Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberBLD99-03212
StatusFinaled
Name PATTERSON COMPANY
Site Address 141 E SKYLARK DR
Project Name 
Customer Number 
ePlanReviewNo
Description
To construct a 283 sq. ft. two story addition at rear of single family dwelling per approved plans, all engineering and attached requirement lists. Work to include remodel of upper/level floors with revised exterior elevations. Smoke detectors to be installed in all bedrooms and hallways leading to the same. Setbacks ok per Roger Jones (P&Z 10-21-99) DJO
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/21/20172/21/20172/21/2017PDONE
DetailsTony Young
Call to meet // Debra Phone #: ###-####// project was done prior,, maintenance for cable is maintained by owner,, spacing is 4",, verified smoke detector locations
DOC - Permit Finaled2/21/20172/21/20172/21/2017PPASS
DetailsTony Young
done
BLD-Other2/16/20172/16/20172/16/2017PPEND
DetailsBob Archibald
Ok for reactivation with 2hr addmin fee to obtain final inspection.
BLD-Conference8/7/20008/7/20008/7/2000APART
Details
with 305 to discuss rail system proposed repair with 305,301, 325 and dwayne carver, parts installed will be acceptable if they are secured at the bottom and are no farther apart than the two that are installed for demonstatiion. 8/7/2000 5:02:33 PM
BLD-Conference6/14/20006/14/20006/14/2000APART
Details
received letter from architect my response is attached. his letter in file.
BLD-Conference6/7/20006/7/20006/7/2000APASS
Details
as there has been no contact (letter from) Mr. Carver The attached letter is being sent to his office.
BLD-Conference5/31/20005/31/20005/31/2000 PASS
Details
met on the jobsite with 305, dwayne carver, on the lack of compliance for the cable guardrails used for intermediate fall protection. Mr carver is to draft a letter to the city requesting acceptance standards for the new rail of the elevated deck. 305and myself are to research and call icbo for more info.
BLD-Framing/Rough-in5/31/20005/31/20005/31/2000PFAIL
Details
railing Chris Larson ###-#### please call before you go out correction still stands 5/31/00 3:35:13 PM
BLD-Final5/24/20005/25/20005/25/2000AFAIL
Details
Scheduled by a contractor via Hello! on 05/24/2000 at 11:53:33. Contact: ###-####. 97-ubc 509.3 guardrail intermediates are cables 3 7/8" o.c. and are too light and do not have enough available tension to be complying 5/26/00 6:59:44 AM
BLD-Energy code compliance3/17/20003/17/20003/17/2000PPASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 03/17/2000 at 09:51:14. Contact: ###-####.
BLD-Framing/Rough-in3/14/20003/15/20003/15/2000AFAIL
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 03/14/2000 at 11:11:15. Contact: ###-####. Not ready. 3/16/00 1:28:52 PM
BLD-Framing/Rough-in3/15/20003/15/20003/15/2000PPASS
DetailsRuss Owen
rescheduled from this am ok to insulate 3/16/00 1:44:23 PM
BLD-Framing/Rough-in2/11/20002/11/20002/11/2000PPART
DetailsRuss Owen
###-#### Ext. only C/N on job card. 2/14/00 1:59:55 PM
BLD-Footing1/6/20001/6/20001/6/2000PPASS
DetailsRuss Owen
Scheduled by a contractor via Hello! on 01/06/2000 at 10:27:09. Contact: ###-####. Interior footings.
BLD-Foundation12/8/199912/9/199912/9/1999APASS
DetailsRuss Owen
Scheduled by a contractor via Hello! on 12/08/1999 at 09:42:36. Contact: ###-####.
BLD-Footing11/8/199911/10/199911/10/1999APASS
DetailsJim Storey
scott---###-#### cell ft -behind house Footings ok.