick Jackson
|
|
|
scheduled for 9:00 ? generator not maintaining constant voltage; filters for copper lines; pump tested okay for flow; still need to test off-site monitoring, bell, hydrant hook-up
|
INSP-Sprinkler Rough-in/Hydro | 11/17/1998 | 11/18/1998 | 11/18/1998 | A | FAIL |
Rick Jackson
|
|
|
PUMP HOUSE..LONNIE WILL CALL TO SCHEDULE...###-#### couldn't pump at 100 percent; transfer to generator power not working; smoke detector too low
|
INSP-Sprinkler Rough-in/Hydro | 10/20/1998 | 10/20/1998 | 10/20/1998 | A | PART |
Rick Jackson
|
|
|
observed vault and screens - okay; measured pond size - okay. TVFP to install backplate on 10/21
|
INSP - Foundation | 10/15/1998 | 10/15/1998 | 10/15/1998 | P | PASS |
|
|
|
10/15/98 333 - FDN -OK FOUNDATION
|
INSP - Foundation | 10/15/1998 | 10/15/1998 | 10/15/1998 | P | FAIL |
Wes Worcester
|
|
|
10/15/98 342 - LANSE ###-#### poured w/o inspection
|