Permanent Occupancy | | 2/15/2000 | 2/15/2000 | | DONE |
|
|
|
|
BLD-Final | 2/14/2000 | 2/14/2000 | 2/15/2000 | P | PASS |
Carl Dependahl
|
|
|
late pm ###-#### Card to owner. 2/15/00 1:17:32 PM
|
FIRE-Final Inspection | 2/11/2000 | 2/14/2000 | 2/14/2000 | A | PASS |
Joe Tawney
|
|
|
Scheduled by a contractor via Hello! on 02/11/2000 at 16:33:47. Contact: ###-####. Reinsp. ok for permanant occ. 2/14/00 2:29:09 PM
|
BLD-Final | 2/4/2000 | 2/4/2000 | 2/4/2000 | P | FAIL |
Carl Dependahl
|
|
|
1/800/526/7811 sheila --ann taylor store -fn keep c/n failed fire
|
FIRE-Final Inspection | 1/31/2000 | 2/4/2000 | 2/4/2000 | A | FAIL |
Joe Tawney
|
|
|
###-#### Sheila Prater Reinsp. fail manual flush bolts on double door leaf. 2/7/00 8:55:33 AM
|
BLD-Final | 10/4/1999 | 10/4/1999 | 10/4/1999 | A | PART |
Carl Dependahl
|
|
|
Anne Taylor (tenant) - lower level #1087; ok for t/o,pending fire approval of front door hdwe...lock is < 15" from floor, doesn't meet ADA.
|
INSP-Alarm Testing | 5/18/1999 | 5/19/1999 | 5/19/1999 | A | PASS |
Rick Jackson
|
|
|
Scheduled by Hello!. smoke detector operated smoke evac okay
|
INSP-Final Inspection | 5/19/1999 | 5/19/1999 | 5/19/1999 | A | PART |
Rick Jackson
|
|
|
temp occ approved - need door hardware per joe's c/n
|
INSP-Alarm Testing | 5/17/1999 | 5/18/1999 | 5/18/1999 | A | PART |
Joe Tawney
|
|
|
05/18/99 406 - DETECTORS TESTED OK BUT SMOKE EXH DAMPER FAILED TO OPEN
|
INSP-Final Inspection | 5/17/1999 | 5/18/1999 | 5/18/1999 | A | FAIL |
Joe Tawney
|
|
|
05/18/99 406 - FINAL FAIL SMOKE/EXH DAMPER, DOOR HDWRE, FIRE EXT
|
INSP - Framing/Rough-in | 5/1/1999 | 5/3/1999 | 5/3/1999 | A | PART |
Tom Arcoraci
|
|
|
05/03/99 408 - sesmic pod ok
|
INSP - Framing/Rough-in | 4/23/1999 | 4/26/1999 | 4/26/1999 | P | PART |
Carl Dependahl
|
|
|
04/26/99 340 - ###-#### DOUG//CEILING GRID; need seismic at back rm, res
|
INSP - Framing/Rough-in | 3/31/1999 | 4/1/1999 | 4/1/1999 | A | PART |
Carl Dependahl
|
|
|
04/01/99 340 - Scheduled by Hello!. Contact phone is [3778497]....seal
|