Permanent Occupancy | | 10/8/1999 | 10/8/1999 | | DONE |
|
|
|
|
BLD-Final | 10/6/1999 | 10/7/1999 | 10/7/1999 | P | PASS |
|
|
|
Scheduled by a contractor via Hello! on 10/06/1999 at 13:24:32. Contact: ###-####. Correction notice removed ok for perm occ
|
FIRE-Alarm Testing | 10/6/1999 | 10/6/1999 | 10/6/1999 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/06/1999 at 10:19:56. Contact: ###-####.
|
FIRE-Final Inspection | 10/6/1999 | 10/7/1999 | 10/6/1999 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/06/1999 at 11:28:04. Contact: ###-####.
|
FIRE-Final Inspection | 10/6/1999 | 10/6/1999 | 10/6/1999 | P | PASS |
Rick Jackson
|
|
|
|
FIRE-Alarm Testing | 9/23/1999 | 9/27/1999 | 9/27/1999 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 09/23/1999 at 15:58:26. Contact: ###-####. Couldn't test alarms/duct detectors for AHV's
|
INSP - Final | | | 7/16/1999 | | PART |
|
|
|
07/16/99 338 - Scheduled by Hello!. Contact phone is [8673334].
|
INSP-Final Inspection | 7/15/1999 | 7/15/1999 | 7/15/1999 | A | FAIL |
Rick Jackson
|
|
|
alarm panel not complete
|
INSP - Final | 7/12/1999 | 7/12/1999 | 7/12/1999 | P | FAIL |
|
|
|
07/13/99 338 - previous c/n not completed
|
INSP - Final | 7/6/1999 | 7/6/1999 | 7/6/1999 | P | FAIL |
|
|
|
07/06/99 338 - c/n issued rails and dorr ratings cabo ansi in bathrooms
|
INSP-Final Inspection | 7/6/1999 | 7/6/1999 | 7/6/1999 | A | PART |
Rick Jackson
|
|
|
temp occ approved - need info on placement of duct detectors and 3 units didn't shut down
|
INSP-Conference | 6/25/1999 | 6/25/1999 | 6/25/1999 | P | PART |
Rick Jackson
|
|
|
Conference John Walker ###-#### exit doors have wrong type hardware - discussed with plan review and contractor - contractor to get with architect
|
INSP - Framing/Rough-in | 6/4/1999 | 6/4/1999 | 6/4/1999 | P | PART |
|
|
|
06/04/99 338 - madeok to cover with ele and plmg approvals
|
INSP - Framing/Rough-in | 5/27/1999 | 5/27/1999 | 6/1/1999 | P | CANC |
Jim Storey
|
|
|
05/27/99 301 - p paine
|
INSP - Framing/Rough-in | 5/27/1999 | 5/28/1999 | 5/28/1999 | A | PART |
|
|
|
05/28/99 338 - MADE OK TO COVER THE FRAMED OVER STEEL CLOUMNS AND THE FR
|