Permit NumberBLD99-00329
StatusFinaled
Name PRICE FINANCING PTNRSHIP L P
Site Address 350 N MILWAUKEE ST Unit: 1087
Project NameBTS - #1087
Customer Number 
ePlanReviewNo
Description
To construct a 3,995 sq.ft. retail tenant per approved plans on file. Work to include, construction of a new storefront system, new entry doors, construction of a new one-hour fire-resistive exit corridor, finish tenant demising wall, new non-rated interior partitions to separate sales area from stockroom. construction of seven new fitting rooms one to be fully accessible, New accessible restroom, Miscelaneous interior finishes. NOTE: This building is fully fire sprinklered and has a smoke control system. Any alterations or modification to the fire sprinkler system shall be per NFPA #13 as regulated by the fire department. Smoke evacuation system shall be connected to and maintained under the original system per UBC 1985 code. (P.C.#095-99)*RMH* DEMO WAS PERFORMED UNDER BLD99-0491
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 2/15/20002/15/2000 DONE
Details
BLD-Final2/14/20002/14/20002/15/2000PPASS
DetailsCarl Dependahl
late pm ###-#### Card to owner. 2/15/00 1:17:32 PM
FIRE-Final Inspection2/11/20002/14/20002/14/2000APASS
DetailsJoe Tawney
Scheduled by a contractor via Hello! on 02/11/2000 at 16:33:47. Contact: ###-####. Reinsp. ok for permanant occ. 2/14/00 2:29:09 PM
BLD-Final2/4/20002/4/20002/4/2000PFAIL
DetailsCarl Dependahl
1/800/526/7811 sheila --ann taylor store -fn keep c/n failed fire
FIRE-Final Inspection1/31/20002/4/20002/4/2000AFAIL
DetailsJoe Tawney
###-#### Sheila Prater Reinsp. fail manual flush bolts on double door leaf. 2/7/00 8:55:33 AM
BLD-Final10/4/199910/4/199910/4/1999APART
DetailsCarl Dependahl
Anne Taylor (tenant) - lower level #1087; ok for t/o,pending fire approval of front door hdwe...lock is < 15" from floor, doesn't meet ADA.
INSP-Alarm Testing5/18/19995/19/19995/19/1999APASS
DetailsRick Jackson
Scheduled by Hello!. smoke detector operated smoke evac okay
INSP-Final Inspection5/19/19995/19/19995/19/1999APART
DetailsRick Jackson
temp occ approved - need door hardware per joe's c/n
INSP-Alarm Testing5/17/19995/18/19995/18/1999APART
DetailsJoe Tawney
05/18/99 406 - DETECTORS TESTED OK BUT SMOKE EXH DAMPER FAILED TO OPEN
INSP-Final Inspection5/17/19995/18/19995/18/1999AFAIL
DetailsJoe Tawney
05/18/99 406 - FINAL FAIL SMOKE/EXH DAMPER, DOOR HDWRE, FIRE EXT
INSP - Framing/Rough-in5/1/19995/3/19995/3/1999APART
DetailsTom Arcoraci
05/03/99 408 - sesmic pod ok
INSP - Framing/Rough-in4/23/19994/26/19994/26/1999PPART
DetailsCarl Dependahl
04/26/99 340 - ###-#### DOUG//CEILING GRID; need seismic at back rm, res
INSP - Framing/Rough-in3/31/19994/1/19994/1/1999APART
DetailsCarl Dependahl
04/01/99 340 - Scheduled by Hello!. Contact phone is [3778497]....seal