Permit NumberBLD98-02235
StatusExpired
Name ST LUKES STL990333
Site Address 190 E BANNOCK ST
Project NameST LUKES-2ND FLR
Customer NumberSTL990333
ePlanReviewNo
Description
To remodel selective areas of second floor West, Central, South & North wings as indicated on approved plans to create a Perinatology administrative support area as part of the second floor pediatrics care / birthing unit of SLRMC. To create staff sleeping rooms, offices and accessory support areas. Work to include rerouting of portion of existing rated exit corridor, removing & infilling door openings into the corridor, creation of office & exam rooms with a new hallway access separate from the corridor, a new accessible restroom/shower facility, new residence & physician lounge & expand women's locker room. To upgrade electrical, mechanical & plumbing for new suite areas. NOTE: This building is fully fire sprinklered. (P.C.#507-98)/drs 11/22/99 - SLRMC PRESENTED PLANS FOR MODIFICATION OF PROPOSED USE OF 2ND FLOOR CENTRAL FROM PARENATOLOGY ADMINISTRATIVE OFFICES TO PATIENT ROOMS, NURSING STATION, NURSERY HOLDING & SUPPORT AREAS. TO CONSTRUCT 3 NEW ACCESSIBLE PATIENT AND REST ROOMS; NEW NURSE STATION; NEW NURSERY HOLDING ROOM; NEW STAFF LOCKER ROOM, NEW NUTRITION ROOM & SUPPORT AREAS. TO UPGRADE LIFE SAFETY FEATURES FOR PATIENT ROOMS & FIRE SEPARATION BY CONSTRUCTION & OPENING / PENETRATION UPGRADES. ALL CONSTRUCTION TO BE NONCOMBUSTIBLE FRAMING WITH FIRE CODE SHEETROCK COVER, ETC. AS APPLICABLE TO TYPE I-FR CONSTRUCTION, SECTION 602 UBC. ALL PER APPROVED PLANS NOTES & PLAN REVIEW COMMENTS ATTACHED. NOTE: BUILDING IS FULLY SPRINKLED. PC#99-911/drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Conference9/24/20019/24/20019/24/2001PPART
DetailsCarl Dependahl
Added by Inspector: 340 On 9/24/2001 1:53:36 PM re modification..to reinstall med gas at patient rooms
BLD-Final6/7/20016/8/20016/8/2001APASS
DetailsCarl Dependahl
Carl this is a StLukes job that I came across and it is expired...George said to send you an inspection to check on.....thanks; shows an l/c issued by Perry...probably just not turned in at office for official final?? 6/7/2001 4:49:48 PM
BLD-Final7/13/20007/14/20007/14/2000APASS
Details
Scheduled by Inspector: 338 On 7/13/2000 dan 3812023 c/c# 19401 7/14/2000 9:54:48 AM
BLD-Final7/12/20007/13/20007/13/2000ACANC
Details
Scheduled by a contractor via Hello! on 07/12/2000 at 13:31:19. Contact: ###-####. reschedule fr 7'14'2k 7/13/2000 2:16:35 PM
BLD-Final7/13/20007/13/20007/13/2000ACANC
Details
Scheduled by Inspector: 338 On 7/13/2000 dan 381 2023
BLD-Final6/1/20006/2/20006/2/2000AFAIL
Details
Scheduled by a contractor via Hello! on 06/01/2000 at 12:50:47. Contact: ###-####. NEED 60 MIN DOORS AT 2014 AND 2016, CLEAN SUPPLIES AND SOILED UTILITY 6/5/00 9:47:11 AM
FIRE-Final Inspection5/25/20005/26/20005/26/2000APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/25/2000 at 14:58:17. Contact: ###-####.
FIRE-Final Inspection5/17/20005/18/20005/18/2000AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/17/2000 at 08:59:39. Contact: ###-####. Tested detectors for fire dampers- okay; penetrations need repair; rated doors not completed. 5/18/00 3:17:49 PM
BLD-Framing/Rough-in5/1/20005/2/20005/2/2000APASS
Details
###-#### ok to cover with ele and plmg approvals need to check fire caulking of the above ceiling level at the grid insp 5/3/00 10:09:56 AM
BLD-Framing/Rough-in2/29/20002/29/20002/29/2000PPART
DetailsJim Storey
Scheduled by a contractor via Hello! on 02/29/2000 at 09:15:57. Contact: ###-####. Pagent rm. ceiling rm. 3/1/00 11:12:31 AM
INSP - Final5/20/19995/21/19995/21/1999APART
Details
05/21/99 338 - ok to use phase ! areas
INSP-Final Inspection4/14/19994/15/19994/15/1999AFAIL
DetailsRick Jackson
Scheduled by Hello!. Contact phone is [3812023]. smoke detector overspaced in room 141 where coverage is needed for shaft/duct/damper coverage; damper requires access door
INSP - Wall cover1/27/19991/28/19991/28/1999APART
Details
need to reinspect for floor above penetrations and rated wall fix at the heater cabinet at ext wall.
INSP - Wall cover12/16/199812/17/199812/17/1998APART
Details
12/17/98 333 - loung ok