Permanent Occupancy | | 3/15/2000 | 3/15/2000 | | DONE |
|
|
|
|
BLD-Final | 3/14/2000 | 3/14/2000 | 3/14/2000 | P | PASS |
Tom Arcoraci
|
|
|
gene ###-#### early pm
|
BLD-Final | 3/10/2000 | 3/13/2000 | 3/13/2000 | A | FAIL |
Russ Owen
|
|
|
late pm gene ###-####.. Needs continious handrail at ramp and electrical.
|
FIRE-Final Inspection | 3/10/2000 | 3/13/2000 | 3/13/2000 | A | PASS |
Joe Tawney
|
|
|
gene ###-#### Reinsp ok for perm. occ. 3/14/00 1:52:10 PM
|
FIRE-Final Inspection | 3/8/2000 | 3/9/2000 | 3/9/2000 | A | FAIL |
Joe Tawney
|
|
|
gene ###-#### Final fail need alarm system add 1 detector & remove 1 door hold open. 3/9/00 2:16:47 PM
|
BLD-Framing/Rough-in | 3/7/2000 | 3/7/2000 | 3/7/2000 | P | PASS |
Tom Arcoraci
|
|
|
###-#### call first to meet there
|
BLD-Framing/Rough-in | 2/16/2000 | 2/16/2000 | 2/16/2000 | P | PART |
Tom Arcoraci
|
|
|
###-#### 2 hr wall incomplete. 2/17/00 9:07:57 AM
|
BLD-Framing/Rough-in | 2/11/2000 | 2/14/2000 | 2/14/2000 | A | PART |
Carl Dependahl
|
|
|
Framing R/I for cover. Gene; ###-####. 408's area, WIP ok to continue; need both layers @ 2hr wall & firestops @ plates. 2/14/00 2:15:37 PM
|
BLD-Framing/Rough-in | 2/8/2000 | 2/9/2000 | 2/9/2000 | A | PART |
Tom Arcoraci
|
|
|
gene ###-#### 2 hour wall incomplete.
|
FIRE-Sprinkler Rough-in | 2/9/2000 | 2/9/2000 | 2/9/2000 | P | PART |
Joe Tawney
|
|
|
###-#### sprinkler rough in ok to cover.
|
BLD-Framing/Rough-in | 2/2/2000 | 2/3/2000 | 2/3/2000 | A | FAIL |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 02/02/2000 at 16:15:27. Contact: . 2 hr wall incomplete. 2/4/00 11:13:19 AM
|
FIRE-Final Inspection | 2/3/2000 | 2/3/2000 | 2/3/2000 | P | FAIL |
Joe Tawney
|
|
|
Gene ###-#### Need sprinkler plans to cover new addition. 2/7/00 8:38:16 AM
|
BLD-Framing/Rough-in | 2/2/2000 | 2/2/2000 | 2/2/2000 | P | FAIL |
Tom Arcoraci
|
|
|
###-#### gene --r/i --call 1st before insp incomplete 2hr wall 2/3/00 9:20:54 AM
|
BLD-Framing/Rough-in | 1/28/2000 | 1/28/2000 | 1/28/2000 | P | FAIL |
Tom Arcoraci
|
|
|
Gene; ###-####. Please call before insp. see c/n 1 hr and 2hr problems 1/31/00 8:31:30 AM
|
BLD-Framing/Rough-in | 1/11/2000 | 1/11/2000 | 1/11/2000 | P | FAIL |
Tom Arcoraci
|
|
|
Gene ###-####. No elec. , no plumbing, no fire sprkl.
|
BLD-Framing/Rough-in | 11/10/1999 | 11/10/1999 | 11/10/1999 | P | FAIL |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 11/10/1999 at 08:53:53. Contact: ###-####. Ok to side ext., Re-check 2hr. Wall.
|
BLD-Framing/Rough-in | 11/1/1999 | 11/1/1999 | 11/1/1999 | P | FAIL |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 11/01/1999 at 09:03:55. Contact: ###-####. See C/Notice
|
BLD-Foundation | 10/12/1999 | 10/12/1999 | 10/12/1999 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 10/12/1999 at 09:28:09. Contact: ###-####. Ramp wall ok only rest of wall poured without insp. See C/Notice
|
BLD-Foundation | 9/29/1999 | 9/30/1999 | 9/30/1999 | A | PART |
Tom Arcoraci
|
|
|
Stan ###-#### FT ok
|